Outside Air Enthalpy: Definition & How to Calculate

Calculator No. 01-7977 · Updated · Formula and assumptions shown below

Specific enthalpy 80.8 kJ/kg_da
Humidity ratio
0.0178 kg_w/kg_da
Result, rounded to 4 decimal places
Dry-bulb temperature
35 °C
Set in the form below
Relative humidity
50 %
Set in the form below
You enter
Dry-bulb temperature (°C), Relative humidity (%)
You get
Specific enthalpy (kJ/kg_da), Humidity ratio (kg_w/kg_da)
Rounding
1 dp · 4 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

Outside air enthalpy is a measure of the total heat content (sensible plus latent heat) of the outdoor air at a given temperature and humidity. It is expressed in energy per unit mass of dry air (typically kJ/kg or Btu/lb) and is used in HVAC design to calculate ventilation loads, cooling coil loads, and economizer savings. You input dry-bulb temperature and humidity ratio (or relative humidity), and the calculator returns the specific enthalpy of the air.

Formula

The specific enthalpy of moist air (per kilogram of dry air) is given by:

h = 1.006·T + W·(2501 + 1.86·T)

where:

  • h = specific enthalpy (kJ/kg dry air)
  • T = dry-bulb temperature (°C)
  • W = humidity ratio (kg water vapor per kg dry air)
  • 1.006 = specific heat of dry air (kJ/(kg·°C))
  • 2501 = latent heat of vaporization of water at 0°C (kJ/kg)
  • 1.86 = specific heat of water vapor (kJ/(kg·°C))

The humidity ratio is computed from relative humidity and saturation pressure using:

W = 0.622·(φ·Pws) / (P – φ·Pws)

where φ is relative humidity (fraction), Pws is the saturation vapor pressure (kPa) approximated by the Magnus formula, and P is the total atmospheric pressure (101.325 kPa).

Worked Example

Using the default values: T = 35°C, RH = 50%.

  1. Calculate saturation pressure: Pws = 0.6108·exp(17.27·35 / (35 + 237.3)) = 0.6108·exp(604.45/272.3) = 0.6108·exp(2.219) = 0.6108·9.198 = 5.618 kPa.
  2. Actual vapor pressure = 0.50 × 5.618 = 2.809 kPa.
  3. Humidity ratio W = 0.622 × 2.809 / (101.325 – 2.809) = 1.747 / 98.516 = 0.01773 kg/kg.
  4. Enthalpy h = 1.006×35 + 0.01773×(2501 + 1.86×35) = 35.21 + 0.01773×(2566.1) = 35.21 + 45.50 = 80.71 kJ/kg.

The calculator rounds to 80.7 kJ/kg, matching the result.

Assumptions

  • Atmospheric pressure is 101.325 kPa (sea level).
  • Air behaves as an ideal gas; the Magnus formula approximates saturation vapor pressure.
  • The reference state for enthalpy is 0°C dry air and 0°C liquid water.
  • Relative humidity is expressed as a percentage (0–100).

Why Outside Air Enthalpy Matters

HVAC engineers use outside air enthalpy to calculate the energy required to bring ventilation air to indoor conditions. In cooling, the enthalpy difference between outdoor and supply air determines the total heat removal, which includes both sensible cooling (temperature drop) and latent cooling (moisture removal). In heating, enthalpy includes the energy to warm air and vaporize any liquid water if humidification is needed.

For example, on a hot humid day (35°C, 80% RH), the enthalpy is roughly 115 kJ/kg, while on a hot dry day (35°C, 20% RH) it is about 62 kJ/kg. The same dry-bulb temperature yields very different loads because of moisture content.

How to Use the Calculator

Enter the dry-bulb temperature (in °C) and relative humidity (in %). The calculator returns the specific enthalpy and the humidity ratio. Use the enthalpy value in energy balance equations, such as:

  • Ventilation load: Q = ṁ·(houtside – hindoor)
  • Mixed air temperature and enthalpy for economizer cycles
  • Cooling coil sizing: total heat = mass flow × enthalpy difference

For air at standard sea-level pressure, the result is accurate to within about 2% for typical HVAC conditions. At high altitudes, use a lower atmospheric pressure input if your calculator allows it.

Common Mistakes and Misconceptions

  • Confusing enthalpy with temperature: Enthalpy includes latent heat; two air masses at the same temperature can have very different enthalpies.
  • Using dry-bulb temperature alone: Always include humidity; otherwise you underestimate cooling loads on humid days.
  • Mixing units: Ensure temperature is in °C and pressure in kPa. If using Btu/lb, the formula changes (use 0.24 Btu/lb·°F and 1061 Btu/lb).
  • Forgetting the reference state: Enthalpy values are relative; always state the reference (0°C or 0°F).

Limitations of the Formula

The Magnus formula for saturation pressure is accurate to about 0.3% between 0°C and 50°C, but less accurate at extreme low temperatures. At pressures far from 101.325 kPa, the humidity ratio calculation should use the actual barometric pressure. For very high humidity (near 100%), condensation may occur, and the ideal-gas assumption breaks down slightly. For most HVAC applications, the error is negligible.

Frequently Asked Questions

What is the difference between enthalpy and temperature?

Temperature measures the average kinetic energy of molecules, while enthalpy measures the total heat content, including latent heat from moisture. Two air samples at the same temperature can have different enthalpies if one is more humid.

Why do I need outside air enthalpy instead of just temperature?

Because ventilation loads depend on both sensible and latent heat. On a humid day, removing moisture requires extra cooling energy that temperature alone does not reveal. Enthalpy gives the true energy content for load calculations.

How do I convert enthalpy from kJ/kg to Btu/lb?

Multiply by 0.4299 (since 1 kJ/kg = 0.4299 Btu/lb). For example, 80 kJ/kg × 0.4299 = 34.4 Btu/lb.

Does outside air enthalpy change with altitude?

Yes. At higher altitudes, atmospheric pressure is lower, which reduces the humidity ratio for the same relative humidity, thus lowering enthalpy. The calculator assumes sea level; for high-altitude locations, adjust the pressure in the formula.

What is the typical enthalpy of outside air in summer?

It varies widely. For example, 30°C and 60% RH gives about 75 kJ/kg, while 35°C and 80% RH gives about 115 kJ/kg. In arid climates, enthalpy can be as low as 50 kJ/kg at high temperatures.

Related

Formula used
in t | Dry-bulb temperature | °C | 35 | -40 | 60
in rh | Relative humidity | % | 50 | 0 | 100
out h | Specific enthalpy | kJ/kg_da | 1.006 * t + (2501 + 1.86 * t) * (0.622 * (rh/100 * 0.6108 * exp(17.27 * t / (t + 237.3))) / (101.325 - (rh/100 * 0.6108 * exp(17.27 * t / (t + 237.3))))) | 1
out hr | Humidity ratio | kg_w/kg_da | 0.622 * (rh/100 * 0.6108 * exp(17.27 * t / (t + 237.3))) / (101.325 - (rh/100 * 0.6108 * exp(17.27 * t / (t + 237.3)))) | 4

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.