Mixed Air Temp Calculator: DB & WB Explained

Calculator No. 01-8124 · Updated · Formula and assumptions shown below

Mixed dry-bulb temp 27.67 °C
Enthalpy of stream 1
83.08 kJ/kg
Result, rounded to 2 decimal places
Enthalpy of stream 2
56.79 kJ/kg
Result, rounded to 2 decimal places
Mixed wet-bulb temp
20.00 °C
Result, rounded to 2 decimal places
You enter
Airstream 1 dry-bulb temp (°C), Airstream 1 wet-bulb temp (°C), Airstream 1 flow rate (m³/s), Airstream 2 dry-bulb temp (°C), Airstream 2 wet-bulb temp (°C), Airstream 2 flow rate (m³/s)
You get
Mixed dry-bulb temp (°C), Enthalpy of stream 1 (kJ/kg), Enthalpy of stream 2 (kJ/kg), Mixed wet-bulb temp (°C)
Rounding
2 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

A mixed air temperature calculator determines the dry-bulb (DB) and wet-bulb (WB) temperature of air after two or more airstreams are combined, typically outdoor air and return air in an HVAC system. You enter the dry-bulb and wet-bulb temperatures and the volumetric flow rate of each airstream, and the calculator returns the resulting mixture’s dry-bulb temperature, wet-bulb temperature, and often its enthalpy. The dry-bulb mix is a simple flow-weighted average, but the wet-bulb mix requires an energy balance using enthalpy, which is why a dedicated calculator is useful.

Formula

The dry-bulb temperature of a mixture is the flow-weighted arithmetic mean:

Tmix,DB = (T1·Q1 + T2·Q2) / (Q1 + Q2)

where T1, T2 are the dry-bulb temperatures of the two airstreams (°C) and Q1, Q2 are their volumetric flow rates (m³/s). This works because the sensible heat of moist air is nearly proportional to temperature at typical HVAC conditions.

The wet-bulb temperature of the mixture is not a simple average. It is found by first calculating the enthalpy of each stream using the wet-bulb temperature:

h = 1.006·Tdb + (2501 + 1.86·Tdb)·W

where W is the humidity ratio (kg water per kg dry air), computed from the wet-bulb temperature using the psychrometric relation:

W = 0.62198·(pws / (P – pws))

with pws = 611.2·exp(17.67·Twb / (Twb + 243.5)) (saturation pressure in Pa) and P = 101325 Pa (standard atmospheric pressure). Then the mixed enthalpy is the flow-weighted average:

hmix = (h1·Q1 + h2·Q2) / (Q1 + Q2)

Finally, the mixed wet-bulb temperature is found by iteratively solving the enthalpy equation for Twb that gives hmix. The calculator above uses a direct approximation: it computes the flow-weighted average of the wet-bulb temperatures, which is accurate to within about 0.5 °C for typical HVAC mixtures. For precise work, use a psychrometric chart or a full iterative solver.

Worked Example

Suppose you mix 2.0 m³/s of outdoor air at 35 °C dry-bulb and 24 °C wet-bulb with 4.0 m³/s of return air at 24 °C dry-bulb and 18 °C wet-bulb.

Step 1: Mixed dry-bulb temperature

Tmix,DB = (35 × 2.0 + 24 × 4.0) / (2.0 + 4.0) = (70 + 96) / 6 = 166 / 6 = 27.67 °C

Step 2: Enthalpy of stream 1

pws1 = 611.2 × exp(17.67 × 24 / (24 + 243.5)) = 611.2 × exp(424.08 / 267.5) = 611.2 × exp(1.585) ≈ 611.2 × 4.881 = 2983 Pa

W1 = 0.62198 × (2983 / (101325 – 2983)) = 0.62198 × (2983 / 98342) = 0.62198 × 0.03033 = 0.01887 kg/kg

h1 = 1.006 × 35 + (2501 + 1.86 × 35) × 0.01887 = 35.21 + (2501 + 65.1) × 0.01887 = 35.21 + 2566.1 × 0.01887 = 35.21 + 48.42 = 83.63 kJ/kg

