To calculate a U-value (thermal transmittance) from thermal conductivity (k-value), use the formula U = 1 / Rtotal, where Rtotal is the sum of the thermal resistances of each material layer (R = thickness / k) plus any surface resistances. Enter the layer thicknesses and their thermal conductivities below to get the U-value in W/m²·K, along with the total R-value.
Formula
The U-value is the inverse of the total thermal resistance (Rtotal). For a wall made of several layers, the total resistance is the sum of each layer’s resistance plus the surface resistances on the inside and outside.
U = 1 / (Rsi + R1 + R2 + … + Rn + Rso)
Where each layer’s resistance is:
Rlayer = d / k
- U – thermal transmittance in W/(m²·K). Lower is better for insulation.
- Rsi – inside surface resistance, typically 0.13 m²·K/W for vertical surfaces (still air).
- Rso – outside surface resistance, typically 0.04 m²·K/W for exposed exterior (windy).
- d – thickness of the layer in meters (m).
- k – thermal conductivity of the material in W/(m·K). Lower means better insulation.
This calculator sums the resistances of up to three layers plus the two surface resistances. If you have fewer layers, set the extra thickness to 0.001 m and conductivity to a large number (e.g., 1000) so that layer’s resistance becomes negligible.
Worked Example
Using the default values: a 0.1 m layer of mineral wool (k = 0.04), a 0.15 m layer of rigid foam (k = 0.035), and a 0.012 m layer of plasterboard (k = 0.5), with inside surface resistance 0.13 and outside 0.04.
- R1 = 0.1 / 0.04 = 2.5 m²·K/W
- R2 = 0.15 / 0.035 = 4.2857 m²·K/W
- R3 = 0.012 / 0.5 = 0.024 m²·K/W
- Rtotal = 0.13 + 2.5 + 4.2857 + 0.024 + 0.04 = 6.9797 m²·K/W
- U = 1 / 6.9797 = 0.1433 W/(m²·K)
The calculator rounds to 0.143 W/(m²·K) and shows Rtotal = 6.980 m²·K/W.
Assumptions
- Steady-state heat flow (no thermal bridging, no moisture movement).
- Each layer is homogeneous and has a constant thermal conductivity.
- Surface resistances are typical values for vertical building elements; actual values depend on emissivity and air speed.
- Layers are in perfect contact – no air gaps between them.
- The total resistance is the simple sum of resistances (series model).
Why Thermal Conductivity Is Not the Same as U-Value
Thermal conductivity (k) is a material property – it tells you how well a specific material conducts heat. The U-value is a system property – it tells you how well a whole building element (wall, roof, window) transmits heat, considering all its layers and the air films on both sides. A single material’s k-value alone cannot give you the U-value because thickness matters: a 10 cm slab of foam has a higher R than a 5 cm slab of the same foam. The U-value also includes the surface resistances, which depend on whether the element is indoors, outdoors, vertical, horizontal, or exposed to wind.
For example, a brick has k ≈ 0.77 W/(m·K). A 20 cm brick wall has R = 0.2 / 0.77 = 0.26 m²·K/W. Add surface resistances (0.13 + 0.04) to get Rtotal = 0.43, so U ≈ 2.33 W/(m²·K) – a poor insulator. In contrast, 20 cm of foam (k = 0.035) gives R = 5.71, total R = 5.88, U = 0.17 – much better.
How to Choose the Right k-Value for Your Calculation
Thermal conductivity values are usually provided by material manufacturers, but they vary with temperature, moisture content, and density. For building insulation, use the “declared” or “design” k-value from the product data sheet – often given at 10°C mean temperature. For common materials, typical ranges are:
- Mineral wool (glass or rock): 0.030 – 0.045 W/(m·K)
- Expanded polystyrene (EPS): 0.030 – 0.040 W/(m·K)
- Extruded polystyrene (XPS): 0.028 – 0.035 W/(m·K)
- Polyurethane foam: 0.022 – 0.030 W/(m·K)
- Wood (softwood): 0.12 – 0.15 W/(m·K)
- Brick (common): 0.6 – 0.8 W/(m·K)
- Concrete (dense): 1.0 – 1.8 W/(m·K)
- Glass: about 1.0 W/(m·K)
If you are calculating for a real wall, check the data sheet or use a conservative (higher) k-value to avoid overestimating insulation performance. For a quick estimate, the values above are reasonable.
