Mixed Air Temperature: How to Calculate It

Calculator No. 01-7816 · Updated · Formula and assumptions shown below

The calculator on this page is switched off while it is checked. The formula is below, and the worked example shows how to do the sum by hand.

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

Mixed air temperature is the temperature of the combined airstream when two or more separate air streams (for example, outdoor fresh air and indoor return air) are blended together in a ventilation or HVAC system. You calculate it using a weighted average based on the mass (or volume) flow rate and dry-bulb temperature of each stream: Tmixed = (T1·Q1 + T2·Q2) / (Q1 + Q2).

Formula

The mixed air temperature is the flow-weighted average of the individual dry-bulb temperatures:

Tmixed = (T1 × Q1 + T2 × Q2) / (Q1 + Q2)

  • Tmixed – resulting mixed air dry-bulb temperature (°C or °F)
  • T1, T2 – dry-bulb temperatures of the two entering airstreams (°C or °F)
  • Q1, Q2 – volumetric airflow rates of the two streams (m³/h, L/s, or ft³/min)

The same formula extends to three or more streams: multiply each temperature by its flow, add the products, and divide by the total flow. The result is a straight weighted average, so it always lies between the lowest and highest entering temperatures.

Worked Example

Using the calculator defaults: return air at 22 °C with a flow of 3000 m³/h mixes with outdoor air at 35 °C at 1000 m³/h.

  1. Multiply each temperature by its flow: 22 × 3000 = 66,000; 35 × 1000 = 35,000.
  2. Add the products: 66,000 + 35,000 = 101,000.
  3. Add the flows: 3000 + 1000 = 4000 m³/h.
  4. Divide: 101,000 / 4000 = 25.25 °C.

The mixed air temperature is 25.25 °C, matching the calculator’s output. The outdoor fraction is 1000 / 4000 = 25%.

Assumptions

  • Air is treated as an incompressible fluid at constant density; volumetric flow ratios equal mass flow ratios.
  • No heat is added or removed within the mixing plenum (adiabatic mixing).
  • No moisture condensation occurs during mixing; the calculation uses dry-bulb temperature only.
  • Each airstream is well-mixed and uniform in temperature before blending.

Why Mixed Air Temperature Matters

HVAC designers use mixed air temperature to size cooling and heating coils. A coil must condition the mixed airstream, not just the return air, so knowing the blend temperature determines the coil’s load. For example, in mild climates the mixed temperature may be close to the return temperature, requiring little preheating; in extreme climates the outdoor fraction dominates and the coil must handle a much hotter or colder entering air.

The calculation also appears in economizer control: a building controller compares mixed air temperature with supply air setpoints to decide how much outdoor air to introduce. In energy modeling, mixed air temperature is the starting point for calculating fan and coil energy consumption. Even simple residential systems with a 20% outdoor air intake use the same weighted average to predict supply temperatures.

How to Choose the Airflow Values

Use the actual volumetric flow rates at the mixing point, not design maximums, when predicting real operating conditions. Common sources for these values:

  • Balancing reports from commissioning tests
  • Fan curves combined with measured static pressure
  • Pitot tube traverses of the ducts
  • Building management system (BMS) airflow sensors

If you only know the outdoor air fraction (for example, 15% outdoor air), you can still compute the mixed temperature: multiply the outdoor fraction by the outdoor temperature, multiply the return fraction (85%) by the return temperature, and add the two. This is mathematically identical to the flow-weighted formula because the fraction is Qoutdoor / (Qoutdoor + Qreturn).

Common Mistakes and Misconceptions

The most frequent error is averaging the temperatures without weighting by flow. Averaging 22 °C and 35 °C gives 28.5 °C, but the true mixed temperature with unequal flows is 25.25 °C — a difference of over 3 °C, enough to mis-size a coil. Another mistake is mixing units: if one flow is in L/s and the other in m³/h, convert first (1 m³/h = 0.2778 L/s). Temperature units must also match; the formula works in Celsius or Fahrenheit as long as you are consistent, but never mix them.

A common misconception is that humidity affects the dry-bulb mixed temperature. It does not. The dry-bulb temperature of a mixture depends only on the sensible heat content of each stream. However, the wet-bulb temperature (and therefore enthalpy) of the mixture is not a simple flow-weighted average of wet-bulb temperatures because it depends on the moisture content of each stream. If you need the mixed air enthalpy or wet-bulb temperature, you must first find the mixed humidity ratio (also a flow-weighted average of the absolute humidity values) and then use a psychrometric chart.

Limitations of the Simple Formula

The weighted-average formula assumes no heat transfer through the duct walls and no fan heat gain before the mixing point. In practice, long uninsulated ducts in hot attics or cold crawlspaces can add or remove heat, shifting the actual mixed temperature. Fan energy also heats the air slightly — typically 0.5 to 2 °C depending on fan pressure and efficiency — so the temperature at the coil may be a bit higher than the calculated mixed temperature.

Another limitation is that the formula uses volumetric flow, which varies with air density. At sea level and typical HVAC temperatures (10–40 °C), density variation is small enough that volumetric weighting is accurate to within a few percent. At high altitudes or extreme temperatures, mass-flow weighting would be more precise, but for most design work the volumetric average is standard practice.

Frequently Asked Questions

Does mixed air temperature change with humidity? No, the dry-bulb temperature of the mixture is independent of humidity. Humidity affects the enthalpy and wet-bulb temperature, but the dry-bulb temperature is a pure sensible-heat weighted average.

Can I use this formula for three or more airstreams? Yes. Extend it by adding each temperature-flow product in the numerator and the sum of all flows in the denominator. The result is still a single weighted average.

What if the outdoor air fraction is given as a percentage? Multiply the outdoor temperature by the fraction (as a decimal), multiply the return temperature by (1 − fraction), and add. For 25% outdoor air at 35 °C and return at 22 °C: (0.25 × 35) + (0.75 × 22) = 8.75 + 16.5 = 25.25 °C.

Should I use dry-bulb or wet-bulb temperature? For coil sizing and sensible load calculations, use dry-bulb temperature. For cooling coil dehumidification design, you need the mixed air enthalpy, which requires wet-bulb or dew-point data and a psychrometric analysis.

Is the mixed temperature the same as the supply air temperature? No. The supply temperature is measured after the cooling or heating coil and the fan. The mixed temperature is the coil’s entering air temperature; the supply temperature is the coil’s leaving air temperature (plus any fan heat).

How accurate is this for real systems? Within a few degrees if the ducts are short and insulated and the flow measurements are reliable. Discrepancies usually come from unmeasured duct heat gain, fan heat, or inaccurate flow readings rather than from the formula itself.

Related

Formula used
in t1 | Temperature of stream 1 | °C | 22 | -273.15 | 200
in q1 | Airflow of stream 1 | m³/h | 3000 | 0 | 100000
in t2 | Temperature of stream 2 | °C | 35 | -273.15 | 200
in q2 | Airflow of stream 2 | m³/h | 1000 | 0 | 100000
out tm | Mixed air temperature | °C | (t1 * q1 + t2 * q2) / (q1 + q2) | 2
out r1 | Stream 1 fraction | % | q1 / (q1 + q2) * 100 | 1

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.