The mixed air temperature calculator determines the temperature of air after two or more airstreams combine in a duct, such as return air mixing with outdoor ventilation air in an HVAC system. You enter the temperatures and flow rates of the two incoming airstreams, and the calculator returns the resulting average temperature of the mixed stream, accounting for the mass (or volume) of each.
Formula
The mixed air temperature is the flow-weighted average of the individual airstream temperatures:
Tm = (Q1 × T1 + Q2 × T2) / (Q1 + Q2)
- Tm – mixed air temperature (°C)
- T1, T2 – dry-bulb temperatures of the two airstreams (°C)
- Q1, Q2 – volumetric flow rates of the two airstreams (m³/h, L/s, or ft³/min)
The formula assumes constant air density and no heat loss to the duct walls, which is reasonable for typical HVAC mixing plenums. For more than two streams, extend the pattern: sum of (each flow × its temperature) divided by the sum of all flows.
Worked Example
Using the calculator defaults: return air at 22 °C with a flow of 3000 m³/h mixes with outdoor air at 35 °C flowing at 1000 m³/h.
Step 1 – Multiply each temperature by its flow:
3000 × 22 = 66,000 °C·m³/h
1000 × 35 = 35,000 °C·m³/h
Step 2 – Add those products: 66,000 + 35,000 = 101,000 °C·m³/h
Step 3 – Divide by the total flow: 3000 + 1000 = 4000 m³/h
101,000 / 4000 = 25.25 °C
The mixed air temperature is 25.3 °C (rounded to one decimal).
Assumptions
- Air density is constant across both streams (same pressure and humidity level).
- No heat is added or lost in the mixing plenum.
- The two airstreams are fully mixed before the temperature is measured.
- Volumetric flow rates are measured at the same conditions.
Why Mixed Air Temperature Matters
HVAC designers and technicians use mixed air temperature to predict what temperature air will be after outdoor ventilation air combines with return air before it enters the cooling coil, heating coil, or heat pump. This value determines the coil load: a higher mixed temperature in summer means more cooling energy is needed; a lower mixed temperature in winter means more heating. It also helps set the minimum outdoor air damper position to meet ventilation codes while controlling energy use.
For example, a building requiring 15% outdoor air at 35 °C mixed with return air at 24 °C will have a mixed temperature around 25.7 °C. Knowing this, the cooling coil can be selected to handle the resulting load. In winter, cold outdoor air mixed with warm return air prevents the coil from freezing and reduces the need for preheating.
How to Use the Calculator
Enter the dry-bulb temperatures (in °C) and the volumetric flow rates (in m³/h or any consistent unit) for the two airstreams. The calculator returns the mixed temperature in °C. The flow rates must be in the same unit for both streams – if one is in L/s and the other in m³/h, convert first (1 m³/h = 0.2778 L/s).
For more than two streams, you can combine them in stages: first mix stream 1 and 2, then mix the result with stream 3, using the total flow each time. The result is identical to a single weighted average.
Common Mistakes and Limits
- Unit mismatch: Mixing m³/h with L/s without converting gives a wrong weighted average. Always use the same unit for both flows.
- Using Celsius instead of Kelvin: The formula works with Celsius because the temperature difference is linear, but if you use the ideal gas law to convert flows to mass, you must convert to Kelvin (add 273.15).
- Ignoring humidity: The formula gives the dry-bulb temperature of the mixture. The actual enthalpy (heat content) also depends on moisture content. For precise coil loads, use a psychrometric chart or an enthalpy-weighted average.
- Assuming perfect mixing: In real ducts, temperature stratification can occur if the mixing length is too short. The calculated value is the theoretical average; a sensor may read a different value if placed too close to the inlet.
Comparison with Enthalpy Weighting
For sensible heat calculations, temperature weighting is sufficient. However, when the outdoor air is very humid or very dry, the total cooling load depends on enthalpy, not just temperature. Enthalpy-weighted mixed air temperature uses the specific enthalpy (kJ/kg) of each stream, which accounts for latent heat. In tropical climates, the enthalpy method can give a mixed temperature several degrees higher than the simple dry-bulb average. For most routine HVAC sizing, the dry-bulb mixed temperature is adequate, but for dehumidification design, use enthalpy.
Frequently Asked Questions
What is mixed air temperature in simple terms?
It is the average temperature of air after two or more airstreams blend together, weighted by their flow rates. If you mix 1 part at 20 °C with 3 parts at 30 °C, the result is closer to 30 °C because the larger flow has more influence.
Does mixed air temperature equal the average of the two temperatures?
Only if both flow rates are equal. Otherwise, it is a weighted average: the stream with the larger flow contributes more to the final temperature. For example, 1000 m³/h at 10 °C mixed with 3000 m³/h at 30 °C gives (1000×10 + 3000×30)/4000 = 25 °C, not 20 °C.
Why do HVAC systems mix return air with outdoor air?
To provide fresh air for occupants (ventilation) while recovering energy from the conditioned return air. Mixing reduces the load on the heating or cooling coil compared to conditioning 100% outdoor air, and it also helps maintain indoor air quality by diluting contaminants.
How do you measure mixed air temperature?
Place a temperature sensor (thermistor or thermocouple) in the mixing plenum downstream of where the two airstreams join, ideally after a mixing baffle or at least 5–10 duct diameters downstream. The sensor should be shielded from radiant heat and positioned to avoid stratification.
What is the difference between dry-bulb and wet-bulb mixed temperature?
Dry-bulb is the ordinary air temperature. Wet-bulb reflects evaporative cooling and is used to calculate humidity. For mixed air, you can compute both, but the dry-bulb value is what most people mean by “mixed air temperature.” The wet-bulb mixed temperature is needed for cooling tower and evaporative coil calculations.
Can I use this calculator for mixing gases other than air?
Yes, the same weighted-average formula applies to any gas mixture as long as the flow rates are on a mass or molar basis. For volumetric flows, it is accurate only when pressures and temperatures are similar; otherwise, convert to mass flow using the ideal gas law.
Related
Formula used
in t1 | Temperature of airstream 1 | °C | 22 | -273.15 in t2 | Temperature of airstream 2 | °C | 35 | -273.15 in q1 | Flow rate of airstream 1 | m³/h | 3000 | 0 in q2 | Flow rate of airstream 2 | m³/h | 1000 | 0 out tm | Mixed air temperature | °C | (q1 * t1 + q2 * t2) / (q1 + q2) | 1
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.