This calculator determines the mixed air temperature when two air streams with different temperatures and flow rates combine. You enter the temperature and airflow of each stream, and it returns the resulting mixed air temperature, assuming adiabatic mixing (no heat loss or gain).
Formula
The mixed air temperature is the airflow-weighted average of the two stream temperatures:
Tm = (T1 × Q1 + T2 × Q2) / (Q1 + Q2)
Where:
- Tm = mixed air temperature (°C)
- T1 = temperature of stream 1 (°C)
- Q1 = airflow rate of stream 1 (m³/h)
- T2 = temperature of stream 2 (°C)
- Q2 = airflow rate of stream 2 (m³/h)
This is essentially the same as calculating a weighted average, where the airflow rates are the weights. The result is a temperature that lies between the two input temperatures, closer to the temperature of the stream with the larger airflow.
Worked Example
Using the default values from the calculator:
- Stream 1: T1 = 22 °C, Q1 = 2000 m³/h
- Stream 2: T2 = 32 °C, Q2 = 1000 m³/h
Step 1: Multiply each temperature by its airflow.
Stream 1: 22 × 2000 = 44,000 °C·m³/h
Stream 2: 32 × 1000 = 32,000 °C·m³/h
Step 2: Add these products together.
44,000 + 32,000 = 76,000 °C·m³/h
Step 3: Add the airflows.
2000 + 1000 = 3000 m³/h
Step 4: Divide the sum of products by the sum of airflows.
76,000 / 3000 = 25.333… °C
Rounded to two decimal places, the mixed air temperature is 25.33 °C, which matches the calculator output.
Assumptions
- Adiabatic mixing: No heat is gained or lost to the surroundings during mixing.
- Constant pressure: The pressure of both streams is the same.
- Constant density: Air density is assumed constant across the temperature range, which is reasonable for typical HVAC conditions.
- No phase change: No condensation or evaporation occurs during mixing.
When to Use This Calculation
This calculation is commonly used in HVAC (heating, ventilation, and air conditioning) design and troubleshooting. For example, when a building’s air handling unit mixes return air from the building with fresh outdoor air, the mixed air temperature affects the load on the cooling or heating coil. Knowing the mixed temperature helps engineers size equipment and predict system performance.
It is also useful for estimating the temperature of air entering a heat recovery ventilator, or for balancing airflow in systems with multiple supply ducts.
How to Read the Result
The result is a single temperature in °C (or °F if you input temperatures in °F). It will always be between the two input temperatures. If one airflow is much larger than the other, the mixed temperature will be close to that stream’s temperature. For example, if 90% of the air comes from a 20 °C room and 10% from a 40 °C outdoors, the mixed temperature will be about 22 °C.
Common Mistakes
- Using different units for airflow or temperature: Both airflows must be in the same unit (e.g., both m³/h or both CFM) and both temperatures in the same unit (both °C or both °F). Mixing units will give a wrong answer.
- Forgetting to weight by airflow: Simply averaging the two temperatures (e.g., (22+32)/2 = 27 °C) is incorrect unless the airflows are equal.
- Using volume flow when mass flow is needed: The formula works with volume flow only if the densities are similar. In most HVAC applications, the temperature differences are small enough that this is acceptable. For high precision, use mass flow rates.
- Rounding intermediate values too early: Keep full precision until the final step to avoid rounding errors.
Tips
- If you have more than two air streams, extend the formula: add each temperature multiplied by its flow, then divide by the total flow.
- Use consistent units: if you input temperatures in °F, the result will be in °F. The calculator does not convert between °C and °F.
- For quick estimates, remember that the result is closer to the temperature of the larger flow. If flows are equal, the result is the simple average.
- In duct systems, measure airflow at the point where the streams combine, if possible, to verify your inputs.
Troubleshooting
Result seems too high or too low: Double-check your airflow units. If one airflow is in CFM and the other in m³/h, convert one to the other (1 CFM = 1.699 m³/h). Also, verify that you haven’t swapped the temperatures.
Getting an error message: Ensure all inputs are numbers and that airflows are positive. The calculator requires airflow > 0; if you enter 0 for both, the denominator becomes zero, which is undefined.
Result is not what you expected from a physical measurement: The formula assumes perfect mixing. In real systems, stratification can occur, meaning the temperature at a point may differ from the calculated average. Also, if there is heat transfer through duct walls, the actual temperature may differ.
Mixed temperature is below both inputs: This is impossible with this formula. If you see this, check for negative airflow values or a data entry error.
Frequently Asked Questions
Can I use this calculator for liquids?
Yes, the same weighted-average formula applies to any fluid, as long as you use the same units for both streams. However, for liquids with significantly different densities, using mass flow rates is more accurate.
What if I have three or more air streams?
Extend the formula: add the product of each temperature and its flow, then divide by the sum of all flows. The calculator only handles two streams, but you can combine them sequentially.
Does this work with temperatures in Fahrenheit?
Yes, as long as both temperatures are in Fahrenheit and both airflows are in the same unit. The result will be in Fahrenheit. The calculator does not convert between scales.
Why is the mixed air temperature not just the average of the two temperatures?
Because the streams have different flow rates. The stream with more air has a greater influence on the final temperature. The formula weights each temperature by its airflow.
Is this calculation affected by humidity?
The formula assumes dry air. For moist air, the enthalpy (total heat content) should be used instead of temperature, because latent heat from moisture affects the mixture. For most HVAC design, the dry-bulb temperature is sufficient for preliminary estimates.
What is the difference between mixed air temperature and supply air temperature?
Mixed air temperature is the temperature of air after mixing but before any heating or cooling. Supply air temperature is the temperature of the air after it passes through the heating or cooling coil. The difference helps determine the coil load.
Related
Formula used
in t1 | Temperature of stream 1 | °C | 22 | -273.15 | 200 in q1 | Airflow of stream 1 | m³/h | 2000 | 0 | 100000 in t2 | Temperature of stream 2 | °C | 32 | -273.15 | 200 in q2 | Airflow of stream 2 | m³/h | 1000 | 0 | 100000 out tm | Mixed air temperature | °C | (t1 * q1 + t2 * q2) / (q1 + q2) | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- Normality to g/L Converter & Formula29.220 g/L
- Normality to meq/mL Conversion Calculator1.0000 meq/mL
- Normality Test Q-Q Plot: How to Read It
- Normality Test Results: How to Analyze Them
- Normality Slay the Spire?
- Normality Test for Paired t Test: How to Check