Specific Enthalpy of Air: Formula & Calculator

Calculator No. 01-7813 · Updated · Formula and assumptions shown below

The calculator on this page is switched off while it is checked. The formula is below, and the worked example shows how to do the sum by hand.

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

This calculator determines the specific enthalpy of moist air (kJ/kg of dry air) from its dry-bulb temperature, relative humidity, and absolute pressure. You enter those three values and get the specific enthalpy, which is the total heat content per kilogram of dry air, including the heat in the water vapor it carries.

where pw = 0.61094 * exp(17.625 * t / (t + 243.04)) kPa (saturation vapor pressure) and x is the humidity ratio computed in the second output.

Formula

The specific enthalpy of moist air h (kJ/kg dry air) is calculated with the standard psychrometric equation:

h = cpa · t + x · (hfg0 + cpv · t)

  • cpa = specific heat of dry air at constant pressure ≈ 1.006 kJ/(kg·°C)
  • t = dry-bulb temperature in °C
  • x = humidity ratio (kg water vapor per kg dry air), dimensionless
  • hfg0 = latent heat of vaporization of water at 0 °C ≈ 2501 kJ/kg
  • cpv = specific heat of water vapor ≈ 1.86 kJ/(kg·°C)

The humidity ratio x comes from the relative humidity φ (as a fraction) and the saturation pressure pws:

x = 0.621945 · (φ · pws) / (p − φ · pws)

where the saturation pressure pws (kPa) is given by the Magnus formula:

pws = 0.61094 · exp(17.625 · t / (t + 243.04))

The constant 0.621945 is the ratio of the molar mass of water (18.015 g/mol) to that of dry air (28.97 g/mol).

Worked Example

Calculate the specific enthalpy of air at 25 °C, 50 % relative humidity, and standard atmospheric pressure 101.325 kPa.

Step 1: Saturation pressure

pws = 0.61094 · exp(17.625 × 25 / (25 + 243.04)) = 0.61094 · exp(17.625 × 25 / 268.04) = 0.61094 · exp(1.6436) = 0.61094 × 5.1728 = 3.160 kPa

Step 2: Humidity ratio

x = 0.621945 × (0.50 × 3.160) / (101.325 − 0.50 × 3.160) = 0.621945 × 1.580 / (101.325 − 1.580) = 0.621945 × 1.580 / 99.745 = 0.621945 × 0.015840 = 0.009852 kg/kg

Step 3: Specific enthalpy

h = 1.006 × 25 + 0.009852 × (2501 + 1.86 × 25) = 25.15 + 0.009852 × (2501 + 46.5) = 25.15 + 0.009852 × 2547.5 = 25.15 + 25.10 = 50.25 kJ/kg dry air

The calculator returns 50.25 kJ/kg dry air, matching this result.

Assumptions

  • Moist air behaves as an ideal gas mixture of dry air and water vapor.
  • The Magnus formula gives saturation pressure over liquid water (valid roughly −40 °C to 60 °C).
  • Specific heats are constant over the temperature range.
  • The reference state is 0 °C for both dry air and liquid water (enthalpy = 0 at 0 °C).
  • No dissolved gases or contaminants in the water vapor.

When to Use Specific Enthalpy

Specific enthalpy of air is the central quantity in HVAC design, drying processes, cooling tower analysis, and any calculation involving air heating, cooling, humidification, or dehumidification. It tells you the total energy per kilogram of dry air, so it is the number you use in energy balances for air-handling units.

For example, if you heat air from 10 °C to 30 °C at constant humidity ratio, the enthalpy increase tells you the heater load. If you cool air below its dew point, the enthalpy drop includes both sensible cooling and the latent heat removed when water vapor condenses.

Psychrometric charts plot specific enthalpy as diagonal lines. Reading enthalpy directly off a chart is faster than calculating, but the calculator gives more precision and works for non-standard pressures.

How to Read the Result

The result is in kJ per kilogram of dry air, not per kilogram of moist air. This is a deliberate convention: dry air mass stays constant through heating, cooling, and humidification, while water vapor mass changes. Using dry air as the basis makes energy balances simpler.

A value of 50 kJ/kg at 25 °C and 50 % RH is typical for mild, comfortable indoor air. At 30 °C and 80 % RH, enthalpy rises to roughly 90 kJ/kg because of the extra water vapor. At 0 °C and 100 % RH, enthalpy is about 9.4 kJ/kg—mostly latent heat from the moisture, since sensible heat is near zero.

