This guide shows you how to calculate the specific enthalpy of supply air, a key value in HVAC design and load calculations. You enter the dry-bulb temperature and relative humidity of the air, and you get the enthalpy in kilojoules per kilogram of dry air (kJ/kgda). This figure is essential for sizing cooling coils, estimating energy recovery, and performing psychrometric analysis.
Formula
The specific enthalpy of moist air is the sum of the enthalpy of dry air and the enthalpy of the water vapor mixed with it. The standard formula is:
h = 1.006 × T + x × (2501 + 1.86 × T)
Where:
- h = specific enthalpy of moist air (kJ/kg of dry air)
- T = dry-bulb temperature of the air (°C)
- x = humidity ratio (kg of water vapor per kg of dry air)
- 1.006 = specific heat of dry air at constant pressure (kJ/(kg·°C))
- 2501 = latent heat of vaporization of water at 0°C (kJ/kg)
- 1.86 = specific heat of water vapor at constant pressure (kJ/(kg·°C))
The humidity ratio x is calculated from the dry-bulb temperature and relative humidity using the saturation vapor pressure formula (a common approximation is the Magnus formula):
pws = 0.61121 × exp(17.67 × T / (T + 243.5))
pw = RH/100 × pws
x = 0.62198 × pw / (Patm − pw)
Where:
- pws = saturation vapor pressure (kPa)
- pw = partial pressure of water vapor (kPa)
- RH = relative humidity (%)
- Patm = atmospheric pressure (101.325 kPa at sea level)
- 0.62198 = ratio of molar masses of water (18.015) to dry air (28.97)
In the calculator above, the humidity ratio is computed first (as an output), then used in the enthalpy expression. The first output shown is the enthalpy, which is the main result you need.
Worked Example
Let’s use the default values from the calculator: dry-bulb temperature T = 24°C, relative humidity RH = 50%.
Step 1: Calculate saturation vapor pressure.
pws = 0.61121 × exp(17.67 × 24 / (24 + 243.5))
17.67 × 24 = 424.08
24 + 243.5 = 267.5
424.08 / 267.5 = 1.58535
exp(1.58535) = 4.8815
pws = 0.61121 × 4.8815 = 2.9837 kPa
Step 2: Calculate partial pressure of water vapor.
pw = 0.50 × 2.9837 = 1.4919 kPa
Step 3: Calculate humidity ratio.
x = 0.62198 × 1.4919 / (101.325 − 1.4919)
0.62198 × 1.4919 = 0.92793
101.325 − 1.4919 = 99.8331
x = 0.92793 / 99.8331 = 0.0092946 kg/kgda = 9.29 g/kgda
Step 4: Calculate enthalpy.
h = 1.006 × 24 + 0.0092946 × (2501 + 1.86 × 24)
1.006 × 24 = 24.144
1.86 × 24 = 44.64
2501 + 44.64 = 2545.64
0.0092946 × 2545.64 = 23.660
h = 24.144 + 23.660 = 47.80 kJ/kgda
The calculator rounds to two decimals, giving 47.80 kJ/kgda.
Assumptions
- The air is a mixture of ideal gases (dry air and water vapor).
- Atmospheric pressure is taken as 101.325 kPa (sea level).
- The Magnus formula is an approximation of the saturation vapor pressure; it is accurate to within about 0.1% for temperatures between −40°C and +60°C.
- The specific heats of dry air and water vapor are constant over the temperature range.
- Relative humidity is expressed as a percentage of the saturation vapor pressure at the same temperature.
When to Use This Calculation
Supply air enthalpy is used in HVAC design to determine the cooling or heating load on coils. For example, when you know the enthalpy of the air entering a cooling coil and the enthalpy of the supply air leaving it, the difference multiplied by the mass flow rate gives the coil load. It is also used in energy recovery calculations, psychrometric chart plotting, and in the analysis of air handling units. This calculation is a standard part of any HVAC engineer’s toolkit.
How to Read the Result
The result is the total heat content of one kilogram of dry air plus the water vapor it carries. The higher the temperature and humidity, the higher the enthalpy. For instance, cool dry air (e.g., 15°C, 30% RH) has an enthalpy around 30 kJ/kgda, while warm humid air (e.g., 30°C, 80% RH) can exceed 90 kJ/kgda. When you compare two air states, the difference in enthalpy tells you how much energy must be added or removed to change from one state to the other.
Common Mistakes
- Mixing up units: The formula expects temperature in °C and pressure in kPa. If you enter temperature in °F or pressure in mmHg, the result will be wrong. Convert first.
- Using relative humidity as a fraction instead of a percentage: The calculator expects RH as a number between 0 and 100. If you enter 0.5 instead of 50, the humidity ratio becomes tiny and the enthalpy is too low.
