Dry Air Enthalpy Table: How to Read & Use It

Calculator No. 01-8129 · Updated · Formula and assumptions shown below

The calculator on this page is switched off while it is checked. The formula is below, and the worked example shows how to do the sum by hand.

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

A dry air enthalpy table lists the specific enthalpy (heat content) of dry air at various temperatures, usually in kJ/kg, assuming a constant pressure of 1 atm. You use it to quickly find how much thermal energy is stored in a kilogram of dry air without calculating it from the specific heat each time. The table is a practical reference for HVAC design, psychrometric analysis, and any process where air is heated or cooled.

Formula

The specific enthalpy of dry air is calculated with the simple linear relation:

h = cp × T

where:

  • h = specific enthalpy (kJ/kg)
  • cp = specific heat of dry air at constant pressure ≈ 1.006 kJ/(kg·°C) (at 25 °C and 1 atm)
  • T = dry-bulb temperature (°C)

This formula assumes the reference state is 0 °C, meaning enthalpy is zero at 0 °C. If you want enthalpy relative to another reference (e.g., 0 K or 0 °F), you must add or subtract the offset. For most HVAC work, the 0 °C reference is standard because it aligns with the zero point of the Celsius scale.

Worked Example

Using the default values from the calculator: T = 25 °C.

  1. Write the formula: h = 1.006 × T
  2. Plug in the temperature: h = 1.006 × 25
  3. Multiply: h = 25.15 kJ/kg

The calculator shows h = 25.15 kJ/kg (rounded to two decimals). This matches the result exactly.

Assumptions

  • Dry air (0% relative humidity, no water vapor).
  • Constant pressure of 1 atm (101.325 kPa).
  • Specific heat cp is constant at 1.006 kJ/(kg·°C) over the temperature range shown (0–200 °C). In reality, cp varies slightly with temperature (e.g., 1.005 at 0 °C, 1.009 at 100 °C, 1.014 at 200 °C), but the difference is under 1% for most applications.
  • Reference state: 0 °C, 1 atm, enthalpy = 0 kJ/kg.

How to Read a Dry Air Enthalpy Table

A typical table has columns for temperature (°C) and enthalpy (kJ/kg). To use it:

  • Find the dry-bulb temperature in the left column.
  • Read across to the enthalpy column.
  • For temperatures between listed values, interpolate linearly (the relationship is nearly linear, so linear interpolation is accurate).

For example, if a table lists 20 °C → 20.12 kJ/kg and 30 °C → 30.18 kJ/kg, then at 25 °C you would interpolate to about 25.15 kJ/kg, which matches the formula.

Enthalpy is a state function, so the table gives the energy content relative to the reference. To find the energy change when air goes from 10 °C to 30 °C, subtract the enthalpy at 10 °C from that at 30 °C. The difference is the heat added per kilogram of dry air.

When to Use Dry Air Enthalpy vs. Moist Air Enthalpy

Dry air enthalpy tables are only valid for air with zero water vapor. In real atmospheric air, water vapor adds significant enthalpy because the latent heat of vaporization is large. For example, at 25 °C and 50% relative humidity, the enthalpy of moist air is about 50.3 kJ/kg of dry air, roughly double the dry air value. This is why psychrometric charts use moist air enthalpy, not dry air enthalpy.

Use a dry air table when:

  • You are working with compressed air or instrument air that is assumed dry.
  • You are calculating sensible heat only (no phase change).
  • You need a quick estimate for a process where humidity is negligible.

Use moist air enthalpy (from a psychrometric chart or formula) when:

  • You are designing HVAC systems for occupied spaces.
  • You are analyzing cooling coils, humidifiers, or drying processes.
  • Relative humidity is above 10% or temperature is high.

Common Mistakes and Misconceptions

Mistake 1: Using dry air enthalpy for moist air. This is the most common error. The difference can be huge, especially at high humidity. Always check whether your air contains water vapor.

Mistake 2: Forgetting the reference state. Some tables use 0 °C, others use 0 K or 0 °F. If you mix tables, your enthalpy differences will be wrong. Always confirm the reference.

Mistake 3: Using cp = 1.005 vs 1.006. The value 1.005 is often quoted for 0 °C, while 1.006 is for 25 °C. The difference is negligible for most calculations, but be consistent.

Mistake 4: Interpolating non-linearly. Over a wide temperature range (e.g., -100 °C to 500 °C), cp changes more, so linear interpolation becomes less accurate. For most HVAC ranges (-20 °C to 60 °C), it’s fine.

Limitations of the Simple Formula

The linear formula h = 1.006 × T is an approximation. At very low temperatures (below -50 °C), cp drops to about 1.003 kJ/(kg·°C). At high temperatures (above 300 °C), it rises to about 1.05. For precise work, use the polynomial fits from NIST or the ASHRAE handbook, which give cp as a function of temperature.

Also, the formula ignores pressure effects. Enthalpy of an ideal gas is independent of pressure, but real air deviates slightly at high pressures (e.g., above 10 atm). For typical atmospheric applications, pressure effects are negligible.

Frequently Asked Questions

Q: What is the difference between enthalpy and temperature?
Temperature measures the average kinetic energy of molecules, while enthalpy measures the total heat content of a system, including internal energy plus the work required to displace the surroundings (pressure-volume work). For a constant-pressure process, the change in enthalpy equals the heat added.

Q: Why is the enthalpy of dry air at 0 °C zero?
It’s an arbitrary reference. By convention, we set h = 0 at 0 °C and 1 atm for dry air. This makes calculations convenient because temperature differences in °C directly give enthalpy differences in kJ/kg when multiplied by cp.

Q: Can I use this table for humid air if I just add the water vapor enthalpy?
Yes, but you must also account for the latent heat. The standard formula for moist air enthalpy is: h = 1.006·T + W·(2501 + 1.86·T), where W is the humidity ratio (kg water per kg dry air). The 2501 kJ/kg is the latent heat of vaporization at 0 °C. This is exactly what psychrometric charts show.

Q: How do I convert enthalpy from kJ/kg to Btu/lb?
Multiply by 0.4299 (since 1 kJ/kg = 0.4299 Btu/lb). For example, 25.15 kJ/kg × 0.4299 = 10.81 Btu/lb.

Q: Does altitude affect the enthalpy table?
For dry air as an ideal gas, enthalpy is independent of pressure, so altitude doesn’t change the specific enthalpy values. However, the density changes, so the enthalpy per cubic meter does change. Always work on a per-mass basis.

Q: What is the specific heat of dry air in other units?
Common values: 1.006 kJ/(kg·°C), 0.240 Btu/(lb·°F), 0.24 kcal/(kg·°C), and 1006 J/(kg·K). The numerical value in kJ/(kg·°C) is the same as in kJ/(kg·K) because a 1 °C change equals a 1 K change.

Related

Formula used
in T | Dry-bulb temperature | °C | 25 | -273.15 | 200
out h | Specific enthalpy (dry air) | kJ/kg | 1.006 * T | 2
out hk | Enthalpy per kg (rounded) | kJ/kg | round(h, 2) | 2

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.

More in this section

The whole Moles & Molar Mass section →