Mixed Air Wet Bulb Temperature Equation

Calculator No. 01-8383 · Updated · Formula and assumptions shown below

Mixed air dry bulb temp 26.75 °C
Mixed air humidity ratio
0.0125 kg/kg
Result, rounded to 4 decimal places
Mixed air enthalpy
58.79 kJ/kg
Result, rounded to 2 decimal places
Mixed air wet bulb temp
26.75 °C
Result, rounded to 2 decimal places
You enter
Mass flow of airstream 1 (kg/s), Dry bulb temp of airstream 1 (°C), Humidity ratio of airstream 1 (kg/kg), Mass flow of airstream 2 (kg/s), Dry bulb temp of airstream 2 (°C), Humidity ratio of airstream 2 (kg/kg)
You get
Mixed air dry bulb temp (°C), Mixed air humidity ratio (kg/kg), Mixed air enthalpy (kJ/kg), Mixed air wet bulb temp (°C)
Rounding
2 dp · 4 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

The mixed air wet bulb temperature is the wet bulb temperature of the air stream after two or more airstreams with different conditions are mixed together. You calculate it by first finding the mixed air enthalpy and humidity ratio using mass-weighted averages, then using those to find the wet bulb temperature from the psychrometric chart or a suitable equation. This value is essential for sizing cooling coils and predicting the performance of HVAC systems that mix return air with outdoor air.

Formula

The mixed air wet bulb temperature is not calculated directly from a simple equation. Instead, you must first determine the mixed air dry bulb temperature and humidity ratio using mass-weighted averages, then compute the mixed air enthalpy, and finally solve for the wet bulb temperature using the enthalpy equation. The key formulas are:

  • Mixed air dry bulb temperature: Tm = (m1T1 + m2T2) / (m1 + m2)
  • Mixed air humidity ratio: Wm = (m1W1 + m2W2) / (m1 + m2)
  • Mixed air enthalpy: hm = 1.006 Tm + Wm (2501 + 1.86 Tm) kJ/kg
  • Wet bulb temperature (approximate, for unsaturated air): Twb ≈ (hm − 2501 Wm) / (1.006 + 1.86 Wm)

Where:

  • m1, m2 = mass flow rates of the two airstreams (kg/s)
  • T1, T2 = dry bulb temperatures of the two airstreams (°C)
  • W1, W2 = humidity ratios of the two airstreams (kg water per kg dry air)
  • Tm = mixed air dry bulb temperature (°C)
  • Wm = mixed air humidity ratio (kg/kg)
  • hm = mixed air enthalpy (kJ/kg dry air)
  • Twb = mixed air wet bulb temperature (°C)

The enthalpy equation is a common approximation for moist air at standard atmospheric pressure, using 1.006 kJ/kg·°C for the specific heat of dry air, 1.86 kJ/kg·°C for water vapor, and 2501 kJ/kg for the latent heat of vaporization at 0°C.

Worked Example

Let’s use the default values from the calculator: airstream 1 has a mass flow of 1.5 kg/s, dry bulb 24°C, humidity ratio 0.010 kg/kg; airstream 2 has 0.5 kg/s, 35°C, 0.020 kg/kg.

Step 1: Mixed air dry bulb temperature
Tm = (1.5 × 24 + 0.5 × 35) / (1.5 + 0.5) = (36 + 17.5) / 2.0 = 53.5 / 2.0 = 26.75°C

Step 2: Mixed air humidity ratio
Wm = (1.5 × 0.010 + 0.5 × 0.020) / 2.0 = (0.015 + 0.010) / 2.0 = 0.025 / 2.0 = 0.0125 kg/kg

Step 3: Mixed air enthalpy
hm = 1.006 × 26.75 + 0.0125 × (2501 + 1.86 × 26.75)
= 26.9105 + 0.0125 × (2501 + 49.755)
= 26.9105 + 0.0125 × 2550.755
= 26.9105 + 31.8844 = 58.7949 kJ/kg

Step 4: Wet bulb temperature
Twb = (58.7949 − 2501 × 0.0125) / (1.006 + 1.86 × 0.0125)
= (58.7949 − 31.2625) / (1.006 + 0.02325)
= 27.5324 / 1.02925 = 26.75°C

So the mixed air wet bulb temperature is approximately 26.75°C. Interestingly, in this case it equals the dry bulb temperature because the air is saturated (the humidity ratio corresponds to saturation at that temperature). In general, the wet bulb will be lower than the dry bulb for unsaturated air.

Assumptions

  • The two airstreams mix adiabatically (no heat transfer to or from the surroundings).
  • The mixing process occurs at constant total pressure, typically atmospheric pressure.
  • Moist air behaves as an ideal gas mixture.
  • The enthalpy equation used is an approximation valid for temperatures between about 0°C and 60°C and humidity ratios up to about 0.03 kg/kg.
  • Mass flow rates are measured on a dry-air basis, not including the water vapor.

Why Mixing Matters in HVAC

In most commercial buildings, a portion of the return air from the occupied space is mixed with fresh outdoor air before being cooled or heated. This mixed air is then conditioned and supplied to the space. The wet bulb temperature of this mixed air determines the heat transfer rate in the cooling coil. A higher wet bulb temperature means the air has more enthalpy, so the coil must remove more heat and moisture. Engineers use the mixed air wet bulb temperature to select the coil size, airflow rate, and chilled water temperature to achieve the desired supply air conditions.

For example, if outdoor air is hot and humid (say 35°C dry bulb, 24°C wet bulb) and return air is at 24°C dry bulb, 50% relative humidity (wet bulb about 17°C), mixing them in a 1:3 ratio (outdoor to return) yields a mixed air condition that is cooler and drier than the outdoor air alone. The wet bulb of the mixture will be somewhere between the two, weighted by the flow rates. This is why energy recovery ventilators and economizers work: they take advantage of the return air’s lower enthalpy to reduce the load on the coil.

