This calculator works out the wet bulb temperature from air temperature and relative humidity, or the relative humidity from a dry and wet bulb reading. You enter the dry bulb temperature (normal air temperature) and either relative humidity or wet bulb temperature, and get the missing value plus dew point and humidity ratio.
Formula
The calculator uses the standard psychrometric approximation for wet bulb temperature (Twb) from dry bulb temperature (Tdb in °C) and relative humidity (RH in %):
Twb = Tdb · atan(0.151977 · √(RH + 8.313659)) + atan(Tdb + RH) − atan(RH − 1.676331) + 0.00391838 · RH1.5 · atan(0.023101 · RH) − 4.686035
This is the Stull (2011) empirical formula, valid for Tdb between −20 °C and 50 °C and RH between 5% and 99% (the calculator allows a slightly wider range). It gives the wet bulb temperature within about ±0.3 °C of the true value.
Dew point is approximated from RH and dry bulb temperature using the Magnus formula. Humidity ratio (also called specific humidity) is the mass of water vapor per kilogram of dry air, calculated from saturation vapor pressure at the air temperature.
Worked Example
Using the default values: air temperature = 25 °C, relative humidity = 50%.
- Compute √(50 + 8.313659) = √58.313659 ≈ 7.6356
- 0.151977 × 7.6356 ≈ 1.1605
- atan(1.1605) ≈ 0.8590 rad (49.2°)
- 25 × 0.8590 = 21.475
- atan(25 + 50) = atan(75) ≈ 1.5577 rad (89.2°)
- atan(50 − 1.676331) = atan(48.3237) ≈ 1.5500 rad (88.8°)
- 1.5577 − 1.5500 = 0.0077
- 0.00391838 × 501.5 × atan(0.023101 × 50) = 0.00391838 × 353.55 × atan(1.15505) ≈ 0.00391838 × 353.55 × 0.8562 ≈ 1.186
- Total: 21.475 + 0.0077 + 1.186 − 4.686035 ≈ 17.98 °C
The calculator shows 17.98 °C, which rounds to 18.0 °C. The dew point is about 13.9 °C and the humidity ratio about 9.9 g/kg. You can verify these with the calculator above.
Assumptions
- Air is at standard atmospheric pressure (101.325 kPa). Wet bulb temperature changes slightly with altitude.
- The wet bulb is properly ventilated (aspirated) and the bulb is covered with a wet wick.
- The Stull formula is empirical and assumes the wet bulb is not frozen (above 0 °C).
- Relative humidity is relative to liquid water, not ice.
What Is Wet Bulb Temperature?
Wet bulb temperature is the lowest temperature that air can reach by evaporating water into it. It is measured with a thermometer whose bulb is wrapped in a wet cloth and ventilated. As water evaporates, it cools the bulb. The drier the air, the more evaporation occurs and the lower the wet bulb temperature falls below the dry bulb temperature.
When relative humidity is 100%, the air is saturated, no evaporation occurs, and wet bulb equals dry bulb. At lower humidity, the wet bulb is always lower than the dry bulb. The difference between dry and wet bulb is a direct measure of how much moisture the air can still absorb.
Wet bulb temperature is not just a meteorological curiosity. It is used to design cooling towers, evaporative coolers, and HVAC systems. It also matters for human comfort and heat stress: the human body cools itself by sweating, so the wet bulb temperature is a better indicator of heat danger than the dry bulb temperature alone. A wet bulb of 35 °C is often cited as the survivable limit for a healthy person at rest for a few hours.
How to Use the Calculator
You have two common scenarios:
- You know air temperature and relative humidity (from a weather app or a hygrometer). Enter those two values, and the calculator gives wet bulb temperature, dew point, and humidity ratio.
- You have a sling psychrometer (two thermometers, one dry, one wet). Read both temperatures, then you can compute relative humidity by entering the dry bulb as air temperature and adjusting the relative humidity until the wet bulb output matches your measured wet bulb. Or use the inverse formula (not shown here) for a direct RH readout.
For most practical purposes, the Stull formula works well. If you are at high altitude (above about 2000 m), the result will be slightly off because the formula assumes sea-level pressure. For precise work, use a psychrometric chart or a full thermodynamic calculator that includes barometric pressure.
Common Mistakes and Misconceptions
- Confusing wet bulb with dew point. Wet bulb is the temperature of evaporative cooling; dew point is the temperature at which condensation occurs. Dew point is always lower than wet bulb (except at saturation).
- Using the wrong humidity value. Relative humidity is a percentage (0–100), not a fraction (0–1). The formula expects 0–100.
- Forgetting to ventilate the wet bulb. A wet bulb thermometer that is not moving through air reads too high. The standard is 3–5 m/s airflow.
- Assuming wet bulb is the same as the ‘feels like’ temperature. Heat index and humidex use different formulas that also account for radiation and wind.
