The enthalpy of air at any temperature is the total heat content per unit mass of dry air plus the heat carried by any water vapor present, typically expressed in kJ/kg of dry air. For dry air at 1 atm, enthalpy increases from 0 kJ/kg at 0°C to about 301 kJ/kg at 100°C, and for moist air you add the latent heat of the water vapor.
Formula
The standard psychrometric equation for moist air enthalpy is:
h = 1.006·t + W·(2501 + 1.86·t)
- h = specific enthalpy of moist air (kJ/kg of dry air)
- t = dry-bulb temperature (°C)
- W = humidity ratio (kg water vapor per kg dry air)
- 1.006 = specific heat of dry air (kJ/(kg·°C))
- 2501 = latent heat of vaporization of water at 0°C (kJ/kg)
- 1.86 = specific heat of water vapor (kJ/(kg·°C))
For dry air, W = 0, so the formula reduces to h = 1.006·t. This is the sensible heat only. For moist air, the term W·2501 accounts for the latent heat, and W·1.86·t accounts for the sensible heat of the water vapor itself.
Worked Example
Using the calculator defaults: t = 25°C, W = 0.010 kg/kg.
- Sensible heat of dry air: 1.006 × 25 = 25.15 kJ/kg
- Latent heat of vapor: 0.010 × 2501 = 25.01 kJ/kg
- Sensible heat of vapor: 0.010 × 1.86 × 25 = 0.465 kJ/kg
- Total enthalpy: 25.15 + 25.01 + 0.465 = 50.63 kJ/kg dry air
The calculator shows 50.63 kJ/kg for the moist air and 25.15 kJ/kg for dry air alone, matching the step-by-step result.
Assumptions
- Air is an ideal gas mixture.
- Water vapor behaves as an ideal gas.
- Reference state: 0°C, dry air enthalpy = 0 kJ/kg.
- Pressure is near 1 atm (101.325 kPa); the formula is pressure-independent.
- Specific heats are constant over the temperature range.
Why Enthalpy Matters in HVAC and Drying
Enthalpy is the key property for energy calculations in air conditioning, ventilation, and drying processes. When you cool air, you remove enthalpy; when you heat it, you add enthalpy. In a cooling coil, the total heat removed equals the enthalpy difference between entering and leaving air, multiplied by the mass flow rate of dry air. Similarly, in a drying oven, the enthalpy of the heated air determines how much moisture it can pick up from the product. Engineers use psychrometric charts, which plot enthalpy along with temperature, humidity, and other properties, to design systems that heat, cool, humidify, or dehumidify air.
How Temperature Affects Enthalpy
For dry air, enthalpy rises linearly with temperature because specific heat is nearly constant. For example, at 0°C, dry air enthalpy is 0 kJ/kg; at 20°C, it is 20.12 kJ/kg; at 40°C, 40.24 kJ/kg; at 60°C, 60.36 kJ/kg; at 80°C, 80.48 kJ/kg; and at 100°C, 100.6 kJ/kg. For moist air, the enthalpy is always higher than dry air at the same temperature because of the latent heat. The difference becomes larger as humidity increases. At 25°C, dry air has 25.15 kJ/kg, but air with a humidity ratio of 0.020 (typical tropical air) has 76.1 kJ/kg. At higher temperatures, the sensible heat of water vapor adds a small extra amount, but the dominant term is the latent heat.
Common Mistakes and Misconceptions
- Using °C in the latent heat term incorrectly: The latent heat 2501 kJ/kg is at 0°C; the correction 1.86·t accounts for the vapor’s sensible heat. Some simplified formulas use 2500 kJ/kg, which is fine for rough work.
- Confusing enthalpy with internal energy: Enthalpy includes the work done to push air into a system (PV work). For air at atmospheric pressure, the difference is small but not negligible in precise work.
- Forgetting the reference temperature: Enthalpy is always relative to a reference state. Here we use 0°C, but some charts use 0°F or 15°C. Always check the reference.