For sizing equipment, compare enthalpy differences, not absolute values. The enthalpy difference between outdoor air and supply air, multiplied by the mass flow rate of dry air, gives the cooling or heating load in kW.

Common Mistakes

  • Using relative humidity as a fraction instead of a percentage. The calculator expects 0–100; a common error is entering 50 instead of 0.50 in a manual formula.
  • Forgetting the pressure term. At altitude, atmospheric pressure is lower, which increases the humidity ratio for the same RH and temperature, raising enthalpy.
  • Confusing specific enthalpy with specific internal energy. Enthalpy includes the p·v work term; for air at atmospheric pressure the difference is small but not negligible in precise work.
  • Using total air mass instead of dry air mass. Always divide the moist air flow by (1 + x) to get dry air flow before applying enthalpy.
  • Rounding saturation pressure too early. Small errors in pws propagate into x and then into h; keep at least three significant figures in intermediate steps.

Limits of the Formula

The Magnus formula for saturation pressure is accurate to about 0.1 % between 0 °C and 50 °C, degrading slightly at the extremes. Below −40 °C, saturation over ice should be used instead of over liquid water; the difference in enthalpy is small but matters in high-altitude and cryogenic applications.

At very high pressures (above roughly 200 kPa), the ideal gas assumption for water vapor becomes less accurate, and real-gas corrections are needed. At very low pressures (below 30 kPa), the formula still works but the humidity ratio can approach the maximum allowed by the pressure, and the calculator will show an error if the partial pressure of water exceeds total pressure.

The specific heat values (1.006 and 1.86 kJ/kg·°C) are constant in this model. Over a 100 °C span, the error from this simplification is under 1 %, acceptable for most engineering work.

Frequently Asked Questions

What is the difference between specific enthalpy and relative humidity?

Relative humidity is a ratio of how much water vapor is in the air compared to the maximum it can hold at that temperature—it has no energy units. Specific enthalpy is an energy content per kilogram of dry air. Two air samples with the same RH can have very different enthalpies if their temperatures differ; enthalpy captures both temperature and moisture content in one number.

Why is enthalpy per kg of dry air, not per kg of moist air?

Because the mass of dry air in a process stays constant while water vapor is added or removed. If you used total moist air mass, you would have to track the changing mass, making energy balances much more complicated. The dry-air basis is the universal convention in psychrometrics.

Does altitude affect specific enthalpy?

Yes. At higher altitude, atmospheric pressure is lower, so the air can hold more water vapor for the same relative humidity and temperature. More water vapor means more latent heat, so specific enthalpy increases. For example, at 2000 m elevation (about 79.5 kPa), air at 25 °C and 50 % RH has an enthalpy of about 56 kJ/kg versus 50 kJ/kg at sea level.

How do I convert specific enthalpy to total heat load?

Multiply the enthalpy difference (kJ/kg) by the dry air mass flow rate (kg/s). The result is in kW. For example, moving 1.2 kg/s of dry air and changing its enthalpy from 40 to 80 kJ/kg requires 1.2 × 40 = 48 kW of heating or cooling.

What is the enthalpy of completely dry air?

When relative humidity is 0 %, the humidity ratio x is zero, and the formula reduces to h = 1.006 × t. At 25 °C, dry air has an enthalpy of 25.15 kJ/kg. This is pure sensible heat; there is no latent component.

Can I use this for air at temperatures above 60 °C?

The Magnus formula becomes less accurate above 60 °C, and at 100 °C the saturation pressure equals atmospheric pressure, so the humidity ratio formula breaks down at standard pressure. For high-temperature drying or combustion air, use steam tables or a real-gas psychrometric model instead.

Related

Formula used
in t | Dry-bulb temperature | °C | 25 | -40 | 60
in rh | Relative humidity | % | 50 | 0 | 100
in p | Absolute pressure | kPa | 101.325 | 30 | 200
out h | Specific enthalpy | kJ/kg dry air | 1.006 * t + x * (2501 + 1.86 * t) | 2
out x | Humidity ratio | kg water/kg dry air | (0.621945 * (rh/100 * pw / (p - rh/100 * pw))) | 5

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.