Common Mistakes and How to Avoid Them
- Using cm instead of meters: Always convert thickness to meters. 10 cm = 0.1 m. A common error is to use 10 in the formula, giving a resistance 100 times too large.
- Forgetting surface resistances: The U-value of a building element always includes the inside and outside surface films. Omitting them underestimates the U-value (makes it look better than it is).
- Adding k-values instead of R-values: You cannot sum thermal conductivities directly. You must convert each layer to R = d/k, then sum the R-values.
- Ignoring thermal bridges: This simple series model assumes no studs, joists, or metal fasteners that conduct heat more than the insulation. In real walls, thermal bridges can increase the U-value significantly. For accurate building energy calculations, use a more detailed method (e.g., finite element analysis) or add a bridging factor.
- Using the wrong surface resistance: Inside surface resistance is higher (0.13) than outside (0.04) because indoor air is still. For roofs or floors, the values differ – for example, an upward heat flow (roof) has Rsi ≈ 0.10, while a downward heat flow (floor) has Rsi ≈ 0.17.
Limits of the Simple Series Model
The series resistance model is accurate for flat, homogeneous layers with uniform thickness and perfect contact. Real building elements often have:
- Air gaps between layers – these add extra resistance but also allow convection, which can reduce the benefit.
- Moisture – wet insulation conducts heat much better (higher k), so a damp wall has a higher U-value.
- Non-homogeneous materials – for example, a wall with timber studs every 60 cm is not uniform. The overall U-value is a weighted average of the insulated and studded areas, which requires a more complex calculation (e.g., the parallel path method).
- Dynamic conditions – the U-value assumes steady-state heat flow. In reality, heat storage in massive materials can affect the thermal performance over time, but the U-value is still the standard metric for building regulations.
For building code compliance, always use the standard calculation method specified in your local regulations (e.g., ISO 6946), which includes corrections for air gaps and mechanical fasteners.
Frequently Asked Questions
What is the difference between U-value and R-value?
R-value measures thermal resistance – the higher the better. U-value measures thermal transmittance – the lower the better. They are reciprocals: U = 1/R (when R includes surface resistances). A wall with R = 5 has U = 0.2. In the US, R-value is more common; in Europe and for windows, U-value is standard.
How do I convert k-value to R-value?
R = d / k, where d is the thickness in meters and k is thermal conductivity in W/(m·K). For example, 0.1 m of material with k = 0.04 gives R = 2.5 m²·K/W. Remember to use meters, not centimeters.
Do I need to include surface resistances in the U-value calculation?
Yes, for building elements. The U-value of a wall or roof includes the heat transfer from the indoor air to the surface, through the layers, and from the outer surface to the outdoor air. Standard surface resistances are 0.13 (inside) and 0.04 (outside) for vertical walls. For a single material’s “U-value” without surfaces, you would just use 1/(d/k), but that is not a true building U-value.
What is a good U-value for a wall?
It depends on climate and building regulations. In many cold climates, a wall U-value of 0.15 to 0.30 W/(m²·K) is considered good. Passive house standards require U ≤ 0.15 for walls. The lower the U-value, the less heat escapes in winter or enters in summer.
Can I use this calculator for windows?
No, windows are complex – they have glass, frames, gas fills, and edge effects. The U-value of a window (Uw) is a weighted average of the center-of-glass, edge-of-glass, and frame U-values. This calculator is only for homogeneous opaque layers like walls, roofs, and floors.
Does the U-value change with temperature?
Yes, slightly. Thermal conductivity of most materials increases with temperature, so the U-value is higher at higher mean temperatures. However, for typical building temperatures (10–20°C), the variation is small. Manufacturers often state k-values at 10°C. For extreme temperatures (e.g., industrial insulation), use temperature-dependent data.
Practical Tips for Using the Calculator
- For a single-layer wall, set layers 2 and 3 to negligible resistance: thickness = 0.001 m and k = 1000 W/(m·K) (so R ≈ 0.000001).
- If you have more than three layers, combine them: calculate the R for each extra layer and add it to the total manually, or adjust the calculator by using a combined layer.
- Always double-check your units: thickness in meters, k in W/(m·K).
- For a quick estimate, you can ignore surface resistances, but for building code work, include them.