Mixed Air Temperature Formula: How to Calculate It

Calculator No. 01-7815 · Updated · Formula and assumptions shown below

Mixed air temperature 25.25 °C
Fraction of airstream 1
0.250
Result, rounded to 3 decimal places
Temperature of airstream 1
35 °C
Set in the form below
Volume flow rate of airstream 1
0.5 m³/s
Set in the form below
You enter
Temperature of airstream 1 (°C), Volume flow rate of airstream 1 (m³/s), Temperature of airstream 2 (°C), Volume flow rate of airstream 2 (m³/s)
You get
Mixed air temperature (°C), Fraction of airstream 1
Rounding
2 dp · 3 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

The mixed air temperature formula calculates the temperature of air after two or more airstreams combine, typically outdoor air and return air in an HVAC system. You input the dry-bulb temperatures and mass flow rates (or volumes) of each airstream, and the calculator returns the resulting mixed air dry-bulb temperature. This value is essential for sizing cooling coils, estimating load, and troubleshooting comfort issues.

Formula

The mixed air temperature is the flow-weighted average of the individual airstream dry-bulb temperatures:

Tm = (T1 × V1 + T2 × V2) / (V1 + V2)

Where:

  • Tm = mixed air dry-bulb temperature (°C or °F)
  • T1, T2 = dry-bulb temperatures of the two entering airstreams (°C or °F)
  • V1, V2 = volume flow rates of the two airstreams (m³/s, L/s, CFM, etc.)

The same formula applies for more than two streams: add each temperature multiplied by its flow, then divide by the sum of all flows. The key is that the flow units must be consistent (both in m³/s or both in CFM), and the temperatures must be in the same scale (both °C or both °F).

Worked Example

Using the default values from the calculator:

  • T1 = 35 °C (outdoor air), V1 = 0.5 m³/s
  • T2 = 22 °C (return air), V2 = 1.5 m³/s

Step 1: Multiply each temperature by its flow:

35 × 0.5 = 17.5

22 × 1.5 = 33.0

Step 2: Sum the products: 17.5 + 33.0 = 50.5

Step 3: Sum the flows: 0.5 + 1.5 = 2.0

Step 4: Divide: 50.5 / 2.0 = 25.25 °C

The calculator rounds to two decimals, giving 25.25 °C. This matches the first output line exactly.

Assumptions

  • The airstreams are at the same pressure (typical for atmospheric mixing in ducts).
  • The specific heat of air is constant and the same for both streams; this is valid for dry air near room temperature.
  • No heat is gained or lost from the duct walls during mixing (adiabatic mixing).
  • Volume flow rates are used as a proxy for mass flow rates. This is accurate when the densities of the two airstreams are similar, which is true for typical HVAC temperature differences (e.g., 10–20 °C). For extreme temperature differences, mass flow should be used.

When to Use This Formula

This formula is standard in HVAC design and troubleshooting. You use it when:

  • Determining the entering coil temperature for a cooling or heating coil, given the outdoor air and return air mix.
  • Calculating the supply air temperature when a ventilation airstream is mixed with recirculated air.
  • Estimating the temperature of air in a mixing box or plenum before it enters the filter or coil.
  • Checking if the mixed air temperature is within the range that prevents coil freezing or excessive humidity.

The result is a dry-bulb temperature, which is what a standard thermometer measures. It does not account for humidity or enthalpy, which are important for coil load calculations but not for the simple temperature mixing.

How to Choose Flow Units and Temperatures

You can use any consistent set of units, but the formula is unit-agnostic as long as you match them:

  • If you use CFM for both flows, the result is correct.
  • If you use m³/s for one and L/s for the other, you must convert one to the other first (1 m³/s = 1000 L/s).
  • For temperatures, mixing °C and °F will give a meaningless number. Convert to the same scale first.

In practice, most HVAC engineers use volume flow rates from duct traverses or anemometer readings. If the temperature difference between the streams is larger than about 30 °C, the density difference becomes significant, and you should use mass flow (kg/s) instead. Mass flow is found by multiplying volume flow by air density (about 1.2 kg/m³ at 20 °C and 101.325 kPa).

