Enthalpy of Humid Air: Formula & Calculator

Calculator No. 01-7892 · Updated · Formula and assumptions shown below

The calculator on this page is switched off while it is checked. The formula is below, and the worked example shows how to do the sum by hand.

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

This calculator determines the specific enthalpy of humid air (moist air) in kJ/kg of dry air. You input the dry-bulb temperature, relative humidity, and atmospheric pressure, and it returns the enthalpy per kilogram of dry air, a key value for HVAC design, drying processes, and cooling tower analysis. The calculation uses the ideal gas mixture model for air and water vapor, a standard approach in psychrometrics.

Formula

The specific enthalpy of moist air is calculated per kilogram of dry air, not per kilogram of moist air. The formula is:

h = 1.006·T + x·(2501 + 1.86·T)

  • h = specific enthalpy (kJ/kg dry air)
  • T = dry-bulb temperature (°C)
  • x = humidity ratio (kg water vapor per kg dry air)

The humidity ratio is found from the relative humidity and saturation pressure:

x = 0.62198 · (φ·Psat / (P − φ·Psat))

  • φ = relative humidity (as a fraction, e.g., 0.5 for 50%)
  • Psat = saturation vapor pressure of water (kPa)
  • P = total atmospheric pressure (kPa)

The saturation vapor pressure is estimated with the Magnus formula (valid from −40 °C to +60 °C):

Psat = 0.61094 · exp(17.625·T / (T + 243.04))

The constants 1.006 kJ/(kg·°C) is the specific heat of dry air, 1.86 kJ/(kg·°C) is the specific heat of water vapor, and 2501 kJ/kg is the latent heat of vaporization of water at 0 °C.

Worked Example

Using the default values: T = 25 °C, RH = 50%, P = 101.325 kPa.

  1. Calculate saturation pressure: Psat = 0.61094 × exp(17.625 × 25 / (25 + 243.04)) = 0.61094 × exp(440.625 / 268.04) = 0.61094 × exp(1.6439) = 0.61094 × 5.174 = 3.161 kPa.
  2. Calculate humidity ratio: x = 0.62198 × (0.5 × 3.161) / (101.325 − 0.5 × 3.161) = 0.62198 × 1.5805 / (101.325 − 1.5805) = 0.62198 × 1.5805 / 99.7445 = 0.62198 × 0.015846 = 0.009856 kg/kg.
  3. Calculate enthalpy: h = 1.006 × 25 + 0.009856 × (2501 + 1.86 × 25) = 25.15 + 0.009856 × (2501 + 46.5) = 25.15 + 0.009856 × 2547.5 = 25.15 + 25.11 = 50.26 kJ/kg dry air.

The calculator returns h = 50.26 kJ/kg dry air (rounded to 2 decimals).

Assumptions

  • Ideal gas behavior for dry air and water vapor.
  • Standard atmospheric pressure at sea level (101.325 kPa) as default, but adjustable.
  • Magnus formula for saturation pressure is accurate within 0.1% over −40 °C to +60 °C.
  • Enthalpy is referenced to 0 °C for dry air and liquid water at 0 °C.
  • Relative humidity is with respect to water (not ice) even below 0 °C.

Why Enthalpy of Humid Air Matters

In HVAC engineering, the enthalpy of moist air is the key property for calculating heating and cooling loads. When air is heated, cooled, humidified, or dehumidified, the change in enthalpy tells you the energy required or removed. For example, a cooling coil that cools and dehumidifies air must remove both sensible heat (temperature drop) and latent heat (condensation of water vapor). The enthalpy difference between entering and leaving air, multiplied by the mass flow rate of dry air, gives the coil’s total cooling capacity.

In drying processes (food, lumber, textiles), the enthalpy of the air indicates its capacity to absorb moisture. In cooling towers, the enthalpy of ambient air determines the theoretical minimum water temperature achievable.

How to Read the Result

The result is per kilogram of dry air, not per kilogram of moist air. This is a psychrometric convention because dry air mass remains constant during humidification or dehumidification, making energy balances simpler. For example, if you have 2 kg/s of dry air flowing through a heater, and the enthalpy increases from 40 to 60 kJ/kg, the heat added is 2 × (60 − 40) = 40 kW.

A higher enthalpy means the air carries more energy. At the same temperature, air with higher relative humidity has higher enthalpy because it contains more water vapor, which carries latent heat. At 25 °C, saturated air (100% RH) has an enthalpy of about 75.5 kJ/kg, while dry air (0% RH) has only 25.15 kJ/kg.

Common Mistakes and Misconceptions

  • Using °F or °C inconsistently: The formula requires Celsius. If you have Fahrenheit, convert first: T(°C) = (T(°F) − 32) × 5/9.
  • Confusing enthalpy with temperature: Enthalpy includes latent heat, so two air samples at the same temperature can have very different enthalpies.
  • Forgetting pressure correction: At high altitudes (lower pressure), the humidity ratio for a given RH is higher because there is less dry air. The calculator includes this effect.
  • Using the wrong reference: Some charts use 0 °C, others use 0 °F. Our calculator uses the common SI reference of 0 °C.

Limitations of the Formula

The ideal gas model is accurate for typical atmospheric conditions (temperatures from −40 °C to 60 °C and pressures near 1 atm). At very high pressures (above 200 kPa) or near saturation, the ideal gas assumption deviates slightly. The Magnus formula for saturation pressure is empirical and fits well in the range given, but for temperatures above 60 °C, more complex correlations (e.g., ASHRAE formulations) are recommended. Also, the formula assumes that the air is a mixture of dry air and water vapor only; it ignores pollutants or other gases.

Frequently Asked Questions

What is the difference between specific enthalpy and enthalpy?

Enthalpy (H) is the total energy of the air stream, measured in kJ. Specific enthalpy (h) is enthalpy per unit mass of dry air, measured in kJ/kg dry air. In engineering, we use specific enthalpy because it is intensive and easier to work with in energy balances.

Why is the humidity ratio important?

The humidity ratio (x) tells you the actual mass of water vapor per unit mass of dry air. It is essential for calculating the amount of water that must be added or removed in a process, and it directly affects enthalpy.

Can I use this calculator for saturated air?

Yes, set relative humidity to 100%. The calculator will give the enthalpy of saturated air, which is the maximum moisture content at that temperature.

How does altitude affect enthalpy?

At higher altitudes, atmospheric pressure is lower. For the same temperature and relative humidity, the humidity ratio is higher (because there is less dry air), so the enthalpy is slightly higher. For example, at 25 °C and 50% RH, at 101.325 kPa the enthalpy is 50.26 kJ/kg, but at 80 kPa (about 2000 m altitude) it becomes about 56.5 kJ/kg.

What is the enthalpy of dry air at 0 °C?

By definition, the reference point is 0 kJ/kg for dry air at 0 °C. For moist air at 0 °C with any humidity, the enthalpy is positive because of the latent heat of water vapor.

Related

Formula used
in t | Dry-bulb temperature | °C | 25 | -40 | 60
in rh | Relative humidity | % | 50 | 0 | 100
in p | Atmospheric pressure | kPa | 101.325 | 50 | 120
out h | Specific enthalpy | kJ/kg dry air | 1.006 * t + x * (2501 + 1.86 * t) | 2
out x | Humidity ratio | kg water/kg dry air | 0.62198 * (rh / 100 * psat / (p - rh / 100 * psat)) | 4
out psat | Saturation vapor pressure | kPa | 0.61094 * exp((17.625 * t) / (t + 243.04)) | 2

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.