The mixed air formula calculates the temperature (or enthalpy) of air after two or more airstreams combine in a ventilation system. You enter the airflow and temperature of each stream, and the formula returns the resulting mixed air temperature. This is essential for sizing cooling coils, predicting supply air conditions, and ensuring proper ventilation in HVAC design.
Formula
The mixed air temperature is a flow-weighted average of the individual stream temperatures:
Tmixed = (Q1 × T1 + Q2 × T2) / (Q1 + Q2)
Where:
- Q1, Q2 = volumetric airflow of each stream (L/s, m³/s, or cfm)
- T1, T2 = dry-bulb temperature of each stream (°C or °F)
This works because the enthalpy (heat content) of moist air is nearly proportional to temperature at typical HVAC conditions. For accurate enthalpy mixing, use the same formula with enthalpy values (kJ/kg) instead of temperature, but for most design work, temperature mixing is sufficient.
Worked Example
Using the calculator defaults: return air at 24 °C with 500 L/s, and outdoor air at 35 °C with 150 L/s.
- Multiply each flow by its temperature: 500 × 24 = 12,000; 150 × 35 = 5,250
- Sum the products: 12,000 + 5,250 = 17,250
- Sum the flows: 500 + 150 = 650 L/s
- Divide: 17,250 / 650 = 26.538… ≈ 26.54 °C
The mixed air temperature is 26.54 °C, which matches the calculator output.
Assumptions
- Steady-state flow: both streams are constant.
- No heat loss or gain in the mixing plenum.
- Air density is constant across streams (acceptable for temperature differences under ~30 °C).
- No moisture condensation during mixing (sensible heat only).
When to Use the Mixed Air Formula
This formula appears in nearly every HVAC design and energy calculation. Common applications include:
- Economizer operation: Determine if outdoor air can cool the building without mechanical cooling.
- Coil sizing: The mixed air temperature is the entering condition for cooling and heating coils.
- Ventilation load: Calculate the load imposed by bringing in outdoor air.
- Duct design: Predict temperatures after confluence points in ductwork.
For example, a 10,000 cfm system with 20% outdoor air at 95 °F and return air at 75 °F will have a mixed air temperature of 79 °F. This tells the designer whether the cooling coil needs to handle 79 °F or 95 °F entering air.
How to Choose the Right Flow Units
The formula is unit-agnostic as long as you use the same unit for both flows. Common choices:
- L/s (liters per second) – metric HVAC, common in Europe and Asia.
- m³/s (cubic meters per second) – SI standard for large systems.
- cfm (cubic feet per minute) – imperial, common in North America.
If you mix units, the result will be wrong. Convert all flows to one unit first. For temperature, use either °C or °F consistently; the formula works with both because it’s a linear average.
Common Mistakes and Misconceptions
A frequent error is using the outdoor air fraction incorrectly. The mixed temperature is not simply the average of the two temperatures; it’s weighted by flow. For example, if outdoor air is 10% of the total flow, it contributes only 10% of the temperature difference.
Another misconception is that the formula works for humidity ratio or relative humidity. It does not – those are not conserved in the same linear way. Use a psychrometric chart or enthalpy formula for moisture-related mixing.
Also, be careful with units: a 10 °C difference is 18 °F, so never mix Celsius and Fahrenheit in the same calculation.
Limits of the Formula
The simple temperature mixing formula ignores the latent heat of moisture. If the two airstreams have very different humidity levels, the true mixed enthalpy will be slightly different from the temperature-based estimate. For most HVAC design, the error is small (< 5%), but for precise energy modeling, use the enthalpy-weighted method:
hmixed = (Q1 × h1 + Q2 × h2) / (Q1 + Q2)
where h is specific enthalpy (kJ/kg dry air). This requires psychrometric data, but gives a more accurate result for coil loads.
Frequently Asked Questions
What is the mixed air formula for three or more streams?
Extend the same pattern: sum (flow × temperature) for all streams, then divide by the total flow. For example, with three streams: (Q1T1 + Q2T2 + Q3T3) / (Q1 + Q2 + Q3).
Does the mixed air formula work for enthalpy?
Yes, if you replace temperature with specific enthalpy (kJ/kg or Btu/lb). The formula is the same because enthalpy is a conserved property in adiabatic mixing. Use a psychrometric chart to find enthalpy values.
Why is my mixed air temperature different from what I measured?
Measurement errors, heat gain from duct walls, and stratification (incomplete mixing) are common causes. Also, if the flow readings are inaccurate, the calculation will be off. Ensure the temperature sensor is placed far enough downstream to allow complete mixing.
Can I use this formula for exhaust air and supply air?
Yes, as long as you are mixing two airstreams physically. For example, in a heat recovery ventilator, you might mix a portion of exhaust air with fresh air – the same formula applies.
What is the difference between mixed air temperature and supply air temperature?
Mixed air is the temperature after mixing but before any heating or cooling. Supply air is the conditioned air delivered to the space, after passing through coils. The mixed air temperature is the entering condition for the coil, and the supply temperature is the leaving condition.
How do I account for altitude or air density?
For most HVAC applications, the volumetric flow method is sufficient. At high altitudes, air density is lower, so mass flow is less for the same volumetric flow. For precise work, use mass flow (kg/s) instead of volumetric flow, but the temperature result will be nearly identical because the density cancels out in the weighted average.
Related
Formula used
in q1 | Flow rate stream 1 | L/s | 500 | 0 in t1 | Temperature stream 1 | °C | 24 | -273.15 in q2 | Flow rate stream 2 | L/s | 150 | 0 in t2 | Temperature stream 2 | °C | 35 | -273.15 out tm | Mixed air temperature | °C | (q1 * t1 + q2 * t2) / (q1 + q2) | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- Normality to g/L Converter & Formula29.220 g/L
- Normality to meq/mL Conversion Calculator1.0000 meq/mL
- Normality Test Q-Q Plot: How to Read It
- Normality Test Results: How to Analyze Them
- Normality Slay the Spire?
- Normality Test for Paired t Test: How to Check