This guide shows you how to calculate the specific enthalpy of outside air (in kJ/kg of dry air) using dry-bulb temperature and relative humidity. You’ll get the value needed for HVAC load calculations, psychrometric analysis, and ventilation design. You’ll need a psychrometric chart or the formulas below, plus a calculator.
Formula
The specific enthalpy of moist air is the sum of the enthalpy of dry air and the enthalpy of water vapor per kilogram of dry air:
h = 1.006·t + x·(2501 + 1.86·t)
Where:
- h = specific enthalpy of moist air (kJ/kg dry air)
- t = dry-bulb temperature (°C)
- x = humidity ratio (kg water vapor per kg dry air)
- 1.006 = specific heat of dry air (kJ/kg·°C)
- 2501 = latent heat of vaporization of water at 0°C (kJ/kg)
- 1.86 = specific heat of water vapor (kJ/kg·°C)
The humidity ratio x is calculated from the partial pressure of water vapor (pw) and the total atmospheric pressure (p, usually 101.325 kPa):
x = 0.622·pw / (p – pw)
And pw is the saturation pressure at the dew point, approximated from relative humidity:
pw = (RH/100) · psat(t)
where psat(t) is the saturation vapor pressure of water at temperature t, often found using the Antoine equation or a psychrometric chart. For this calculator, we use the standard psychrometric approximation:
psat(t) = 0.61094 · exp(17.625·t / (t + 243.04)) (kPa)
This is the formula used in the calculator block above.
Worked Example
Using the default values: t = 25°C, RH = 50%, and p = 101.325 kPa.
- Calculate saturation pressure at 25°C:
psat = 0.61094 · exp(17.625·25 / (25 + 243.04)) = 0.61094 · exp(440.625 / 268.04) = 0.61094 · exp(1.644) = 0.61094 · 5.174 = 3.161 kPa - Calculate partial pressure of water vapor:
pw = (50/100) · 3.161 = 1.5805 kPa - Calculate humidity ratio:
x = 0.622 · 1.5805 / (101.325 – 1.5805) = 0.9827 / 99.7445 = 0.009852 kg/kg - Calculate enthalpy:
h = 1.006·25 + 0.009852·(2501 + 1.86·25) = 25.15 + 0.009852·(2501 + 46.5) = 25.15 + 0.009852·2547.5 = 25.15 + 25.10 = 50.25 kJ/kg dry air
The calculator shows 50.25 kJ/kg dry air, matching the example.
Assumptions
- Atmospheric pressure is 101.325 kPa (sea level). At higher altitudes, the value changes slightly.
- The air is a mixture of ideal gases.
- The specific heats of dry air and water vapor are constant over the range.
- The Antoine equation used is accurate for -40°C to 60°C.
When to Use This
Outside air enthalpy is used in HVAC load calculations to determine the energy required to bring ventilation air to indoor conditions. It is also used in cooling coil sizing, economizer control, and psychrometric analysis. For example, if you know the outside air enthalpy and the indoor enthalpy, the difference times the airflow gives the cooling or heating load.
How to Read the Result
The result is the total heat content per kilogram of dry air, including both sensible heat (temperature) and latent heat (moisture). A higher enthalpy means more energy is needed to cool or dehumidify the air. For instance, 50 kJ/kg is typical of warm, humid summer air, while 10 kJ/kg might be cool, dry winter air.
Common Mistakes
- Using °F instead of °C: The formula requires Celsius. Convert Fahrenheit to Celsius first: (°F – 32) × 5/9.
- Forgetting to convert RH from % to fraction: Always divide by 100.
- Using the wrong pressure: At altitudes above sea level, use actual barometric pressure, not 101.325 kPa.
- Rounding too early: Keep at least 4 significant figures in intermediate steps to avoid errors.
- Confusing enthalpy with temperature: Enthalpy includes latent heat, so two air samples at the same temperature but different humidity have different enthalpies.
Tips
- Use a psychrometric chart for quick estimates; the chart lines for enthalpy are diagonal.
- For repeated calculations, use the calculator above to avoid manual arithmetic.
- If you need enthalpy in Btu/lb, multiply kJ/kg by 0.4299.
- Double-check your saturation pressure formula; small errors in psat lead to large errors in humidity ratio at high RH.
Troubleshooting
- Result seems too high or low: Check your temperature units and RH fraction. A typical summer enthalpy is 50-80 kJ/kg; winter might be 0-20 kJ/kg.
- Negative humidity ratio: This happens if pw > p. Ensure RH is ≤100% and temperature is within range.
- Calculator shows “Cannot compute”: The inputs are outside the allowed range. For example, RH above 100% or temperature below -40°C.
- Discrepancy with a psychrometric chart: Charts may use a different reference state (e.g., 0°C vs 0°F) or a different saturation pressure formula. Differences of 1-2 kJ/kg are normal.
Frequently Asked Questions
What is the difference between enthalpy and temperature?
Temperature measures only sensible heat. Enthalpy includes both sensible heat and latent heat from moisture. Two air samples at the same temperature can have very different enthalpies if one is humid and the other dry.
Why do we use dry air as the basis?
Because the amount of dry air in a sample remains constant even when moisture condenses or evaporates. Using dry air as the denominator makes calculations consistent.
Can I use this for altitudes above sea level?
Yes, but you should adjust the atmospheric pressure input. The calculator uses 101.325 kPa, but at 1500 m altitude, pressure is about 84.5 kPa. Use the actual barometric pressure for accuracy.
What is the typical enthalpy of outside air in summer?
It varies widely. In humid climates, it can be 60-100 kJ/kg; in dry climates, 40-60 kJ/kg. The calculator will give you the exact value for your conditions.
How does enthalpy relate to cooling load?
The cooling load for ventilation is the mass flow rate of dry air times the enthalpy difference between outside and inside air. For example, 1 kg/s of air with a 30 kJ/kg enthalpy difference requires 30 kW of cooling.
Is there a simpler way to get enthalpy?
Yes, use a psychrometric chart. Find the point where the dry-bulb temperature line meets the relative humidity curve, then read the enthalpy along the diagonal lines. The chart is accurate enough for most design work.
Related
Formula used
in t | Dry-bulb temperature | °C | 25 | -40 | 60 in rh | Relative humidity | % | 50 | 0 | 100 out h | Specific enthalpy | kJ/kg dry air | 1.006 * t + x * (2501 + 1.86 * t) | 2 out x | Humidity ratio | kg water/kg dry air | (0.622 * pw) / (p - pw) | 4
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- Normality to meq/mL Conversion Calculator1.0000 meq/mL
- Normality to g/L Converter & Formula29.220 g/L
- Normality Test Q-Q Plot: How to Read It
- Normality Test Results: How to Analyze Them
- Normality Slay the Spire?
- Normality Test for Paired t Test: How to Check