The R-value and thermal conductivity (k-value) describe the same physical property—how well a material resists heat flow—but in inverse, unit-dependent ways. R-value is the thickness divided by thermal conductivity, so R = thickness / k, and k = thickness / R.
Formula
The R-value of a flat insulation layer is its thickness divided by its thermal conductivity:
R = t / k
- R = thermal resistance, in h·ft²·°F/BTU (imperial R-value)
- t = thickness of the material, in inches
- k = thermal conductivity, in BTU·in/(h·ft²·°F)
In SI units the same relationship is RSI = tm / kW, where tm is in meters and kW is in W/(m·K). The calculator above converts imperial inputs to both systems.
Worked Example
Take a 3.5-inch thick fiberglass batt with a thermal conductivity of 0.25 BTU·in/(h·ft²·°F).
- R = t / k = 3.5 / 0.25 = 14 h·ft²·°F/BTU
- Convert to RSI: multiply thickness by 0.0254 m/in → 0.0889 m; multiply k by 0.144228 W·in/(BTU·ft²·°F) → 0.036057 W/(m·K); RSI = 0.0889 / 0.036057 ≈ 2.47 m²·K/W
The calculator shows R = 14 and RSI = 2.47 for the default values.
Assumptions
- Heat flow is steady-state and one-dimensional (through the thickness only).
- The material is homogeneous; the k-value given is the average for the whole thickness.
- No air films, framing, fasteners, or compression are included—this is the material’s own resistance, not the assembly’s.
- Temperature is near room conditions; k-values change with temperature and moisture.
Why the Units Look Confusing
Thermal conductivity is often written with mixed units. In the US, k is commonly given in BTU·in/(h·ft²·°F), where the “in” is a thickness in inches. That unit was chosen so that R = t/k works directly when t is in inches. In SI, k is W/(m·K) and RSI is m²·K/W. To convert k from imperial to SI: multiply by 0.144228. To convert R (imperial) to RSI: divide by 5.678. The calculator handles both.
How to Read a Product’s R-Value
Manufacturers list R-values per inch (e.g., R-3.5 per inch for fiberglass, R-6 per inch for polyiso). Multiply by the installed thickness to get the total R. For example, 6 inches of polyiso at R-6 per inch gives R-36. But note: compressing insulation increases its k-value (reduces R per inch) because more solid material conducts heat in the same thickness. Never compress a batt to fit a cavity and expect the labeled R-value.
Common Mistakes and Misconceptions
- Adding R-values of layers is valid only for series heat flow; parallel paths like wood studs need area-weighted calculations.
- R-value does not include air films on surfaces. A wall assembly’s total R includes interior and exterior air films (about R-0.68 and R-0.17).
- Moisture degrades R-value significantly; wet insulation conducts more heat.
- R-value is not the same as reflectivity. Radiant barriers have low emissivity and work differently, not by conduction resistance.
- Higher R is not always better if it causes moisture condensation inside a wall; vapor control matters.
How to Choose Insulation by R-Value
Building codes specify minimum R-values by climate zone for attics, walls, and floors. Use those as a starting point. For a given R target, you can choose a thicker layer of a low-k material or a thinner layer of a high-k material. Cost, fire safety, moisture resistance, and space constraints often matter more than the exact k-value. For example, spray foam at R-6 per inch can fit in a 2×4 wall (3.5-inch cavity) to give about R-21, while fiberglass at R-3.5 per inch would need 6 inches to reach the same R.
Comparing Materials: Typical k-Values
- Fiberglass batt: k ≈ 0.25 BTU·in/(h·ft²·°F) → R-4 per inch
- Mineral wool: k ≈ 0.30 → R-3.3 per inch
- Extruded polystyrene (XPS): k ≈ 0.20 → R-5 per inch
- Polyisocyanurate (polyiso): k ≈ 0.17 → R-6 per inch
- Closed-cell spray foam: k ≈ 0.16 → R-6.2 per inch
- Cellulose loose-fill: k ≈ 0.28 → R-3.6 per inch
These are typical values; actual products vary with density, temperature, and aging (foams lose some R over time as blowing gas escapes).
Cost and Practical Considerations
Higher R per inch usually costs more. Fiberglass is cheapest per R, but it requires more thickness. Spray foam is expensive but also seals air leaks, which can be more valuable than the extra R. When comparing quotes, look at cost per R per square foot, not just cost per inch. Also consider that air leakage bypasses insulation: a perfectly insulated wall with gaps loses more heat than a slightly lower R wall that is airtight.
Safety and Installation Notes
Wear gloves, long sleeves, and a dust mask when handling fiberglass or mineral wool; the fibers irritate skin and lungs. For spray foam, follow the manufacturer’s ventilation instructions and the SDS. Keep insulation away from recessed lighting fixtures and other heat sources unless they are rated for insulation contact. Follow your local building code and the product’s installation guide.
Frequently Asked Questions
How do I convert R-value to k-value? Divide the thickness by the R-value. If R is 14 and thickness is 3.5 inches, k = 3.5 / 14 = 0.25 BTU·in/(h·ft²·°F). In SI, k = thickness (m) / RSI (m²·K/W).
What is a good R-value for an attic? In most US climate zones, attics need R-38 to R-60 (about 12 to 20 inches of fiberglass). Check your local code for the exact requirement.
Does doubling the thickness double the R-value? Yes, for the same material under the same conditions. R is linear in thickness: 2 inches at R-4 per inch gives R-8, 4 inches gives R-16.
Why do some products list RSI instead of R? RSI is the metric unit (m²·K/W). Canada and most of the world use RSI. To convert R to RSI, divide by 5.678. The calculator shows both.
Can I mix different insulation types in the same wall? Yes, but only if you manage moisture. For example, rigid foam outside a wall can keep the sheathing warm and reduce condensation. Do not put a vapor barrier on both sides of a wall, as that traps moisture.
Is a higher R-value always better? Not always. Beyond code minimums, the energy savings diminish. Also, too much insulation in an unvented roof can cause moisture problems. Balance R with air sealing, ventilation, and moisture control.
Related
Formula used
in t | Thickness | in | 3.5 | 0 in k | Thermal conductivity | BTU·in/(h·ft²·°F) | 0.25 | 0.0001 out r | R-value | h·ft²·°F/BTU | t / k | 2 out rsi | RSI (metric R) | m²·K/W | t * 0.0254 / (k * 0.144228) | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- PCR Primer Tm Calculation: How to Compute It
- Molecules to Moles Conversion Steps1.0000 mol
- Mean Rate of Reaction: How to Calculate It0.0050 mol/s
- Propane Vapor Pressure Calculator178.7 kPa
- mRNA vs Mature mRNA: Key Differences4,750
- Mass Fraction to Mole Fraction Calculator0.5195 fraction