Pressure to CFM Calculator: How to Convert

Calculator No. 01-11951 · Updated · Formula and assumptions shown below

Airflow 10.25 CFM
Velocity
470 ft/min
Result, rounded to a whole number
Pressure drop
1 inH2O
Set in the form below
Orifice diameter
2 in
Set in the form below
You enter
Pressure drop (inH2O), Orifice diameter (in), Discharge coefficient
You get
Airflow (CFM), Velocity (ft/min)
Rounding
2 dp · 0 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

A pressure to CFM calculator converts a pressure drop (in inches of water column, psi, or pascals) across an orifice or duct into an airflow rate in cubic feet per minute (CFM). You enter the pressure difference, the orifice or duct dimensions, and a discharge coefficient, and the calculator returns the volumetric flow rate. This is the standard approach used in HVAC balancing, exhaust system design, and leak testing.

Formula

The calculator uses the orifice flow equation derived from Bernoulli’s principle:

Q = Cd × A × √(2 × ΔP / ρ)

Where:

  • Q = volumetric flow rate in cubic feet per second (then converted to CFM by multiplying by 60)
  • Cd = discharge coefficient (dimensionless, typically 0.62 for a sharp-edged orifice)
  • A = cross-sectional area of the opening in square feet (for a circle: π × (d/2)2, with d in inches converted to feet by dividing by 12)
  • ΔP = pressure drop in pascals (1 inH2O = 249.088 Pa)
  • ρ = air density in kg/m³ (default 1.204 kg/m³ at 20°C, 50% RH, sea level)

The expression in the calculator combines these: 0.621 is the conversion factor that accounts for the unit conversions (inH2O to Pa, inches to feet, seconds to minutes) and the default air density. The full formula with units is: CFM = 60 × Cd × (π/4) × (d/12)² × √(2 × (p × 249.088) / 1.204).

Worked Example

Using the default values: pressure drop = 1.0 inH2O, orifice diameter = 2.0 inches, discharge coefficient = 0.62.

  1. Convert pressure to pascals: ΔP = 1.0 × 249.088 = 249.088 Pa
  2. Convert diameter to feet: d = 2.0 / 12 = 0.16667 ft
  3. Calculate area: A = π × (0.16667/2)² = π × 0.006944 = 0.021817 ft²
  4. Calculate the velocity head term: √(2 × 249.088 / 1.204) = √(413.76) = 20.341 m/s
  5. Flow in m³/s: Q = 0.62 × 0.021817 × 20.341 = 0.2752 m³/s
  6. Convert to CFM: 0.2752 m³/s × 2118.88 (ft³/min per m³/s) = 583.2 CFM

The calculator gives 583.2 CFM (rounded to two decimals). The velocity output is 583.2 / 0.021817 = 26730 ft/min, which is unrealistically high for a 2-inch orifice at 1 inH2O—this highlights that the discharge coefficient for a real venturi or duct fitting is often lower, and the pressure drop across a long duct is not the same as across an orifice.

Assumptions

  • Air is incompressible (valid for low pressure drops, typically < 10 inH2O)
  • Steady, turbulent flow through a sharp-edged orifice
  • Air density is constant at 1.204 kg/m³ (20°C, 50% RH, sea level)
  • The pressure drop is measured across the orifice, not along a duct
  • The discharge coefficient accounts for vena contracta and friction losses

When to Use This Calculator

You use a pressure-to-CFM conversion when you have a known pressure differential and need to estimate the airflow through a specific opening. Common applications include:

  • Balancing HVAC supply and return ducts by measuring static pressure across a balancing damper.
  • Estimating exhaust fan performance from a manometer reading across a hood opening.
  • Checking the flow rate of a compressed air leak using a pressure gauge and an orifice model.
  • Designing a test rig for filter pressure drop vs. flow.

The result is an estimate, not a precise measurement. For accurate duct traversals, you would use a pitot tube and a flow hood.

How to Read the Result

The CFM output is the volumetric flow at the actual air density. If your site is at high altitude or high temperature, the mass flow will be lower than the CFM suggests. For HVAC work, you often want standard CFM (SCFM) at 1 atm and 20°C; the calculator assumes that condition, so the CFM is effectively SCFM. If you need mass flow, multiply CFM by air density (in lb/ft³) to get pounds per minute.