- Forgetting that enthalpy is per kg of dry air: The air you measure includes the water vapor, but the reference is the dry air mass. This is standard, but it can confuse.
- Rounding too early: If you round the humidity ratio to 0.009 before multiplying, you get 47.79 instead of 47.80. Keep extra digits during intermediate steps.
- Ignoring atmospheric pressure: The formula assumes sea level. At high altitudes, the lower pressure reduces the humidity ratio for the same RH, so the enthalpy is lower. For high-altitude work, use the actual barometric pressure.
Tips
- Use a psychrometric chart to cross-check your calculated enthalpy. The chart gives approximate values that should match within a few tenths of a kJ/kg.
- For quick estimates, remember that at 20°C and 50% RH, the enthalpy is about 38.5 kJ/kgda. Use this as a sanity check.
- If you are working with a known humidity ratio (e.g., from a dew point measurement), you can skip the RH step and use the enthalpy formula directly.
- When using the calculator, set the temperature first, then adjust RH. The humidity ratio output updates automatically, so you can see how it changes.
- For cooling coil calculations, use the enthalpy difference (hin − hout) multiplied by the mass flow rate of dry air (kg/s) to get the coil load in kW.
Troubleshooting
Result seems too high or too low: Check that the temperature is in °C and RH is between 0 and 100. If you entered 24°F, the saturation pressure would be much lower, giving a low enthalpy. Convert to °C first.
Humidity ratio shows “Cannot compute”: This happens if the partial pressure of water vapor exceeds atmospheric pressure, which is physically impossible. This can occur if RH is 100% and temperature is above 100°C (boiling point), but the calculator’s max temperature is 60°C, so this should not occur. If you see it, check your inputs.
Result differs from a psychrometric chart: Charts often use a different saturation pressure formula or a slightly different specific heat value. Differences of up to 1 kJ/kg are normal. For precise work, use the same formula consistently.
Result is negative: Enthalpy is referenced to 0°C for dry air and liquid water at 0°C. At very low temperatures (below 0°C) and low humidity, the enthalpy can be slightly negative. This is correct; it does not mean an error.
Calculator gives an error message: Make sure RH is between 0 and 100, and temperature is between −40 and 60°C. If you enter a temperature outside this range, the Magnus formula becomes less accurate.
Frequently Asked Questions
Q: What is the difference between enthalpy and temperature?
A: Temperature measures the average kinetic energy of molecules, while enthalpy measures the total heat content, including latent heat from moisture. Two air samples at the same temperature can have different enthalpies if their humidity differs.
Q: Why is enthalpy expressed per kg of dry air, not per kg of moist air?
A: Because the amount of dry air in a system stays constant during heating, cooling, humidification, or dehumidification. Using dry air as the reference simplifies mass and energy balances.
Q: Can I use this calculator for air at high altitudes?
A: The calculator assumes sea level pressure (101.325 kPa). At higher altitudes, the lower pressure reduces the humidity ratio for the same RH, so the enthalpy is slightly lower. For accurate results, you would need to adjust the atmospheric pressure in the formula.
Q: What is the typical enthalpy of supply air in an air conditioning system?
A: For a comfortable indoor condition of 24°C and 50% RH, the enthalpy is about 47.8 kJ/kgda. Supply air is often cooler and drier, so its enthalpy might be 30–40 kJ/kgda.
Q: How does this relate to cooling coil load?
A: The cooling coil load is the mass flow rate of dry air multiplied by the enthalpy difference between the entering and leaving air. For example, if air enters at 60 kJ/kgda and leaves at 40 kJ/kgda, and the flow is 2 kg/s, the load is 2 × (60−40) = 40 kW.
Q: Does the enthalpy formula work for temperatures below 0°C?
A: Yes, the formula works down to about −40°C. Below that, the Magnus formula becomes less accurate, and ice formation affects the latent heat term. For very low temperatures, use a more detailed psychrometric model.
Related
Formula used
in t | Dry-bulb temperature | °C | 24 | -40 | 60 in rh | Relative humidity | % | 50 | 0 | 100 out h | Supply air enthalpy | kJ/kg_da | 1.006 * t + x * (2501 + 1.86 * t) | 2 out x | Humidity ratio | g/kg_da | (0.62198 * (rh/100 * 0.61121 * exp(17.67 * t / (t + 243.5))) / (101.325 - (rh/100 * 0.61121 * exp(17.67 * t / (t + 243.5))))) * 1000 | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- Normality to g/L Converter & Formula29.220 g/L
- Normality to meq/mL Conversion Calculator1.0000 meq/mL
- Normality Test Q-Q Plot: How to Read It
- Normality Test Results: How to Analyze Them
- Normality Slay the Spire?
- Normality Test for Paired t Test: How to Check