Step 3: Enthalpy of stream 2

pws2 = 611.2 × exp(17.67 × 18 / (18 + 243.5)) = 611.2 × exp(318.06 / 261.5) = 611.2 × exp(1.216) ≈ 611.2 × 3.373 = 2062 Pa

W2 = 0.62198 × (2062 / (101325 – 2062)) = 0.62198 × (2062 / 99263) = 0.62198 × 0.02077 = 0.01292 kg/kg

h2 = 1.006 × 24 + (2501 + 1.86 × 24) × 0.01292 = 24.14 + (2501 + 44.64) × 0.01292 = 24.14 + 2545.64 × 0.01292 = 24.14 + 32.89 = 57.03 kJ/kg

Step 4: Mixed enthalpy

hmix = (83.63 × 2.0 + 57.03 × 4.0) / (2.0 + 4.0) = (167.26 + 228.12) / 6 = 395.38 / 6 = 65.90 kJ/kg

Step 5: Mixed wet-bulb temperature

Using the flow-weighted average approximation: Tmix,WB = (24 × 2.0 + 18 × 4.0) / 6 = (48 + 72) / 6 = 120 / 6 = 20.00 °C. The true iterative solution gives about 20.1 °C. The calculator output shows 20.00 °C.

Assumptions

  • Standard atmospheric pressure (101.325 kPa).
  • Air behaves as an ideal gas; moist air properties are approximated by the perfect gas relations.
  • Flow rates are volumetric and remain constant; no condensation occurs during mixing.
  • The wet-bulb temperature approximation assumes the mixture enthalpy is the flow-weighted average, which is exact for adiabatic mixing.
  • No heat transfer to or from the duct walls.

Why Mixed Air Temperature Matters

In HVAC design, mixed air temperature is the condition of air entering the cooling coil or heating coil after outdoor ventilation air is blended with return air. This value determines the coil load, the required cooling capacity, and the supply air temperature. For example, in a building with 20% outdoor air at 35 °C and 80% return air at 24 °C, the mixed dry-bulb is 26.2 °C, which is far below the outdoor temperature, so the coil only needs to cool from 26.2 °C to the supply setpoint, not from 35 °C. This is why economizer cycles and variable outdoor air fractions are used to reduce energy consumption.

How to Use the Calculator

Enter the dry-bulb and wet-bulb temperatures for each airstream and their volumetric flow rates. The calculator returns the mixed dry-bulb, the enthalpy of each stream, and the mixed wet-bulb (approximated as the flow-weighted average). For precise wet-bulb, use the enthalpy method: compute hmix as above, then find the wet-bulb temperature that gives that enthalpy on a psychrometric chart.

Common mistakes include using mass flow instead of volumetric flow without converting (density of air is about 1.2 kg/m³, so multiply m³/s by 1.2 to get kg/s), forgetting to convert temperatures to °C, and assuming the wet-bulb mix is a simple average. Also, if one airstream is saturated (relative humidity 100%), the wet-bulb equals the dry-bulb, which simplifies the calculation.

Limitations and Accuracy

The dry-bulb mixing formula is exact for adiabatic mixing of ideal gases. The wet-bulb approximation using the flow-weighted average is accurate to within ±0.5 °C for typical HVAC conditions (0-40 °C dry-bulb, 0-30 °C wet-bulb). For extreme conditions (very high humidity or large temperature differences), the error can reach 1 °C. The enthalpy calculation assumes standard pressure; at high altitudes (e.g., Denver at 84 kPa), the saturation pressure relation changes, and the wet-bulb calculation would need adjustment. Also, the formula ignores the heat capacity of water vapor in the enthalpy (it uses a simplified form), which introduces a small error of less than 0.5%.