How to Use the Calculator

Enter the mass flow rate (in kg/s), dry bulb temperature (°C), and humidity ratio (kg water per kg dry air) for each of the two airstreams. The humidity ratio is the mass of water vapor divided by the mass of dry air. If you know the relative humidity and dry bulb temperature, you can find the humidity ratio from a psychrometric chart or a formula. The calculator then computes the mixed air dry bulb, humidity ratio, enthalpy, and wet bulb temperature.

The wet bulb temperature is the most important output for coil sizing. It is the temperature a thermometer with a wet wick would read if exposed to the mixed air. It is always lower than or equal to the dry bulb temperature, and equal only when the air is saturated (100% relative humidity).

If you have more than two airstreams, you can combine them two at a time: first mix stream 1 and 2, then mix the result with stream 3, and so on. The order does not matter because the mixing equations are linear.

Common Mistakes and Misconceptions

  • Using volume flow instead of mass flow: The mixing equations require mass flow rates, not volumetric flow rates (e.g., CFM or m³/s). If you only have volume flow, you must multiply by the air density (about 1.2 kg/m³ at standard conditions) to get mass flow. Air density changes with temperature and altitude, so using a constant can introduce errors.
  • Confusing wet bulb with dew point: The wet bulb temperature is the temperature of adiabatic saturation, while the dew point is the temperature at which water vapor begins to condense. They are different except at saturation. The wet bulb is always higher than the dew point for unsaturated air.
  • Assuming the wet bulb is a simple average: You cannot average the wet bulb temperatures of the two streams directly. You must average the enthalpy and humidity ratio, then back out the wet bulb. The calculator does this for you.
  • Using the wrong units: Ensure temperatures are in °C and humidity ratios are in kg/kg (not g/kg). If you have humidity ratio in g/kg, divide by 1000 before entering.

Limitations of the Approximate Equation

The wet bulb temperature equation used here is derived from the enthalpy balance and assumes that the Lewis number is 1, which is a good approximation for air-water vapor mixtures. However, it is an approximation that works best for unsaturated air at temperatures between 0°C and 60°C. At very high humidity ratios or temperatures, the specific heat of water vapor and the latent heat vary slightly, so the result may differ by a few tenths of a degree from a more precise psychrometric calculation. For most HVAC design work, this accuracy is sufficient.

If you need a more precise value, you can use a psychrometric chart or a more sophisticated equation that iteratively solves for the wet bulb using the saturation pressure curve. The calculator’s result should be within 0.1°C for typical conditions.

Frequently Asked Questions

Q: What is the difference between wet bulb and dry bulb temperature?
Dry bulb temperature is the ordinary air temperature measured with a standard thermometer. Wet bulb temperature is measured with a thermometer whose bulb is covered with a wet wick and ventilated. Evaporation of water from the wick cools the thermometer, so the wet bulb is lower than the dry bulb unless the air is saturated. The wet bulb indicates the cooling capacity of the air.

Q: Can I use this calculator for mixing more than two airstreams?
Yes. Mix the first two streams using the calculator, then take the result as stream 1 and mix it with the third stream, and so on. The final wet bulb temperature will be the same regardless of the order of mixing.

Q: What if I only have relative humidity instead of humidity ratio?
You need to convert relative humidity to humidity ratio using the saturation pressure at the dry bulb temperature. Many psychrometric charts and online calculators can do this. Alternatively, you can use the approximation: W ≈ 0.622 × (φ × Pws) / (P − φ × Pws), where φ is relative humidity, Pws is saturation pressure, and P is total pressure.

Q: Why is the mixed air wet bulb temperature lower than the average of the two wet bulb temperatures?
The wet bulb temperature is not a linear function of enthalpy and humidity ratio. Since the wet bulb is determined by both heat and mass transfer, the mixing process is nonlinear. The calculator correctly accounts for this by computing the mixed enthalpy and humidity ratio first.

Q: Is the wet bulb temperature the same as the temperature of the air leaving a cooling coil?
No. The air leaving a cooling coil may be cooler than the wet bulb temperature if the coil surface temperature is below the dew point, causing condensation. The wet bulb temperature of the entering air is used to calculate the coil’s capacity, but the leaving air condition depends on the coil design and bypass factor.

Q: Does altitude affect the calculation?
Yes, because air density and saturation pressure change with altitude. The calculator assumes standard atmospheric pressure at sea level. At higher altitudes, the humidity ratio for a given relative humidity is lower, and the enthalpy equation should use a slightly different latent heat. For most applications, the error is small below 1500 m, but for high-altitude work, use a psychrometric chart adjusted for the local pressure.

Related

Formula used
in m1 | Mass flow of airstream 1 | kg/s | 1.5 | 0
in t1 | Dry bulb temp of airstream 1 | °C | 24 | -40
in w1 | Humidity ratio of airstream 1 | kg/kg | 0.010 | 0
in m2 | Mass flow of airstream 2 | kg/s | 0.5 | 0
in t2 | Dry bulb temp of airstream 2 | °C | 35 | -40
in w2 | Humidity ratio of airstream 2 | kg/kg | 0.020 | 0
out tm | Mixed air dry bulb temp | °C | (m1 * t1 + m2 * t2) / (m1 + m2) | 2
out wm | Mixed air humidity ratio | kg/kg | (m1 * w1 + m2 * w2) / (m1 + m2) | 4
out hm | Mixed air enthalpy | kJ/kg | 1.006 * tm + wm * (2501 + 1.86 * tm) | 2
out twb | Mixed air wet bulb temp | °C | (hm - 2501 * wm) / (1.006 + 1.86 * wm) | 2

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.