- Using total air mass instead of dry air mass: The enthalpy is per kg of dry air, not per kg of moist air. If you measure the mass of moist air, you must convert using the humidity ratio.
How to Use the Calculator
Enter the dry-bulb temperature in °C (between -273.15 and 200). This is the temperature of the air as measured by a standard thermometer. Enter the humidity ratio, which is the mass of water vapor per mass of dry air. You can obtain this from a psychrometric chart, a humidity sensor, or by measuring relative humidity and using the saturation pressure. The calculator returns the enthalpy of moist air and the enthalpy of dry air alone. Use the moist air value for any system where moisture is present, such as cooling coils, cooling towers, and compressed air systems. Use the dry air value for pure dry air applications like high-temperature ovens where moisture is negligible.
Limits of the Formula
This formula assumes ideal gas behavior, which is accurate for air at typical atmospheric conditions (up to about 200°C and a few atmospheres). At very high pressures or very low temperatures near condensation, deviations occur. The specific heat of dry air is not perfectly constant; it varies slightly with temperature (e.g., 1.005 at 0°C, 1.009 at 100°C), but the difference is less than 0.5% over the range shown. The latent heat of vaporization also changes with temperature (2501 at 0°C, 2257 at 100°C), but the formula uses a linear correction that is accurate to within 1% up to 100°C. For combustion or high-temperature processes above 200°C, use a more detailed property database.
Frequently Asked Questions
What is the enthalpy of air at 20°C and 50% relative humidity?
At 20°C, the saturation pressure of water is about 2.339 kPa. At 50% RH, the partial pressure is 1.169 kPa. The humidity ratio is 0.622 × (1.169 / (101.325 – 1.169)) = 0.00724 kg/kg. Using the formula: h = 1.006×20 + 0.00724×(2501 + 1.86×20) = 20.12 + 0.00724×2538.2 = 20.12 + 18.38 = 38.50 kJ/kg dry air.
Why does humid air have higher enthalpy than dry air at the same temperature?
Because water vapor carries latent heat that was added during evaporation. When water evaporates, it absorbs 2501 kJ/kg of energy at 0°C. That energy remains in the air as part of the vapor’s enthalpy. So even though the temperature is the same, the total heat content is higher.
Can I use this formula for compressed air?
For pressures up to about 10 atm, the ideal gas assumption holds well, and the formula is still accurate to within a few percent. At higher pressures, intermolecular forces become significant, and you should use real-gas property tables or equations of state like the Peng-Robinson model.
What is the difference between enthalpy and temperature?
Temperature measures the average kinetic energy of molecules, while enthalpy measures the total heat content, including latent heat. Two air samples at the same temperature can have very different enthalpies if one is humid and the other is dry. That’s why enthalpy is the correct property for energy balance calculations, not temperature alone.
How do I convert enthalpy from kJ/kg to BTU/lb?
Multiply by 0.4299 (since 1 kJ/kg = 0.4299 BTU/lb). For example, 50 kJ/kg is about 21.5 BTU/lb. This is useful when working with US engineering data.
Does altitude affect air enthalpy?
Altitude affects air density and pressure, but the enthalpy per kg of dry air at a given temperature and humidity ratio is nearly independent of pressure. The humidity ratio, however, depends on pressure because it is a ratio of partial pressures. At high altitude, the same relative humidity corresponds to a lower humidity ratio, so the enthalpy is lower.
Related
Formula used
in t | Dry-bulb temperature | °C | 25 | -273.15 | 200 in w | Humidity ratio (kg water/kg dry air) | - | 0.010 | 0 | 1 out h | Enthalpy of moist air | kJ/kg dry air | 1.006 * t + w * (2501 + 1.86 * t) | 2 out hd | Enthalpy of dry air only | kJ/kg dry air | 1.006 * t | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- Normality to g/L Converter & Formula29.220 g/L
- Normality to meq/mL Conversion Calculator1.0000 meq/mL
- Normality Test Q-Q Plot: How to Read It
- Normality Test Results: How to Analyze Them
- Normality Slay the Spire?
- Normality Test for Paired t Test: How to Check