The mixed air formula in thermodynamics calculates the final temperature (and often humidity) when two or more air streams are combined adiabatically. You enter the mass flow rates and temperatures of each stream, and the calculator returns the mixture temperature, assuming no heat is lost to the surroundings. For a simple two-stream mix, the formula is T_mix = (m1·T1 + m2·T2) / (m1 + m2), where m is mass flow rate and T is temperature.
Formula
The basic energy balance for adiabatic mixing of two air streams is:
T_mix = (m₁·T₁ + m₂·T₂) / (m₁ + m₂)
Where:
- T_mix = final mixture temperature (°C or K)
- m₁ = mass flow rate of stream 1 (kg/s)
- T₁ = temperature of stream 1 (°C or K)
- m₂ = mass flow rate of stream 2 (kg/s)
- T₂ = temperature of stream 2 (°C or K)
This is a weighted average: the larger the mass flow, the more it pulls the final temperature toward its own temperature. The formula assumes constant specific heat (which is nearly true for air over moderate temperature ranges) and no heat transfer to the duct or surroundings. If you use °C, the result is in °C; if you use K, the result is in K. The calculator above gives both.
Worked Example
Using the default values: m₁ = 2.5 kg/s at T₁ = 20 °C, and m₂ = 1.5 kg/s at T₂ = 80 °C.
Step 1: Multiply each mass by its temperature:
2.5 × 20 = 50.0
1.5 × 80 = 120.0
Step 2: Sum the products:
50.0 + 120.0 = 170.0
Step 3: Sum the mass flows:
2.5 + 1.5 = 4.0 kg/s
Step 4: Divide:
170.0 / 4.0 = 42.5 °C
The calculator shows 42.50 °C. In Kelvin, the same calculation gives (2.5×293.15 + 1.5×353.15)/4.0 = (732.875 + 529.725)/4.0 = 1262.6/4.0 = 315.65 K, which is 42.50 °C (since 315.65 − 273.15 = 42.50).
Assumptions
- Adiabatic mixing: no heat is lost to the duct or the environment.
- Constant specific heat of air (cp ≈ 1.005 kJ/(kg·K) at room temperature).
- No phase change (no condensation or evaporation of water).
- Steady flow: mass flow rates are constant.
- Kinetic and potential energy changes are negligible.
These assumptions hold well for typical HVAC mixing boxes where the temperature difference is not extreme and the air is dry.
When to Use the Mixed Air Formula
This formula is used in heating, ventilation, and air conditioning (HVAC) design to determine the temperature of air entering a cooling or heating coil after fresh outdoor air is mixed with return air. It is also used in industrial processes where two gas streams are combined, and in simple thermodynamic cycle analysis.
For example, a building may bring in 2.5 kg/s of outdoor air at 20 °C and mix it with 1.5 kg/s of return air at 80 °C (perhaps from a heated space). The mixed air temperature of 42.5 °C tells the engineer what load the cooling coil must handle. Similarly, in a gas turbine, compressor bleed air might be mixed with cooler bypass air to control turbine inlet temperature.
How to Choose the Right Formula
If you are mixing more than two streams, extend the formula:
T_mix = (Σ mᵢ·Tᵢ) / (Σ mᵢ)
The calculator above handles two streams; for more, you can apply the formula iteratively or use a spreadsheet. If the streams have different specific heats (e.g., mixing air with another gas), replace mass flow with mass flow × specific heat (m·cp) in the numerator and denominator. If the air streams have significant humidity differences, you must also perform a moisture balance to find the mixed humidity ratio, because latent heat affects the cooling coil load.
Common Mistakes and Misconceptions
- Using volume flow instead of mass flow: Air density changes with temperature, so volume flow rates are not directly proportional to mass. Always convert to mass flow using density at the actual temperature, or use the ideal gas law.
- Mixing °C and K: The formula works in either scale, but you must use the same scale for all temperatures. Mixing them gives a wrong result.
- Ignoring humidity: The simple formula only gives the dry-bulb temperature. The actual enthalpy of moist air includes water vapor, so for accurate coil loads you need a psychrometric chart or a moist air property calculator.
- Thinking the result is the final equilibrium temperature after time: The formula gives the steady-state mixed temperature at the point of mixing, not the temperature after the air has sat in a room.
Comparison: Simple Average vs. Mass-Weighted Average
Many people initially think the mixed temperature is just the arithmetic average: (T₁ + T₂)/2. That is only correct if both mass flows are equal. In our example, the arithmetic average is (20 + 80)/2 = 50 °C, but the true mixed temperature is 42.5 °C because the cooler stream has a larger mass flow. The difference can be significant in real systems. Always use the mass-weighted average.
Costs and Practical Considerations
In HVAC design, getting the mixed air temperature right affects equipment sizing and energy costs. If you undersize a cooling coil because you used a simple average, the coil may not handle the load on hot days. Conversely, oversizing wastes money. The formula itself is free, but the cost of a mistake can be substantial. For existing systems, you can measure the actual mixed temperature with a thermometer and compare it to the calculated value to check if the mixing is truly adiabatic or if duct heat gain/loss is occurring.
Safety and Limits
This formula is for engineering estimation and study purposes. It assumes ideal conditions; real ducts have heat transfer, and air properties vary with temperature and pressure. For precise work, use a psychrometric chart or software that accounts for humidity. Always follow your system’s design specifications and applicable codes. When working with hot or cold air streams, be aware of surface temperatures and use appropriate personal protective equipment if touching ducts.
Frequently Asked Questions
Does the mixed air formula work for gases other than air?
Yes, as long as the specific heat is constant and the streams are at similar pressures. For different gases, use the mass flow times specific heat (m·cp) as the weighting factor. The formula becomes T_mix = (m₁cp₁T₁ + m₂cp₂T₂) / (m₁cp₁ + m₂cp₂).
What if the two streams have different pressures?
If pressures differ significantly, the simple formula is not accurate because enthalpy depends on pressure. In most HVAC applications, pressures are close to atmospheric, and the error is negligible. For high-pressure differences, use a full energy balance with enthalpy values.
How do I account for humidity in mixed air?
You need to perform a moisture balance: W_mix = (m₁W₁ + m₂W₂) / (m₁ + m₂), where W is the humidity ratio (kg water per kg dry air). Then use psychrometric equations to find the mixed enthalpy and relative humidity. The dry-bulb temperature from the simple formula is still correct, but the wet-bulb and dew point will differ.
Can I use this formula for mixing liquids?
Yes, the same weighted average applies to any fluid with constant specific heat, such as water. For liquids, you often use volume flow rates if density is constant, but for accuracy use mass flow. The formula is universal for adiabatic mixing of two streams of the same substance.
Why does the calculator show a Kelvin result?
Kelvin is the SI unit for thermodynamic temperature. The calculator gives both °C and K to help you avoid unit mistakes. The Kelvin result is computed by converting each input to K before averaging, which is mathematically equivalent to converting the °C result.
Related
Formula used
in m1 | Mass flow rate stream 1 | kg/s | 2.5 | 0 in t1 | Temperature stream 1 | °C | 20 | -273.15 in m2 | Mass flow rate stream 2 | kg/s | 1.5 | 0 in t2 | Temperature stream 2 | °C | 80 | -273.15 out tmix | Mixture temperature | °C | (m1 * t1 + m2 * t2) / (m1 + m2) | 2 out tmixK | Mixture temperature | K | (m1 * (t1 + 273.15) + m2 * (t2 + 273.15)) / (m1 + m2) | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.