Frequently Asked Questions

Why isn’t the mixed wet-bulb temperature just the average of the wet-bulbs? Because wet-bulb temperature is not a linear function of enthalpy. The energy content of moist air depends on both temperature and humidity. When you mix two airstreams, the total enthalpy is conserved, but the wet-bulb temperature is a thermodynamic property that is a nonlinear function of enthalpy and humidity. The simple average works as an approximation when the two streams have similar humidity ratios, but it can be off by 1 °C or more when one stream is very humid and the other is dry.

What is the difference between dry-bulb and wet-bulb temperature? Dry-bulb temperature is the ordinary air temperature measured by a standard thermometer. Wet-bulb temperature is the temperature read by a thermometer whose bulb is covered with a wetted wick and ventilated; it reflects the cooling effect of evaporation. The difference between the two indicates the humidity: the larger the difference, the drier the air. At 100% relative humidity, wet-bulb equals dry-bulb.

Can I use this calculator for more than two airstreams? Yes, but the calculator only supports two. For multiple streams, you can combine them pairwise: first mix stream 1 and 2, then mix the result with stream 3, and so on. The order doesn’t matter for the final result because mixing is associative. Alternatively, use the formula with the sum of all flow rates and the sum of each temperature times its flow.

Does the altitude affect the mixed air temperature? Yes, because the saturation pressure of water vapor depends on total pressure. At higher altitudes, the lower atmospheric pressure means the same humidity ratio corresponds to a lower relative humidity and a different wet-bulb temperature. The dry-bulb mixing is unaffected, but the wet-bulb calculation would need a pressure correction. For most HVAC applications at sea level, the standard pressure assumption is fine.

What is a typical mixed air temperature for a rooftop unit? For a unit with 20% outdoor air at 35 °C and 80% return air at 24 °C, the mixed dry-bulb is 26.2 °C. If the outdoor air is 40 °C and the return is 22 °C, the mix is 25.6 °C. The exact value depends on the outdoor air fraction, which is often set by ventilation codes (e.g., ASHRAE 62.1) and can range from 5% to 30%.

Why do I need to know the mixed wet-bulb temperature? Because the wet-bulb temperature determines the enthalpy, which is the true measure of the cooling load. A cooling coil must remove both sensible heat (temperature) and latent heat (moisture). The mixed wet-bulb temperature is used to find the coil entering air condition on a psychrometric chart, which then determines the required coil capacity and the amount of condensate produced.

Related

Formula used
in t1 | Airstream 1 dry-bulb temp | °C | 35 | -40 | 60
in wb1 | Airstream 1 wet-bulb temp | °C | 24 | -40 | 60
in f1 | Airstream 1 flow rate | m³/s | 2.0 | 0 | 100
in t2 | Airstream 2 dry-bulb temp | °C | 24 | -40 | 60
in wb2 | Airstream 2 wet-bulb temp | °C | 18 | -40 | 60
in f2 | Airstream 2 flow rate | m³/s | 4.0 | 0 | 100
out t_mix | Mixed dry-bulb temp | °C | (t1*f1 + t2*f2) / (f1 + f2) | 2
out h1 | Enthalpy of stream 1 | kJ/kg | 1.006*t1 + (2501 + 1.86*t1) * (0.62198 * (611.2 * exp(17.67*wb1/(wb1+243.5)) / 101325) / (1 - 0.62198 * (611.2 * exp(17.67*wb1/(wb1+243.5)) / 101325))) | 2
out h2 | Enthalpy of stream 2 | kJ/kg | 1.006*t2 + (2501 + 1.86*t2) * (0.62198 * (611.2 * exp(17.67*wb2/(wb2+243.5)) / 101325) / (1 - 0.62198 * (611.2 * exp(17.67*wb2/(wb2+243.5)) / 101325))) | 2
out wb_mix | Mixed wet-bulb temp | °C | (wb1*f1 + wb2*f2) / (f1 + f2) | 2

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.