Mixed Air Formula for Heat Transfer

Calculator No. 01-8123 · Updated · Formula and assumptions shown below

Mixed air temperature 27.57 °C
Mass flow of stream 1
1.5 kg/s
Set in the form below
Temperature of stream 1
35 °C
Set in the form below
Mass flow of stream 2
2 kg/s
Set in the form below
Temperature of stream 2
22 °C
Set in the form below
You enter
Mass flow of stream 1 (kg/s), Temperature of stream 1 (°C), Mass flow of stream 2 (kg/s), Temperature of stream 2 (°C)
You get
Mixed air temperature (°C)
Rounding
2 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

The mixed air formula calculates the temperature of air after two or more airstreams combine, based on the energy balance of the streams. You enter the dry-bulb temperature and mass flow rate (or volume flow rate) of each airstream, and the calculator returns the resulting mixed air temperature. This is essential for HVAC design, ventilation system balancing, and predicting coil loads in buildings.

Formula

The mixed air temperature is a mass-weighted average of the individual stream temperatures:

tmix = (m1 · t1 + m2 · t2) / (m1 + m2)

Where:

  • tmix = mixed air dry-bulb temperature (°C)
  • m1 = mass flow rate of airstream 1 (kg/s)
  • t1 = dry-bulb temperature of airstream 1 (°C)
  • m2 = mass flow rate of airstream 2 (kg/s)
  • t2 = dry-bulb temperature of airstream 2 (°C)

This is the steady-flow energy balance for adiabatic mixing of two ideal gases with constant specific heat. The specific heat of air cancels out because it is assumed the same for both streams. For more than two streams, extend the numerator and denominator accordingly.

Worked Example

Using the default values: m1 = 1.5 kg/s at 35 °C, and m2 = 2.0 kg/s at 22 °C.

  1. Calculate the numerator: (1.5 × 35) + (2.0 × 22) = 52.5 + 44.0 = 96.5
  2. Calculate the denominator: 1.5 + 2.0 = 3.5
  3. Divide: 96.5 / 3.5 = 27.5714… ≈ 27.57 °C

The mixed air temperature is 27.57 °C, matching the calculator output.

Assumptions

  • Adiabatic mixing: no heat is lost or gained from the duct or surroundings.
  • Constant specific heat of air (the same for all streams).
  • No condensation or moisture transfer during mixing (sensible heat only).
  • Steady-state flow, no work done by fans or dampers in the mixing section.

When to Use the Mixed Air Formula

HVAC engineers use this formula whenever outdoor ventilation air is mixed with return air before the cooling or heating coil. For example, a rooftop unit may take 20% outdoor air at 35 °C and 80% return air at 22 °C. The mixed air temperature determines the coil load and the supply air temperature after conditioning.

The formula also applies to:

  • Economizer operation, where outdoor air is used for free cooling.
  • Exhaust and makeup air systems in industrial ventilation.
  • Predicting the temperature in a plenum where multiple ducts converge.
  • Energy recovery calculations when comparing mixed vs. unmixed streams.

How to Choose the Right Flow Rate Units

You can use mass flow (kg/s) or volume flow (m³/s) as long as you are consistent. However, volume flow must be corrected for density if temperatures differ significantly. Since density varies with temperature, mass flow is the physically correct basis. In practice, many engineers use standard or normal cubic meters per hour (Nm³/h) to avoid density corrections.

If you only know volume flow rates at actual conditions, convert to mass flow using:

m = ρ × V

Where ρ (density of air) is approximately 1.2 kg/m³ at 20 °C and 101.325 kPa. For greater accuracy, use the ideal gas law: ρ = P / (R_specific × T), with T in kelvin.

Common Mistakes and Misconceptions

  • Using volume flow without density correction: If one stream is hot (less dense) and the other is cold (denser), the volume-weighted average will be wrong. Always use mass flow.
  • Forgetting to convert °C to kelvin: The formula is linear, so using °C gives the same result as kelvin for temperature differences. However, if you use the ideal gas law for density, you must use kelvin.
  • Assuming the mixed air enthalpy is the same as the temperature: The formula gives the dry-bulb temperature, not the enthalpy. For cooling coil loads, you need the enthalpy of the mixed air, which also depends on humidity ratio.
  • Ignoring humidity: When airstreams have different moisture contents, the sensible heat formula is only an approximation. The true mixed air state should be found by mixing enthalpy and humidity ratio.

Limitations of the Formula

The simple formula assumes constant specific heat, which is reasonable for typical HVAC temperatures (0–50 °C). It also assumes no condensation during mixing. If one stream is very humid and the other is cold, the mixture may become supersaturated, and moisture will condense, releasing latent heat. In that case, the mixed air temperature will be slightly higher than the formula predicts because the latent heat raises the sensible temperature.

For accurate psychrometric analysis, use a psychrometric chart or software that accounts for humidity. The formula is a quick estimate for preliminary sizing, but for final design, always perform a full psychrometric calculation.

Frequently Asked Questions

Can I use this formula for more than two airstreams?

Yes, extend the formula to any number of streams: tmix = (Σ mi·ti) / (Σ mi). The calculator above handles two streams, but the principle is the same.

What if I only know the volume flow rates in CFM?

Convert CFM to m³/s by multiplying by 0.0004719474 (1 CFM = 0.0004719474 m³/s). Then convert to mass flow using density, or use standard air density (1.2 kg/m³) for approximate results. For precise work, use the actual air density at the given conditions.

Does the mixed air temperature change if the duct is not insulated?

Yes, if the duct is not insulated, heat transfer with the surroundings will alter the mixed air temperature. The formula assumes adiabatic mixing (no heat loss). For uninsulated ducts, you would need to account for heat gain or loss, which is beyond this simple calculation.

Why do I get a different result when I use a psychrometric chart?

The psychrometric chart accounts for humidity and enthalpy. If the two airstreams have different humidity ratios, the mixing line on the chart is not a straight line in terms of temperature alone. The chart gives the true mixed air state, which may have a slightly different dry-bulb temperature if condensation occurs. For most HVAC design, the difference is small unless one stream is very humid.

Is the mixed air formula the same as the weighted average?

Yes, it is a weighted average, but the weights are mass flow rates, not volume flow rates. This is why it is sometimes called the mass-weighted average temperature.

What is the typical accuracy of this formula?

For dry air or air with similar humidity levels, the formula is accurate to within a fraction of a degree. For air with large humidity differences, the error can be up to 1–2 °C due to latent heat effects. Always check with a psychrometric calculation for critical applications.

Related

Formula used
in m | Mass flow of stream 1 | kg/s | 1.5 | 0
in t1 | Temperature of stream 1 | °C | 35 | -273.15
in m2 | Mass flow of stream 2 | kg/s | 2.0 | 0
in t2 | Temperature of stream 2 | °C | 22 | -273.15
out t_mix | Mixed air temperature | °C | (m * t1 + m2 * t2) / (m + m2) | 2

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.

More in this section

The whole Moles & Molar Mass section →