Multiplying mass flow rate (ṁ) by enthalpy change (ΔH) gives the rate of heat transfer (Q̇) in a steady-flow process, typically expressed in kilowatts (kW) or British thermal units per hour (Btu/h). You enter the mass flow rate (kg/s) and the specific enthalpy change (kJ/kg), and the calculator returns the heat transfer rate.
Formula
The fundamental relation is:
Q̇ = ṁ × Δh
Where:
- Q̇ = heat transfer rate (kW, kJ/s)
- ṁ = mass flow rate (kg/s)
- Δh = specific enthalpy change (kJ/kg) – the enthalpy difference between outlet and inlet
This is the steady-flow energy equation simplified for a single stream with no work, kinetic, or potential energy changes. It applies to heat exchangers, condensers, boilers, and mixing processes.
Worked Example
Using the default values: ṁ = 2.5 kg/s and Δh = 220 kJ/kg.
- Multiply: 2.5 × 220 = 550
- Result: Q̇ = 550 kW
- Convert to kJ/h: 550 × 3600 = 1,980,000 kJ/h
The calculator shows 550.0 kW and 1980000 kJ/h, matching exactly.
Assumptions
- Steady-state flow (no accumulation of mass or energy)
- Negligible kinetic and potential energy changes
- Single inlet and outlet, no shaft work (or work is accounted separately)
- Specific enthalpy change is constant across the process
When to Use This Calculation
You use Q̇ = ṁ × Δh whenever you need the total heat exchanged in a flowing stream. Common applications include:
- Sizing heat exchangers (shell-and-tube, plate, finned)
- Calculating boiler or condenser duty
- Estimating cooling load for a fluid loop
- Checking the heating/cooling capacity of a chiller or heat pump
- Analyzing steam or refrigerant cycles
For example, if water flows at 3 kg/s through a heater and its enthalpy rises by 150 kJ/kg, the heat added is 450 kW. That tells you the heater must supply 450 kJ every second.
How to Read the Result
The result is a power value – energy per unit time. A positive Q̇ means heat is added to the fluid (heating); a negative Q̇ means heat is removed (cooling). In the calculator, if you enter a negative Δh, the output will be negative, which is correct for cooling.
Always check units: mass flow in kg/s, enthalpy in kJ/kg, result in kW. If you have mass flow in kg/h, convert to kg/s by dividing by 3600 before multiplying.
Common Mistakes and Misconceptions
One frequent error is confusing specific enthalpy (kJ/kg) with total enthalpy (kJ). The formula requires specific enthalpy change – if you have total enthalpy, divide by the mass flow first.
Another mistake is mixing up mass flow with volumetric flow. If you know the volumetric flow (m³/s), multiply by density (kg/m³) to get mass flow. For water, density is about 998 kg/m³ at 20°C, but it varies with temperature and pressure.
Also, many people forget that Δh is a change, not an absolute value. For a heat exchanger, you use the enthalpy difference between the outlet and inlet of the same stream. If you have two streams (hot and cold), you apply the formula to each stream separately.
Practical Example: Air Heater
Suppose you heat air from 20°C to 80°C at a mass flow of 1.2 kg/s. The specific heat of air at constant pressure is about 1.005 kJ/(kg·K). The enthalpy change is:
Δh = cp × ΔT = 1.005 × (80 – 20) = 60.3 kJ/kg
Then Q̇ = 1.2 × 60.3 = 72.36 kW.
This matches the calculator if you enter 1.2 for mass flow and 60.3 for enthalpy change. Note that for gases, using cp is an approximation; for exact work, use property tables.
Limitations of the Formula
The simple product works only for a single stream with constant specific heat or when you have the actual enthalpy values. It assumes no significant kinetic or potential energy changes, which is valid for most heat exchangers but not for nozzles or diffusers. For those, you must include velocity terms.
For multi-component mixtures or phase changes, use the enthalpy values from thermodynamic tables or equations of state, not just cpΔT. For example, in a steam condenser, the enthalpy change is the latent heat of vaporization (about 2257 kJ/kg at 100°C), not a temperature difference.
Frequently Asked Questions
What is the difference between enthalpy and internal energy?
Enthalpy (H = U + pV) includes the work done to push the fluid into and out of the system. For flow processes, enthalpy is the relevant property because it accounts for flow work. Internal energy is used for closed systems.
Can I use this for liquids and gases?
Yes, as long as you have the correct specific enthalpy change. For liquids, Δh ≈ cpΔT (with cp in kJ/(kg·K)). For gases, use cp for constant pressure processes; for phase changes, use latent heat.
What if I have volumetric flow rate instead of mass flow?
Convert volumetric flow (V̇ in m³/s) to mass flow using density (ρ in kg/m³): ṁ = V̇ × ρ. Then apply the formula. For water, ρ ≈ 1000 kg/m³ at room temperature.
Why is the result in kW and not kJ?
Because you are multiplying kg/s (mass flow) by kJ/kg (enthalpy per mass), the kg cancels, leaving kJ/s, which is kilowatts. kW is a unit of power – energy per second.
Does the formula work for cooling as well as heating?
Yes. If the fluid loses enthalpy (Δh negative), Q̇ is negative, indicating heat removal. For example, in a chiller, the refrigerant absorbs heat, so Δh is positive for the refrigerant, while the water being cooled has a negative Δh.
How do I find the enthalpy change for steam?
Use steam tables or an online thermodynamic property calculator. Look up the specific enthalpy at the inlet and outlet conditions (pressure and temperature), then subtract. Do not use cpΔT for steam if there is a phase change.
Related
Formula used
in m | Mass flow rate | kg/s | 2.5 | 0 in dh | Specific enthalpy change | kJ/kg | 220 | -10000 out q | Heat transfer rate | kW | m * dh | 1 out qh | Heat transfer rate | kJ/h | q * 3600 | 0
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- Normality to g/L Converter & Formula29.220 g/L
- Normality to meq/mL Conversion Calculator1.0000 meq/mL
- Normality Test Q-Q Plot: How to Read It
- Normality Test Results: How to Analyze Them
- Normality Slay the Spire?
- Normality Test for Paired t Test: How to Check