The velocity output (ft/min) is the average velocity through the opening. Compare it to recommended face velocities for hoods (typically 100-200 ft/min for fume hoods) to check if the flow is adequate.

Common Mistakes and Misconceptions

One major mistake is using the pressure drop across a length of duct as if it were across an orifice. Duct friction causes a pressure drop that is not related to velocity by the simple orifice equation; you need the Darcy-Weisbach equation with a friction factor. Another mistake is using the wrong discharge coefficient: 0.62 is for a sharp-edged orifice, but a rounded inlet (like a bell mouth) can have Cd near 0.98, which increases flow by 58%. Also, mixing units: pressure in psi must be converted to inH2O (1 psi = 27.68 inH2O) before using this calculator.

A common misconception is that CFM is a fixed property of a fan. In reality, CFM depends on the system resistance: a fan will deliver more CFM at lower static pressure. This calculator helps you estimate the flow for a given pressure drop, but you need the fan curve to know the operating point.

Limitations of the Orifice Equation

The orifice equation assumes the pressure drop is entirely converted to kinetic energy, which is true only for a thin plate with sharp edges. For long ducts, nozzles, or venturis, the discharge coefficient changes. Also, the equation does not account for compressibility effects when the pressure drop exceeds about 10% of the absolute pressure. For high-pressure compressed air (100 psi), the flow is choked and the equation is invalid; you would use the ASME nozzle equation instead.

Air density varies with temperature and altitude. At 40°C, air density drops to about 1.127 kg/m³, which would increase CFM by about 1.5% for the same pressure drop. For precision work, adjust the density input or correct the result using the ideal gas law.

Frequently Asked Questions

How do I convert psi to CFM? You can’t directly convert psi to CFM because they measure different things. You need an orifice or duct geometry. Use a pressure gauge to measure the pressure drop across a known opening, then apply the orifice equation as this calculator does. For example, a 1 psi drop across a 4-inch sharp-edged orifice gives about 1,100 CFM.

What is a good discharge coefficient for a round duct? For a sharp-edged orifice, use 0.62. For a rounded entrance (bell mouth), use 0.95-0.98. For a short pipe stub (length < 3 diameters), use 0.8. If you don't know, 0.62 is the conservative choice.

Why does my measured CFM not match the calculator? The most common reasons are: the pressure tap location (must be upstream and downstream of the orifice, not at the fan), the actual air density (temperature and altitude), and the discharge coefficient not matching your geometry. Also, if there are leaks in the system, the measured pressure drop will be lower than expected.

Can I use this for compressed air? Only for low-pressure drops (less than about 10% of absolute pressure). For compressed air at 100 psi, the flow is compressible and you need a different formula. This calculator is for HVAC and low-pressure ventilation.

What is the difference between CFM and SCFM? CFM is the actual volumetric flow at the existing pressure and temperature. SCFM is the flow converted to standard conditions (usually 1 atm, 20°C). This calculator assumes standard conditions, so the output is effectively SCFM. If your air is warmer or at altitude, the actual CFM will be higher than the SCFM.

Do I need to account for the duct length? Yes, if the pressure drop is measured across a long duct, the orifice equation is not valid. For ducts, use the Darcy-Weisbach equation with the duct diameter, length, and friction factor. This calculator is for flow through an opening, not through a duct.

Safety and Accuracy Notes

Always follow your lab or facility’s safety procedures when measuring pressure and airflow. Use a calibrated manometer or pressure transducer. For ventilation systems, ensure that the airflow meets local codes and guidelines (e.g., fume hood face velocity). This calculator is for engineering estimation; for critical applications, verify with a calibrated flow hood or anemometer.

Related

Formula used
in p | Pressure drop | inH2O | 1.0 | 0.001 | 100
in d | Orifice diameter | in | 2.0 | 0.1 | 24
in cd | Discharge coefficient | - | 0.62 | 0.1 | 1.0
out cfm | Airflow | CFM | 0.621 * cd * (pi/4) * (d/12)^2 * sqrt(2 * (p * 249.088) / 1.204) * 60 | 2
out vel | Velocity | ft/min | cfm / ((pi/4) * (d/12)^2) | 0

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.