molecalculator

Moles & Molar Mass

Three-Phase kW Calculator: Power from Volts and Amps

Calculator No. 01-4602 · Updated · Formula and assumptions shown below

Real power 5.89 kW
Apparent power
6.93 kVA
Result, rounded to 2 decimal places
Real power
5,889 W
= Real power × 1000
Line-to-line voltage
400 V
Set in the form below
You enter
Line-to-line voltage (V), Line current (A), Power factor
You get
Real power (kW), Apparent power (kVA), Real power (W)
Rounding
2 dp · 0 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

This three-phase kW calculator estimates real electrical power from line voltage, line current, and power factor. Enter those three values to get kilowatts; the calculation assumes a balanced three-phase system and uses the line-to-line voltage convention common for three-phase supplies.

Formula

For a balanced three-phase circuit, real power in kilowatts is:

P (kW) = √3 × VL × IL × PF ÷ 1000

  • P is real power, in kilowatts (kW).
  • VL is line-to-line voltage, in volts (V).
  • IL is line current, in amperes (A).
  • PF is the power factor, a dimensionless number from 0 to 1.
  • √3 is approximately 1.73205, the factor connecting line values in a balanced three-phase system.
  • 1000 converts watts to kilowatts; the underlying voltage-current product is in watts.

The calculator also reports apparent power, S (kVA) = √3 × VL × IL ÷ 1000, and real power in watts. Apparent power does not include the power-factor multiplier.

Worked Example

Using the calculator’s defaults—400 V line-to-line, 10 A line current, and a power factor of 0.85:

  1. Calculate the voltage-current product: 400 V × 10 A = 4000 VA per line-value product.
  2. Apply the three-phase factor: √3 × 4000 = 6928.2032 VA.
  3. Apply the power factor: 6928.2032 × 0.85 = 5888.9727 W.
  4. Convert watts to kilowatts: 5888.9727 ÷ 1000 = 5.8889727 kW, which rounds to 5.89 kW.

Apparent power is √3 × 400 × 10 ÷ 1000 = 6.9282032 kVA, or 6.93 kVA. Real power in watts is 5889 W when rounded to a whole watt.

Assumptions

  • The three phases are balanced, with equal phase voltages and currents.
  • Voltage entered is line-to-line voltage, and current is line current.
  • The power factor applies to the operating condition being estimated.
  • The calculation gives electrical real power, not necessarily useful mechanical output from a motor.

What the Result Means

Kilowatts measure real power: the rate at which electrical energy is converted into work, heat, light, or other useful output. A reading of 5.89 kW means the load is using real power at roughly that rate under the stated voltage, current, and power-factor conditions. If that load ran steadily for one hour, it would use about 5.89 kWh of energy; actual consumption changes if the load or operating conditions vary.

The kVA result is apparent power, which reflects the combined voltage and current demand on the supply. It can be greater than kW when power factor is below 1. For the example, 5.89 kW is real power and 6.93 kVA is apparent power. The difference matters when assessing generators, transformers, cables, and other equipment rated in kVA or current.

Power factor describes how effectively apparent power is converted into real power. In a simple sinusoidal load it is the cosine of the phase angle between voltage and current. With nonlinear loads, such as many electronic power supplies, distortion also affects true power factor, so it may not be enough to use only the cosine of a phase angle.

Line Values, Phase Values, and Common Mix-Ups

Three-phase systems can be connected in wye (star) or delta. The calculator’s formula uses line-to-line voltage and line current, so it works for either balanced connection when the inputs are those line values. Confusion arises when someone substitutes phase voltage or phase current without changing the formula.

  • In a balanced wye system, line-to-line voltage is √3 times phase voltage, while line current equals phase current.
  • In a balanced delta system, line voltage equals phase voltage, while line current is √3 times phase current.
  • For a common 400 V wye supply, phase voltage is about 400 ÷ √3 = 230.94 V. Enter 400 V in this calculator if the available measurement is line-to-line voltage.

A frequent misconception is that voltage multiplied by current always gives kW. In AC circuits, that product gives apparent power, and power factor is needed to estimate real power. In a balanced three-phase system, the √3 factor is also needed when using line values. Omitting either factor can produce a substantially incorrect result.

When This Calculator Is Useful—and Its Limits

This calculation is useful for a quick estimate when you know a balanced load’s line voltage, line current, and power factor. It can help compare a measured operating point with a nameplate rating or understand why kW and kVA figures differ. For an accurate operating value, use measurements taken under the actual load and conditions, not only nominal nameplate figures.

Do not use this simple formula as a substitute for a full analysis of an unbalanced system. If phase currents or voltages differ materially, calculate each phase’s real power using the appropriate phase voltage, phase current, and phase power factor, then add the phase powers. Harmonics, changing loads, voltage drops, and measurement errors can also affect the result. A meter that measures true power is preferable when those effects matter.

For motors, electrical input power is not the same as shaft output power. Motor efficiency relates them: output power is input real power multiplied by efficiency. Since efficiency varies with motor design and loading, it must be obtained from reliable equipment data or measurement rather than assumed from this calculator. For wiring, protection, and equipment selection, follow applicable electrical codes and have the installation assessed by a qualified professional.

Frequently Asked Questions

How do I calculate kW from three-phase volts and amps?
For a balanced system using line-to-line volts and line amps, multiply √3 × volts × amps × power factor, then divide by 1000.

Can I calculate three-phase kW without power factor?
You can calculate apparent power in kVA from √3 × V × A ÷ 1000. You cannot determine real kW from voltage and current alone unless the power factor is known or reasonably established.

Is three-phase kW the same as kVA?
No. kW is real power; kVA is apparent power. They are equal only when power factor is 1. Otherwise, kW equals kVA multiplied by power factor.

Should I enter phase voltage or line voltage?
Enter line-to-line voltage, which is the voltage measured between two supply lines. Do not enter phase-to-neutral voltage unless you first convert it to line-to-line voltage for a balanced wye system.

Does the formula work for an unbalanced three-phase load?
Not as a single estimate using one voltage, current, and power factor. Calculate each phase’s real power using suitable phase measurements and add the results, or use an appropriate true-power meter.

Related

Formula used
in v | Line-to-line voltage | V | 400 | 0
in a | Line current | A | 10 | 0
in pf | Power factor | - | 0.85 | 0 | 1
out kw | Real power | kW | sqrt(3) * v * a * pf / 1000 | 2
out kva | Apparent power | kVA | sqrt(3) * v * a / 1000 | 2
out w | Real power | W | kw * 1000 | 0

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.

More in this section

The whole Moles & Molar Mass section →