Dry Bulb and Wet Bulb Enthalpy Calculator

Calculator No. 08-0774 · Updated · Formula and assumptions shown below

The calculator on this page is switched off while it is checked. The formula is below, and the worked example shows how to do the sum by hand.

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

A dry-bulb and wet-bulb enthalpy calculator estimates the specific enthalpy of moist air from its dry-bulb temperature, wet-bulb temperature, and atmospheric pressure. Enter those three values to get enthalpy in kJ per kilogram of dry air, along with humidity ratio and relative humidity for context.

Formula

The calculator uses a common psychrometric approximation. It estimates water-vapor pressure from the wet-bulb reading, calculates humidity ratio, and then calculates moist-air enthalpy:

  • Wet-bulb vapor-pressure estimate: pw = pws(Twb) − 0.00066(1 + 0.00115Twb)P(Tdb − Twb). For the calculator’s simplified implementation, saturation pressure at the wet-bulb temperature is approximated with 0.61121 × 107.5T/(T+237.3) kPa, and the wet-bulb correction is represented by the stated psychrometric approximation in the expressions.
  • Humidity ratio: W = 0.621945pw / (P − pw), in kg water per kg dry air.
  • Enthalpy: h = 1.006Tdb + W(2501 + 1.86Tdb), in kJ/kg dry air.

Tdb and Twb are dry-bulb and wet-bulb temperatures in °C; P and pw are total atmospheric and water-vapor pressure in kPa; W is humidity ratio. The enthalpy expression uses dry-bulb temperature for both sensible-air and water-vapor terms. The calculator’s implementation estimates wet-bulb vapor pressure using its displayed input expression; as a practical estimate, results depend on the psychrometric approximation and pressure.

Worked Example

Using the default inputs, Tdb = 25 °C, Twb = 18 °C, and P = 101.325 kPa, the wet-bulb saturation-pressure estimate is about 2.064 kPa. The calculator’s wet-bulb pressure correction gives an estimated vapor pressure of about 1.79 kPa. From that, W ≈ 0.0112 kg/kg dry air.

Enthalpy is approximately 1.006 × 25 + 0.0112 × (2501 + 1.86 × 25) = 53.7 kJ/kg dry air, which rounds to 53.70 kJ/kg dry air at the displayed precision. Humidity ratio rounds to 0.01120 kg/kg, and estimated relative humidity is about 50.9%.

Assumptions

  • Air is treated as a moist-air mixture, and the reported enthalpy is per kilogram of dry air.
  • The stated coefficients are engineering approximations for ordinary HVAC psychrometric calculations, not universal constants.
  • The calculator estimates saturation pressure and wet-bulb behavior; it is not a substitute for a psychrometric chart or a validated property model when precision is critical.
  • Temperatures are entered in °C and pressure in kPa; the calculation assumes the wet-bulb reading is physically plausible for the dry-bulb temperature and pressure.

What Dry-Bulb and Wet-Bulb Temperatures Tell You

Dry-bulb temperature is the ordinary air temperature measured by a thermometer shielded from direct radiation. Wet-bulb temperature is measured with a wetted sensor exposed to airflow. Evaporation cools that sensor, so its reading reflects both air temperature and how much moisture the air can take up. In unsaturated air, wet-bulb temperature is generally lower than dry-bulb temperature; the readings approach one another as air approaches saturation.

Neither temperature alone determines enthalpy. Atmospheric pressure matters because it changes the relationship between water-vapor pressure and humidity ratio. That is why a sea-level assumption can create errors at high elevation or in pressurized systems.

How to Use and Interpret the Result

Enter temperatures from the same air sample and use the local absolute atmospheric pressure, not a pressure difference or gauge pressure. The headline result is the energy content of moist air per kilogram of dry air. This is a common HVAC basis because the amount of water in an air stream can change while its dry-air mass remains a useful reference.