Common Mistakes and Misconceptions

  • Using average temperature without weighting: A simple average (e.g., (35+22)/2 = 28.5 °C) is wrong unless the flows are equal. The correct result is 25.25 °C in the example because the return air flow is three times larger.
  • Forgetting to convert units: Mixing m³/s with L/s, or °C with °F, is a frequent error. Always check that both flows are in the same unit and both temperatures in the same scale.
  • Assuming the formula gives enthalpy: The mixed air temperature is only the dry-bulb temperature. For coil load, you need the mixed air enthalpy, which also depends on humidity ratio. You cannot calculate that from temperature alone.
  • Ignoring duct heat gain: The formula assumes adiabatic mixing. In long uninsulated ducts, heat transfer from the surroundings can change the actual mixed temperature, especially if the duct is in a hot attic or cold crawlspace.

Limitations of the Formula

The formula is a simplification. It works well for typical building ventilation (outdoor air mixed with return air), but it has limits:

  • It assumes constant specific heat, which is fine for dry air between -10 °C and 50 °C, but less accurate if moisture content is very high or temperature extremes are present.
  • It ignores the effect of humidity on density. Moist air is less dense than dry air at the same temperature, so using volume flow without correcting for humidity can introduce a small error (usually under 2%).
  • It assumes complete mixing. In reality, stratification can occur in a mixing box if the streams are not well mixed, leading to temperature variations at the coil face. The formula gives the average, not the maximum or minimum.
  • For more than two streams, the formula extends naturally, but the accuracy depends on measuring each flow correctly.

For most design and troubleshooting work, the simple formula is sufficient. If you need more precision, use a psychrometric chart or software that accounts for humidity and density.

Frequently Asked Questions

Does the mixed air temperature formula work for more than two airstreams?

Yes. Extend the formula to Tm = (T1V1 + T2V2 + T3V3 + …) / (V1 + V2 + V3 + …). Each temperature is multiplied by its own flow, and the sum of products is divided by the total flow. The same unit consistency rules apply.

What if I only know the percentage of outdoor air, not the flow rates?

If you know the fraction of outdoor air (e.g., 20% outdoor air), you can write Tm = (0.20 × Toutdoor) + (0.80 × Treturn). This is the same formula with the flows normalized. For example, with 35 °C outdoor and 22 °C return at 20% outdoor air, Tm = 0.2×35 + 0.8×22 = 24.6 °C.

Does humidity affect the mixed air temperature?

Not directly for dry-bulb temperature. The formula gives the dry-bulb temperature of the mixture. However, humidity affects the enthalpy and density of the air. If you need the mixed air enthalpy (for coil load), you must use the humidity ratio of each stream, not just temperature. The dry-bulb temperature remains the same regardless of humidity.

Can I use this formula for mixing water or other fluids?

Yes, the same weighted-average formula applies to any fluid mixing, as long as you use mass flow rates (or volume if density is equal). For water, use mass flow (kg/s) for accuracy. The formula is a direct application of the first law of thermodynamics for adiabatic mixing with constant specific heat.

Why is my measured mixed air temperature different from the calculated one?

Common reasons include: inaccurate flow measurements, stratification (incomplete mixing), duct heat gain or loss, and sensor placement (the sensor may be in a stratified zone). Also, if the duct is leaky, outdoor air can infiltrate, changing the mix. Check your measurements and ensure the mixing is complete before the sensor.

What is the difference between mixed air temperature and supply air temperature?

Mixed air temperature is the temperature after mixing but before any heating or cooling coil. Supply air temperature is the temperature after the coil, which has been heated or cooled to meet the load. The coil changes the temperature, so they are different unless the coil is off.

Related

Formula used
in t1 | Temperature of airstream 1 | °C | 35 | -273.15 | 200
in v1 | Volume flow rate of airstream 1 | m³/s | 0.5 | 0 | 100
in t2 | Temperature of airstream 2 | °C | 22 | -273.15 | 200
in v2 | Volume flow rate of airstream 2 | m³/s | 1.5 | 0 | 100
out tm | Mixed air temperature | °C | (t1 * v1 + t2 * v2) / (v1 + v2) | 2
out ratio1 | Fraction of airstream 1 | - | v1 / (v1 + v2) | 3

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.