Mixed Air Temp Calculator: Formula & How to Use It

Calculator No. 01-7712 · Updated · Formula and assumptions shown below

The calculator on this page is switched off while it is checked. The formula is below, and the worked example shows how to do the sum by hand.

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

A mixed air temperature calculator determines the temperature of air after two or more airstreams combine, typically outdoor ventilation air and return air in an HVAC system. You enter the dry-bulb temperature and airflow rate (CFM or L/s) for each airstream, and the calculator returns the resulting mixture temperature, assuming no heat is lost or gained during mixing. This value is essential for sizing cooling coils, estimating coil loads, and checking economizer operation.

Formula

The mixed air temperature is a flow-weighted average of the individual airstream temperatures:

Tm = (T1 × Q1 + T2 × Q2) / (Q1 + Q2)

  • Tm = mixed air temperature (°C)
  • T1 = temperature of airstream 1 (°C)
  • Q1 = volumetric flow rate of airstream 1 (L/s, m³/s, or CFM)
  • T2 = temperature of airstream 2 (°C)
  • Q2 = volumetric flow rate of airstream 2 (same unit as Q1)

The formula assumes the two flows have the same density and specific heat, which is acceptable for air near ambient conditions. It is a direct application of energy conservation: the enthalpy of the mixture equals the sum of the enthalpies of the incoming streams.

Worked Example

Using the calculator defaults: return air at 24 °C with a flow of 400 L/s mixes with outdoor air at 35 °C with a flow of 100 L/s.

Step 1: Multiply each temperature by its flow:

  • Return: 24 × 400 = 9600 °C·L/s
  • Outdoor: 35 × 100 = 3500 °C·L/s

Step 2: Add the products: 9600 + 3500 = 13100 °C·L/s

Step 3: Add the flows: 400 + 100 = 500 L/s

Step 4: Divide: 13100 / 500 = 26.2 °C

The mixed air temperature is 26.2 °C, which matches the calculator output (rounded to one decimal).

Assumptions

  • No heat transfer to or from the ductwork (adiabatic mixing).
  • Air density and specific heat are constant and identical for both streams.
  • No moisture condensation or evaporation occurs during mixing.
  • Both airstreams are at the same pressure (typically near atmospheric).

When to Use This Calculator

HVAC engineers and technicians use mixed air temperature for several practical purposes:

  • Coil sizing: The mixed air temperature is the entering condition for the cooling or heating coil. A warmer mixed air temperature means a higher coil load.
  • Economizer checks: In mild weather, the outdoor air damper opens to use free cooling. Knowing the mixed temperature helps verify the economizer is working.
  • Ventilation compliance: ASHRAE 62.1 requires minimum outdoor air rates. The mixed temperature tells you what the supply temperature will be before conditioning.
  • Troubleshooting: If the measured mixed temperature is far from the calculated value, there may be a damper problem, sensor error, or duct leakage.

How to Read the Result

The result is the dry-bulb temperature of the combined airstream. It will always lie between the two entering temperatures, closer to the temperature of the larger flow. For example, if the return air is 24 °C and outdoor is 35 °C, the mixed temperature will be between 24 and 35 °C. The exact value depends on the flow ratio: a higher outdoor fraction pulls the mixture closer to the outdoor temperature.

If you need the wet-bulb temperature or enthalpy of the mixture, you cannot use a simple weighted average of temperatures—you must use a psychrometric chart or a full enthalpy calculation, because moisture content adds nonlinearity.

Common Mistakes and Pitfalls

  • Using different flow units: Both flows must be in the same unit (L/s, m³/s, CFM). If one is in CFM and the other in L/s, convert first (1 CFM = 0.4719 L/s).
  • Ignoring humidity: The dry-bulb formula works for sensible heat only. If the airstreams have very different humidity ratios, the true mixed enthalpy is not a simple temperature average.
  • Assuming equal densities: At extreme temperatures (e.g., -20 °C vs 50 °C), density differences are small but not zero. For most HVAC work, the error is under 1%.
  • Rounding too early: Round only the final answer. If you round intermediate products, you may get a slightly different result.

Practical Example: Sizing a Cooling Coil

Suppose a building needs 1000 L/s of supply air, with 20% outdoor air (200 L/s) at 35 °C and return air at 24 °C. The mixed temperature is (24×800 + 35×200)/1000 = 26.2 °C. The cooling coil must cool this air to, say, 12 °C supply. The coil load is then proportional to the temperature difference: 26.2 – 12 = 14.2 °C. If the outdoor air fraction were 30%, the mixed temperature would be 27.3 °C, and the coil load would be higher. This shows why minimizing outdoor air during peak cooling reduces energy use.

Limitations of the Simple Formula

The flow-weighted average works only for dry-bulb temperature under adiabatic conditions. In reality, duct heat gain or loss, fan heat, and moisture transfer can shift the actual temperature. For precise design, use a psychrometric chart or software that accounts for humidity and density. Also, the formula assumes the two airstreams mix completely; in poorly designed plenums, stratification can occur, meaning the measured temperature at one point may not represent the average.

Frequently Asked Questions

Can I use this for more than two airstreams?

Yes. Extend the formula to any number of streams: multiply each temperature by its flow, sum all products, then divide by the total flow. For example, with three streams, Tm = (T1Q1 + T2Q2 + T3Q3) / (Q1+Q2+Q3).

What if I only know the outdoor air fraction, not the flows?

You can use the fraction directly. If outdoor fraction is f, then Tm = (1–f)×Treturn + f×Toutdoor. For example, 25% outdoor air at 35 °C and return at 24 °C gives Tm = 0.75×24 + 0.25×35 = 26.75 °C.

Why does my measured mixed temperature differ from the calculated one?

Common causes include sensor inaccuracy, incomplete mixing (stratification), duct heat gain or loss, and damper leakage. Also, if the outdoor air intake is on a sunny roof, the sensor may read higher than the true outdoor temperature.

Does the formula work for heating as well as cooling?

Yes. The same weighted average applies whether you are mixing cold outdoor air with warm return air in winter or warm outdoor air with cool return air in summer. The result is always between the two temperatures.

Should I use °C or °F?

Either works, as long as you are consistent. The formula is linear, so the result in °F is the same as converting the °C result. For example, 26.2 °C = 79.2 °F. However, do not mix units (e.g., one temperature in °C and the other in °F).

What about wet-bulb temperature?

Wet-bulb temperature cannot be computed with a simple weighted average because it depends on humidity. You must use a psychrometric chart or a full enthalpy calculation. For approximate work, some engineers use the dry-bulb formula for wet-bulb, but this is only valid when the relative humidity of both streams is similar.

Related

Formula used
in t1 | Return air temp | °C | 24 | -40 | 60
in q1 | Return air flow | L/s | 400 | 0 | 10000
in t2 | Outdoor air temp | °C | 35 | -40 | 60
in q2 | Outdoor air flow | L/s | 100 | 0 | 10000
out tm | Mixed air temp | °C | (t1*q1 + t2*q2) / (q1 + q2) | 1

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work