- Using the formula for ice-covered wet bulbs. Below 0 °C, the wet bulb may freeze, and the formula changes.
Why Wet Bulb Matters for Safety
Wet bulb temperature is the key metric for heat stress in workplaces, sports, and military training. The WBGT (Wet Bulb Globe Temperature) index combines wet bulb, globe temperature, and dry bulb to set safe work/rest cycles. A simple wet bulb reading alone is not enough for safety decisions, but it is the most important component.
When wet bulb exceeds about 30 °C, even healthy people can struggle to cool down. At 35 °C wet bulb, the body cannot lose heat at all, and hyperthermia can occur within hours. This is why heatwaves with high humidity are more dangerous than dry heat. Use this calculator to check your local conditions, but always follow official heat safety guidelines from your local weather service.
Alternatives to This Calculator
If you need more precision or different outputs, consider:
- Psychrometric charts – graphical representation of moist air properties, useful for HVAC design.
- Full thermodynamic calculators – use ASHRAE equations and include barometric pressure, giving exact wet bulb, dew point, enthalpy, and specific volume.
- Online weather services – many report dew point and heat index, which are related but not identical to wet bulb.
- Physical sling psychrometer – the classic instrument, gives direct wet bulb and dry bulb readings.
For most everyday questions, the Stull formula is accurate enough. For engineering or safety-critical applications, use a tool that accounts for pressure and uses the latest ASHRAE standards.
Frequently Asked Questions
What is the difference between wet bulb and dew point?
Wet bulb is the temperature that a wet thermometer reaches due to evaporative cooling. Dew point is the temperature at which air becomes saturated and condensation forms. Wet bulb is always higher than dew point (except at 100% RH, where all three are equal). Wet bulb depends on both temperature and humidity; dew point depends only on humidity (vapor pressure).
Can I use this calculator for freezing temperatures?
The Stull formula is designed for temperatures above −20 °C and relative humidity above 5%. Below 0 °C, the wet bulb may freeze, and the formula may give slightly off results. For accurate sub-zero wet bulb, use a psychrometric chart for ice. The calculator allows down to −40 °C but the result may be less accurate below −20 °C.
Why does wet bulb matter for cooling towers?
Cooling towers reject heat by evaporating water. The lowest temperature that the water can be cooled to is the wet bulb temperature of the ambient air. If the wet bulb is high (humid air), the cooling tower is less effective. Engineers design towers based on the local wet bulb design temperature, often the 1% or 2% annual exceedance value.
How do I measure wet bulb temperature without a wet bulb thermometer?
You can use this calculator with air temperature and relative humidity from a standard hygrometer. Alternatively, you can make a simple wet bulb by covering a thermometer bulb with a wet cloth and swinging it in the air (a sling psychrometer). The calculator’s inverse method (adjusting RH until the wet bulb matches) works if you have a dry and wet bulb reading.
Is wet bulb temperature the same as the heat index?
No. The heat index (or humidex) is a measure of how hot it feels, combining temperature and humidity, but it uses a different formula and assumes light wind and shade. Wet bulb is a physical property of the air, not a perceived temperature. Wet bulb is used for heat stress guidelines because it directly relates to the body’s ability to cool by sweating.
What is a dangerous wet bulb temperature?
For healthy people, a wet bulb of 35 °C is considered the theoretical limit for survival for more than a few hours, because the body cannot dissipate heat. In practice, heat exhaustion and heat stroke can occur at wet bulb temperatures above 30 °C, especially during exertion. Always follow local heat advisories and take breaks in cool, shaded areas.
Related
Formula used
in m | Air temperature (dry bulb) | °C | 25 | -40 | 60 in rh | Relative humidity | % | 50 | 0 | 100 out twb | Wet bulb temperature | °C | m * atan(0.151977 * sqrt(rh + 8.313659)) + atan(m + rh) - atan(rh - 1.676331) + 0.00391838 * rh^1.5 * atan(0.023101 * rh) - 4.686035 | 2 out dp | Dew point | °C | (rh/100)^(1/8) * (112 + 0.9 * m) + 0.1 * rh - 112 | 2 out hr | Humidity ratio | g/kg | 621.97 * (6.112 * exp(17.67 * m / (m + 243.5)) * rh / 100) / (101.325 - 6.112 * exp(17.67 * m / (m + 243.5)) * rh / 100) | 1
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- DNA to RNA in the Nucleus: How Transcription Works0.2000 mol/L
- DNA Sequence Example Code: A Practical Guide0.2000 mol/L
- RNA Sequence Reverse Complement Tool
- DNA Sequence Quality Q15: What It Means
- T4 RNA Ligase 2 Sequence & Function15,485.0 g/mol
- T7 RNA Polymerase Sequence: Full Gene & Key Features97.5 kDa