The mixed air temperature equation calculates the temperature of air after two or more airstreams combine, using the dry-bulb temperature and mass flow rate of each stream. You enter the temperature and airflow (or mass flow) of each airstream, and the calculator returns the resulting mixed air temperature. This is the standard method used in HVAC design to predict the temperature at a mixing box or return-air plenum.
Formula
The mixed air temperature is the mass-weighted average of the individual dry-bulb temperatures:
Tmix = (T1 × m1 + T2 × m2) / (m1 + m2)
- Tmix – mixed air dry-bulb temperature (°C or °F)
- T1, T2 – dry-bulb temperatures of the entering airstreams (°C or °F)
- m1, m2 – mass flow rates of the entering airstreams (kg/s or lb/min)
If you have volumetric flow rates (m³/s or CFM) instead of mass flows, multiply each by the air density at that stream’s condition. For most HVAC room-air mixing, density is close enough to 1.2 kg/m³ at 20°C that using volume flow directly gives a small error (usually under 2%). The exact form uses mass flow because energy conservation is based on mass, not volume.
Worked Example
Using the calculator defaults: return air at 22°C with 1.2 kg/s mixes with outdoor air at 35°C with 0.8 kg/s.
- Multiply each temperature by its mass flow: 22 × 1.2 = 26.4 and 35 × 0.8 = 28.0
- Add the products: 26.4 + 28.0 = 54.4
- Add the mass flows: 1.2 + 0.8 = 2.0
- Divide: 54.4 / 2.0 = 27.2°C
The mixed air temperature is 27.2°C, which the calculator rounds to two decimals. Notice it is closer to 22°C than to 35°C because the 22°C stream has a larger mass flow.
Assumptions
- Steady-state flow – conditions do not change over time.
- No heat transfer to or from the duct walls – adiabatic mixing.
- No moisture condensation or evaporation during mixing (sensible heat only).
- Constant specific heat of air – valid for typical HVAC temperature ranges.
- Mass flow rates are known or approximated from density and volumetric flow.
When to Use This Equation
HVAC engineers use this equation to find the temperature of air entering a cooling coil or heat exchanger when a building recirculates return air and mixes it with outdoor ventilation air. The mixed air temperature determines the coil load, the supply air temperature, and the size of the cooling equipment. It also appears in economizer control: when the outdoor air is cool enough, the controller increases the outdoor air fraction to reduce mechanical cooling. The same mass-weighted average applies when mixing more than two streams – just add all products in the numerator and all flows in the denominator.
You also see this equation in laboratory ventilation, cleanroom makeup air, and any process where two gas streams at different temperatures combine. The principle is identical for any fluid, but air is the most common application.
How to Choose Between Mass and Volume Flow
If you have volumetric flow rates (e.g., 0.5 m³/s and 1.0 m³/s), you can use them directly only when the densities are equal. In HVAC, return air and outdoor air at typical conditions have densities within a few percent of each other, so using volume flow gives a reasonable estimate. For precise work, convert volume flow to mass flow:
- Mass flow (kg/s) = volumetric flow (m³/s) × density (kg/m³)
- Air density at sea level and 20°C is about 1.204 kg/m³
- At higher altitudes or extreme temperatures, use the ideal gas law: density = P / (R × T), where P is absolute pressure in Pa, R = 287 J/(kg·K) for dry air, and T is absolute temperature in kelvin
For example, if you have 0.5 m³/s at 35°C and 1.0 m³/s at 22°C, first convert each to mass flow using densities of 1.146 kg/m³ (at 35°C) and 1.197 kg/m³ (at 22°C): m1 = 0.573 kg/s, m2 = 1.197 kg/s. Then the mixed temperature = (35×0.573 + 22×1.197) / (0.573 + 1.197) = 26.2°C. Using volume flow directly would give (35×0.5 + 22×1.0) / 1.5 = 26.3°C – a small difference.
Common Mistakes and Misconceptions
The most frequent error is using volume flow without accounting for density differences, especially when one stream is much hotter or at high altitude. Another mistake is averaging temperatures without weighting – simply taking (22 + 35)/2 = 28.5°C, which is wrong unless both flows are equal. A third error is mixing up Celsius and kelvin: the equation works in either scale as long as you are consistent, but the result will be in the same scale you input. However, when computing density from the ideal gas law, you must use kelvin.
A common misconception is that the mixed air temperature is the same as the wet-bulb temperature or that it accounts for humidity. It does not – it is only the dry-bulb temperature. If the airstreams have different humidity ratios, the mixed air enthalpy and humidity ratio also need to be calculated separately using a psychrometric chart or formula. The dry-bulb temperature alone is insufficient for coil load calculations.
Limits of the Equation
The equation assumes perfect mixing and no heat loss. In reality, duct walls, fans, and fittings add or remove heat, so the actual temperature at the mixing point may differ by a degree or two. If the airstreams are at very different temperatures, the density difference becomes more significant, and using mass flow is essential. The equation also fails if condensation occurs during mixing – for example, mixing cold dry air with warm humid air can cause fogging, and the latent heat released changes the temperature. In such cases, use a psychrometric analysis that includes moisture.
For most building HVAC designs, the simple mass-weighted average is accurate enough. The error from ignoring density differences is usually under 1°C when the temperature difference between streams is less than 20°C. For extreme conditions, such as mixing very hot exhaust with cold outdoor air, use the full energy balance with enthalpy.
Frequently Asked Questions
Can I use CFM instead of kg/s in the equation?
Yes, if both airstreams have the same density. In typical indoor conditions, using CFM (cubic feet per minute) directly gives a close approximation. For more accurate results, convert CFM to mass flow by multiplying by air density (about 0.075 lb/ft³ at standard conditions). The calculator uses mass flow, so you would need to convert your CFM values to kg/s (1 CFM = 0.0004719 m³/s, then multiply by density).
What if I have three or more airstreams?
Extend the equation: multiply each temperature by its mass flow, sum all products, then divide by the sum of all mass flows. For example, with three streams: T_mix = (T1×m1 + T2×m2 + T3×m3) / (m1 + m2 + m3). The calculator here handles two streams, but the principle is the same.
Does the mixed air temperature change with humidity?
Not the dry-bulb temperature – that is a direct result of sensible heat mixing. However, humidity affects the enthalpy and the wet-bulb temperature. If you need to know the cooling coil load, you must also calculate the mixed air humidity ratio and enthalpy, not just the dry-bulb temperature.
How do I convert between mass flow and volumetric flow?
Use the density of air at the stream’s temperature and pressure. Mass flow = volumetric flow × density. For air, density can be approximated as 1.2 kg/m³ at 20°C and sea level. For more precision, use the ideal gas law: density = P / (R_specific × T), where R_specific for dry air is 287 J/(kg·K) and T is in kelvin.
Is the mixed air temperature the same as the supply air temperature?
No. The mixed air temperature is the temperature after mixing but before any heating or cooling. The supply air temperature is after the coil or heat exchanger. The difference between them determines the coil load. The mixed air temperature is an input to the coil load calculation, not the output.