Calculator No. 01-10446 · Updated · Formula and assumptions shown below

Actual value 340.000 (unit of base)
Per-unit value
0.85 pu
Set in the form below
Base value (same unit as actual)
400 V, A, Ω, etc.
Set in the form below
You enter
Per-unit value (pu), Base value (same unit as actual) (V, A, Ω, etc.)
You get
Actual value ((unit of base))
Rounding
3 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

Converting from per unit means taking a value expressed in the per-unit (pu) system and turning it back into a real physical quantity, such as volts, amps, or ohms. You do this by multiplying the per-unit value by the base value for that same quantity, using the formula: Actual value = Per-unit value × Base value. The per-unit system is a way of normalizing electrical quantities by dividing them by chosen reference values, so converting back is simply reversing that normalization.

Formula

The conversion formula is straightforward:

Actual value = Per-unit value × Base value

Where:

  • Actual value – the real quantity in its normal unit (volts, amperes, ohms, watts, etc.)
  • Per-unit value – the normalized, dimensionless number (often between 0 and 1, but can be higher)
  • Base value – the reference value chosen for that quantity, in the same unit as the actual value

This works for any electrical quantity as long as the base value corresponds to the same type of quantity. For example, if the per-unit voltage is 0.85 and the base voltage is 400 V, the actual voltage is 340 V.

Worked Example

Using the calculator defaults: per-unit value = 0.85, base value = 400 V.

  1. Write the formula: Actual = pu × base
  2. Plug in the numbers: Actual = 0.85 × 400
  3. Multiply: 0.85 × 400 = 340
  4. Result: 340 V

The calculator returns 340 V, matching the manual calculation.

Assumptions

  • The base value must be in the same unit as the desired actual value (e.g., if you want volts, base voltage must be in volts).
  • The per-unit value is dimensionless.
  • This conversion assumes a consistent base system – the per-unit value was originally computed using the same base value you are using now.

Why Use Per-Unit at All?

The per-unit system is standard in power engineering because it simplifies calculations across transformers and different voltage levels. Instead of juggling large and small numbers (e.g., 138,000 V down to 120 V), you normalize everything to a base. This makes comparing equipment, calculating voltage drops, and analyzing fault currents much easier. When you need a physical value – for a meter reading, a protection relay setting, or a lab experiment – you convert back using the base.

How to Choose the Base Value

The base value is not arbitrary; it is usually chosen as the rated voltage, current, or power of the system. For example, in a three-phase system with a 400 V line-to-line voltage and 1000 kVA base power, the base current is:

Base current = Base power / (√3 × Base voltage) = 1,000,000 VA / (1.732 × 400 V) ≈ 1443 A

When converting a per-unit current back to amps, you would multiply by 1443 A, not by the actual load current. The base is a fixed reference, not the operating point.

Common Mistakes and How to Avoid Them

  • Using the wrong base – The most common error is using a base value from a different part of the system. Always check the base that was used to calculate the per-unit value.
  • Mixing single-phase and three-phase – In three-phase systems, base voltage is usually line-to-line, and base power is total three-phase power. Be consistent.
  • Forgetting unit conversions – If the base is in kA and you want amps, multiply by 1000. The calculator here expects the base in the same unit as the output, so enter volts, amps, or ohms directly.
  • Ignoring phase shifts – Per-unit values often ignore phase angle. This conversion only gives magnitude; if you need phase, you must handle complex numbers separately.

When to Convert Back

You convert from per-unit to actual in several real situations:

  • Setting protective relays – relay settings are often in per-unit of the CT/PT ratios, but you need actual trip currents.
  • Reading a power flow study – results come in per-unit; you need volts and amps to size equipment.
  • Lab work – if you model a circuit with per-unit values, you convert to real component values before building.
  • Checking motor nameplate data – a motor may be rated in per-unit on its own base; converting gives actual torque or current.

Limitations of the Simple Conversion

This multiplication works only when the per-unit value is a simple scalar. In AC systems, quantities are often phasors (magnitude and angle). Converting a phasor requires multiplying both magnitude and angle by the base – but the angle stays the same, so you only convert the magnitude. Also, if the per-unit value was calculated with different base values for different parts of the system (e.g., transformer with its own base), you must first convert to a common base before converting to actual. The simple formula assumes a single, consistent base.

Frequently Asked Questions

What does per-unit mean in simple terms?
Per-unit means expressing a value as a fraction of a chosen reference (base). For example, if the base voltage is 400 V and a bus voltage is 340 V, the per-unit voltage is 340/400 = 0.85 pu. It is a ratio, so it has no units.

Can per-unit values be greater than 1?
Yes. A per-unit value above 1 simply means the actual value exceeds the base. For instance, a motor starting current might be 6 pu, meaning six times the base current. The conversion formula still works: multiply 6 by the base current.

How do I convert per-unit impedance to ohms?
Multiply the per-unit impedance by the base impedance. The base impedance is calculated as (base voltage²) / base power. For a 400 V, 1 MVA system, base impedance = (400²) / 1,000,000 = 0.16 Ω. So a 0.05 pu impedance is 0.05 × 0.16 = 0.008 Ω.

Do I need to convert per-unit values for a single-phase or three-phase system differently?
The conversion formula is the same, but the base values differ. In three-phase, base voltage is line-to-line and base power is total three-phase power. For single-phase, use phase voltage and single-phase power. Always use the base that matches the system you are working in.

What if I don’t know the base value?
You cannot convert to actual without the base. If the base is not given, you must infer it from the system ratings (e.g., transformer kVA and voltage) or from the context of the per-unit calculation. Without a base, the per-unit number is meaningless for physical work.

Is per-unit the same as percentage?
Almost. Per-unit is a fraction (0.85), while percentage is that fraction times 100 (85%). To convert per-unit to percent, multiply by 100. To convert percent to per-unit, divide by 100. The conversion to actual value uses the per-unit number, not the percentage.

Safety and Scope

This calculator is for educational and engineering planning use only. Always follow your institution’s or company’s safety procedures when working with electrical systems. For lab work, follow your lab method, the safety data sheet (SDS) and your supervisor. Never use per-unit conversions to set protective equipment without verifying against actual system conditions and applicable standards.

Related

Formula used
in pu | Per-unit value | pu | 0.85 | 0 | 10
in base | Base value (same unit as actual) | V, A, Ω, etc. | 400 | 0
out actual | Actual value | (unit of base) | pu * base | 3

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.