Mixed Air Formula: Definition & Calculation

Calculator No. 01-7734 · Updated · Formula and assumptions shown below

Mixed air temperature 26.33 °C
Fraction of airstream 1
33.3 %
Result, rounded to 1 decimal place
Temperature of airstream 1
35 °C
Set in the form below
Airflow of airstream 1
1000 m³/h
Set in the form below
You enter
Temperature of airstream 1 (°C), Airflow of airstream 1 (m³/h), Temperature of airstream 2 (°C), Airflow of airstream 2 (m³/h)
You get
Mixed air temperature (°C), Fraction of airstream 1 (%)
Rounding
2 dp · 1 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

The mixed air formula calculates the temperature of air after two or more airstreams have combined, typically outdoor air and return air in an HVAC system. You enter the dry-bulb temperature and airflow (volume) of each airstream, and the calculator returns the resulting mixed-air temperature, assuming no heat is lost or gained during mixing.

Formula

The mixed air temperature is the airflow-weighted average of the individual airstream temperatures:

Tmix = (T1 × V1 + T2 × V2) / (V1 + V2)

  • Tmix – mixed air dry-bulb temperature (°C)
  • T1, T2 – dry-bulb temperatures of the two airstreams (°C)
  • V1, V2 – volumetric airflow rates of the two airstreams (m³/h, L/s, or cfm – any consistent unit works)

The formula assumes constant air density and no heat transfer to or from the duct walls. For most HVAC design work, that approximation is accurate enough.

Worked Example

Using the calculator defaults: outdoor air at 35 °C with 1000 m³/h, return air at 22 °C with 2000 m³/h.

  1. Multiply each temperature by its airflow: 35 × 1000 = 35,000; 22 × 2000 = 44,000
  2. Add the products: 35,000 + 44,000 = 79,000
  3. Add the airflows: 1000 + 2000 = 3000
  4. Divide: 79,000 / 3000 = 26.33 °C

The mixed air temperature is 26.33 °C. The fraction of outdoor air is 1000/3000 = 33.3%.

Assumptions

  • Air density is constant across both streams (no correction for altitude or humidity).
  • No heat gain or loss through duct walls during mixing.
  • No moisture condensation or evaporation occurs in the mixing process.
  • Both airstreams are fully mixed before the temperature is measured.

When to Use the Mixed Air Formula

HVAC engineers use this formula to predict the temperature of air entering an air-handling unit (AHU) when outdoor air is mixed with return air for ventilation. It helps size cooling and heating coils, estimate energy consumption, and set minimum outdoor air damper positions. The same weighted-average logic applies to mixing any two fluids of the same heat capacity, such as water streams in a plumbing system.

How to Choose the Input Values

Use the design outdoor temperature for your location (e.g., 35 °C summer design in many hot climates) and the return air temperature you expect from the conditioned space (usually 22–26 °C). The airflow values come from your ventilation requirements: outdoor air is often set by building codes (minimum fresh air per person), while return air is the total supply airflow minus exhaust. If you have more than two streams, apply the formula sequentially – mix two streams first, then mix the result with the third.

Common Mistakes and Misconceptions

  • Using Fahrenheit and Celsius inconsistently – the formula works in either scale, but you must use the same scale for all temperatures. The result will be in that same scale.
  • Forgetting to convert airflow units – as long as both airflows are in the same unit (cfm, L/s, m³/h), the ratio is correct. Mixing cfm with m³/h will give a wrong answer.
  • Assuming the mixed temperature is the arithmetic average – that only works when both airflows are equal. With unequal flows, the larger flow dominates the result.
  • Neglecting humidity – the formula gives dry-bulb temperature only. For cooling coil load, you also need the mixed air enthalpy, which requires humidity ratios. The dry-bulb formula is a first approximation.

Limits of the Formula

The mixed air formula ignores the heat capacity difference between moist and dry air. At high humidity, moist air has a slightly higher specific heat, so the true mixed temperature can differ by a fraction of a degree. For extreme conditions (very high altitude or very humid air), use a psychrometric chart or an enthalpy-weighted calculation instead. Also, the formula assumes perfect mixing; in real ducts, stratification can occur if the airstreams have large temperature differences, so the sensor should be placed downstream of a mixing baffle.

Frequently Asked Questions

What is the mixed air formula for three airstreams?

Apply the two-stream formula twice: first mix streams 1 and 2 to get an intermediate temperature, then mix that result with stream 3. Mathematically, it is the sum of (Ti × Vi) for all streams divided by the sum of all Vi. The order does not matter because addition is commutative.

Does the mixed air formula work with Fahrenheit?

Yes, the formula is linear, so you can use Fahrenheit directly. For example, 100 °F outdoor and 72 °F return with equal flows gives (100+72)/2 = 86 °F. Do not convert to Celsius first unless you want the result in Celsius – just be consistent.

Why is my measured mixed air temperature different from the calculated one?

Common reasons: the sensor is in a stratified zone (not fully mixed), duct heat gain or loss, or the airflow measurement is inaccurate. Also, if the outdoor air damper position changes during measurement, the flow ratio shifts. Allow the system to stabilize and measure at a point with good mixing.

What is the difference between mixed air and supply air?

Mixed air is the combination of outdoor and return air before it passes through the cooling or heating coil. Supply air is the air leaving the coil, after it has been conditioned to the desired temperature and humidity. The mixed air temperature is the starting point for coil load calculations.

Can I use this formula for water or other liquids?

Yes, for liquids with the same specific heat capacity (like water at similar temperatures), the weighted-average formula works. For different liquids or large temperature differences, you need to use enthalpy or specific heat corrections. For air, the constant-density approximation is standard in HVAC design.

Related

Formula used
in t1 | Temperature of airstream 1 | °C | 35 | -273.15
in v1 | Airflow of airstream 1 | m³/h | 1000 | 0
in t2 | Temperature of airstream 2 | °C | 22 | -273.15
in v2 | Airflow of airstream 2 | m³/h | 2000 | 0
out tm | Mixed air temperature | °C | (t1 * v1 + t2 * v2) / (v1 + v2) | 2
out r1 | Fraction of airstream 1 | % | v1 / (v1 + v2) * 100 | 1

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.