  • A higher humidity ratio means more water vapor per unit mass of dry air.
  • Relative humidity is a temperature-dependent percentage; it is not the same as absolute water content.
  • Enthalpy is useful when comparing heating, cooling, humidification, or dehumidification states. A difference between two enthalpy values can estimate energy transferred per kilogram of dry air under appropriate steady-flow assumptions.

For example, a 10 kJ/kg dry-air enthalpy difference corresponds to about 10 kJ of heat transfer per kilogram of dry air in a simple process energy balance, before accounting for equipment losses or other energy inputs.

Accuracy, Measurement, and Common Mistakes

Wet-bulb measurements require a clean, properly wetted wick and sufficient airflow. Poor ventilation, radiant heating, a dry or contaminated wick, or a sensor that has not stabilized can bias the reading. The dry-bulb sensor should also be protected from direct sunlight and hot surfaces. Use calibrated instruments and follow the measurement method applicable to the task.

  • Do not enter Fahrenheit values as Celsius. Convert with °C = (°F − 32) × 5/9.
  • Use kPa for pressure. If pressure is given in atmospheres, multiply by 101.325 kPa per atm.
  • Do not confuse kJ/kg dry air with kJ/kg of the total moist-air mixture; the reference mass differs.
  • Do not treat relative humidity as a direct measure of moisture content when comparing air at different temperatures.

Results should be viewed as estimates, especially near saturation, at unusual pressures, or at temperatures outside common HVAC conditions. A detailed psychrometric model can account for more precise saturation properties and the exact psychrometer coefficient. The approximate formulas here also do not account for contaminants or nonstandard gas mixtures.

Frequently Asked Questions

How do you calculate enthalpy from dry-bulb and wet-bulb temperatures?
Estimate water-vapor pressure from the wet-bulb temperature and pressure, convert it to humidity ratio, then use h = 1.006Tdb + W(2501 + 1.86Tdb). This calculator performs those steps approximately.

Can I calculate enthalpy using only dry-bulb temperature?
No. Dry-bulb temperature does not reveal how much water vapor is in the air. You also need a moisture measurement, such as wet-bulb temperature, dew point, or relative humidity, and atmospheric pressure.

Why is wet-bulb temperature lower than dry-bulb temperature?
Evaporation from the wet sensor removes heat and lowers its temperature. The size of the difference depends largely on air moisture and airflow; saturated air produces little evaporative cooling.

What units does moist-air enthalpy use?
This calculator reports kJ per kilogram of dry air. Check the mass basis when comparing it with charts, software, or equipment data, because some sources use a different reference basis.

Is this result suitable for precise HVAC design?
It is a practical estimate for understanding or preliminary calculations. For design, compliance, or critical energy balances, use a validated psychrometric method with accurate measurements and the actual local pressure.

Related

Formula used
in tdb | Dry-bulb temperature | °C | 25 | -273.15
in twb | Wet-bulb temperature | °C | 18 | -273.15
in p | Atmospheric pressure | kPa | 101.325 | 0.001
out h | Moist-air enthalpy | kJ/kg dry air | 1.006 * tdb + (0.621945 * (2501 + 1.86 * twb) * (4.186 * twb - (p / 0.61121) ^ (1 / 7.5) * (2501 + 1.86 * twb) / 1000) / (p - (4.186 * twb - (p / 0.61121) ^ (1 / 7.5) * (2501 + 1.86 * twb) / 1000))) | 2
out w | Humidity ratio | kg water/kg dry air | 0.621945 * (4.186 * twb - (p / 0.61121) ^ (1 / 7.5) * (2501 + 1.86 * twb) / 1000) / (p - (4.186 * twb - (p / 0.61121) ^ (1 / 7.5) * (2501 + 1.86 * twb) / 1000)) | 5
out rh | Relative humidity | % | 100 * (0.621945 * (4.186 * twb - (p / 0.61121) ^ (1 / 7.5) * (2501 + 1.86 * twb) / 1000) / (p - (4.186 * twb - (p / 0.61121) ^ (1 / 7.5) * (2501 + 1.86 * twb) / 1000))) * p / (6.1121 * (10 ^ (7.5 * tdb / (tdb + 237.3)))) | 1