This calculator works out the mixed air temperature of two or more airstreams, which is the temperature of the air after they combine. You enter the dry-bulb temperature and airflow (volume or mass) for each stream, and you get the resulting mixed air temperature. The same math applies to mixing any two fluids, but it is most commonly used in HVAC design and troubleshooting.
Formula
The mixed air temperature is the airflow-weighted average of the individual stream temperatures:
tm = (t1 × V1 + t2 × V2) / (V1 + V2)
Where:
- tm = mixed air dry-bulb temperature (°C or °F)
- t1, t2 = dry-bulb temperatures of each airstream (°C or °F)
- V1, V2 = volumetric airflow of each stream (m³/s, L/s, CFM, etc.)
This formula assumes the air streams have the same density and specific heat. For HVAC work at typical temperatures (0–40 °C), that is accurate enough. If the temperatures differ by more than about 30 °C, or if you are mixing gases of very different molecular weights, use mass flow instead of volumetric flow.
Worked Example
Using the default values from the calculator:
- Stream 1: 22 °C at 0.5 m³/s
- Stream 2: 5 °C at 0.3 m³/s
Step 1: Multiply each temperature by its flow:
22 × 0.5 = 11.0
5 × 0.3 = 1.5
Step 2: Add the products:
11.0 + 1.5 = 12.5
Step 3: Add the flows:
0.5 + 0.3 = 0.8
Step 4: Divide:
12.5 / 0.8 = 15.625 °C
The calculator rounds to 2 decimal places, so it shows 15.63 °C. That is the mixed air temperature.
Assumptions
- Air streams have the same density and specific heat (valid for normal HVAC temperatures).
- No heat is gained or lost to the ductwork during mixing.
- No moisture condensation occurs during mixing (the formula gives the dry-bulb temperature only).
- Volumetric flow is measured at the same conditions (or corrected to standard conditions).
How to Build a Mixed Air Calculator in Excel
You can make a simple mixed air calculator in Excel in under a minute. The core is the weighted average formula.
- In cells A1 and A2, label “Stream 1 temp (°C)” and “Stream 2 temp (°C)”.
- In cells B1 and B2, enter the temperature values.
- In cells A4 and A5, label “Stream 1 flow (m³/s)” and “Stream 2 flow (m³/s)”.
- In cells B4 and B5, enter the flow values.
- In cell A7, label “Mixed air temp (°C)”.
- In cell B7, enter:
=(B1*B4 + B2*B5)/(B4+B5)
That is the whole thing. You can extend it to three or more streams by adding more terms to the numerator and denominator. For three streams, the formula becomes =(B1*B4 + B2*B5 + B3*B6)/(B4+B5+B6).
Common Mistakes and How to Avoid Them
- Using different units for flow. If one stream is in CFM and the other in m³/s, the result is wrong. Convert all flows to the same unit first.
- Using °F and °C together. The formula works in either scale, but you cannot mix them. Convert everything to one scale.
- Forgetting that the formula gives dry-bulb temperature, not enthalpy. If you need the mixed air enthalpy (for load calculations), you must use the enthalpy values and mass flow, not just temperature.
- Assuming the result is the “supply” temperature. The mixed air temperature is before any heating or cooling coil. After the coil, the temperature is whatever the coil produces.
- Using the formula for liquid mixing without checking density. For water and glycol mixtures, density varies with temperature and concentration; the simple weighted average only works if the fluids are similar.
When to Use a Mixed Air Calculator
This calculation appears in several real situations:
- HVAC economizer design: Determine the temperature of mixed outdoor and return air before it enters the cooling coil.
- Ventilation sizing: Estimate the temperature of the air delivered to a space when mixing supply air with room air.
- Laboratory fume hoods: Calculate the mixed temperature of makeup air and room air to avoid condensation or drafts.
- Process engineering: Mixing two gas streams in a duct or pipe before a filter or sensor.
In most HVAC cases, the mixed air temperature is used to estimate the cooling coil load. For that, you also need the mixed air enthalpy, which requires a psychrometric chart or formula. The temperature-only calculator gives a quick approximation.
Limitations of the Simple Formula
The simple weighted average is a good approximation, but it is not exact for air. Air has humidity, and the specific heat of moist air is slightly higher than dry air. At typical comfort conditions (20–25 °C, 40–60% RH), the error is less than 0.5 °C. At extreme conditions (very hot and humid outdoor air, very cold dry air), the error can be a few degrees. For precise work, use a psychrometric calculator that accounts for humidity ratio and enthalpy.
Another limitation is that the formula assumes no heat transfer in the duct. In reality, long uninsulated ducts can add or remove heat, especially if the air is much warmer or colder than the surroundings. For most indoor duct runs, that effect is small.
Frequently Asked Questions
Can I use this formula for mixing water streams?
Yes, the same weighted average works for any two fluids with the same specific heat. For water, the result is very accurate because water’s specific heat is nearly constant. For glycol mixtures or oils, the specific heat varies with temperature and concentration, so the simple formula is less accurate. Use mass flow instead of volumetric flow for best results.
What if I have three or more airstreams?
Extend the formula: add each temperature multiplied by its flow to the numerator, and add all flows to the denominator. The calculator on this page only handles two streams, but the Excel version can easily be extended.
Does the result change if I use CFM instead of m³/s?
No, as long as you use the same unit for all flows. The weighted average is unit-consistent. If you mix CFM and m³/s, you get a wrong answer. Convert one to the other first (1 m³/s = 2118.88 CFM).
Why is my mixed air temperature lower than the average of the two temperatures?
It should not be lower than the average unless the flows are very different. The formula gives a weighted average, so the result is always between the two input temperatures. If you are getting a result outside that range, check your units and your formula entry.
Can I use this to find the mixed air humidity?
No. Humidity mixing requires a different formula using humidity ratios (grains or grams of water per kg of dry air). The temperature-only formula ignores moisture. For a full mixed air state, use a psychrometric chart or a dedicated mixed air calculator that includes humidity.
Is this calculator suitable for safety-critical ventilation design?
This calculator is for study and general planning. For actual building ventilation and safety systems, follow your local codes, use certified software, and have a qualified engineer review the design. The simple formula does not account for pressure drops, fan heat, or duct leakage.
Safety and Accuracy Notes
When working with real HVAC systems, always follow your lab or facility method, the equipment manufacturer’s instructions, and your supervisor. The calculator is a planning tool, not a substitute for proper measurement. Always verify mixed air temperatures with a calibrated sensor if the result affects system control or safety.
Related
Formula used
in t1 | Stream 1 temperature | °C | 22 | -273.15 in m1 | Stream 1 airflow | m³/s | 0.5 | 0 in t2 | Stream 2 temperature | °C | 5 | -273.15 in m2 | Stream 2 airflow | m³/s | 0.3 | 0 out tm | Mixed air temperature | °C | (t1 * m1 + t2 * m2) / (m1 + m2) | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- Normality to g/L Converter & Formula29.220 g/L
- Normality to meq/mL Conversion Calculator1.0000 meq/mL
- Normality Test Q-Q Plot: How to Read It
- Normality Test Results: How to Analyze Them
- Normality Slay the Spire?
- Normality Test for Paired t Test: How to Check