Enthalpy of Moist Air Formula & How to Use It

Calculator No. 01-6840 · Updated · Formula and assumptions shown below

The calculator on this page is switched off while it is checked. The formula is below, and the worked example shows how to do the sum by hand.

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

The enthalpy of moist air is the total heat content per unit mass of dry air, including the sensible heat of the dry air and water vapor plus the latent heat of the water vapor. You calculate it with the formula h = 1.006·T + W·(2501 + 1.86·T) kJ/kg dry air, where T is the temperature in °C and W is the humidity ratio in kg water/kg dry air. This formula is the standard psychrometric expression used in HVAC design, drying processes, and cooling tower calculations.

Formula

The enthalpy of moist air combines three contributions:

  • Sensible heat of dry air: 1.006·T (kJ per kg of dry air), where 1.006 kJ/(kg·K) is the specific heat of dry air at constant pressure.
  • Sensible heat of water vapor: 1.86·W·T (kJ per kg dry air), where 1.86 kJ/(kg·K) is the specific heat of water vapor.
  • Latent heat of vaporization: 2501·W (kJ per kg dry air), where 2501 kJ/kg is the latent heat of vaporization of water at 0 °C.

Thus the full expression is:

h = 1.006·T + W·(2501 + 1.86·T)

where:

  • h – specific enthalpy of moist air, kJ per kg of dry air (not per kg of moist air)
  • T – dry-bulb temperature, °C
  • W – humidity ratio (also called specific humidity), kg water vapor per kg dry air

The humidity ratio itself is computed from relative humidity and pressure:

W = 0.622·(φ·pws) / (p − φ·pws)

where φ is relative humidity (as a fraction, e.g., 0.5 for 50%), pws is the saturation vapor pressure of water at temperature T (kPa), and p is total atmospheric pressure (kPa). The constant 0.622 is the ratio of the molar mass of water (18.015 g/mol) to the molar mass of dry air (28.97 g/mol).

Worked Example

Calculate the enthalpy of moist air at 25 °C, 50% relative humidity, and standard atmospheric pressure (101.325 kPa).

  1. Find saturation vapor pressure pws at 25 °C. Using the Antoine equation for water (valid 0–60 °C):
    pws = exp(16.6536 − 4030.183 / (T + 235.0)) = exp(16.6536 − 4030.183 / 260.0) = exp(16.6536 − 15.5007) = exp(1.1529) = 3.169 kPa
  2. Compute humidity ratio W:
    W = 0.622·(0.50 × 3.169) / (101.325 − 0.50 × 3.169) = 0.622 × 1.5845 / (101.325 − 1.5845) = 0.9856 / 99.7405 = 0.00988 kg/kg
  3. Compute enthalpy h:
    h = 1.006 × 25 + 0.00988 × (2501 + 1.86 × 25) = 25.15 + 0.00988 × (2501 + 46.5) = 25.15 + 0.00988 × 2547.5 = 25.15 + 25.17 = 50.32 kJ/kg dry air

The calculator gives 50.32 kJ/kg dry air, matching the step-by-step result.

Assumptions

  • Moist air behaves as an ideal gas mixture (valid at typical atmospheric conditions).
  • The reference state for enthalpy is 0 °C for dry air and 0 °C liquid water for the latent heat term.
  • The specific heats (1.006 and 1.86 kJ/(kg·K)) and latent heat (2501 kJ/kg) are treated as constant over the temperature range –40 °C to 60 °C.
  • Saturation vapor pressure is calculated using the Antoine equation, which is accurate to within about 0.1% over 0–60 °C.
  • Total pressure is the ambient barometric pressure, assumed constant.

Why the Enthalpy of Moist Air Matters

In HVAC engineering, enthalpy is the key quantity for sizing cooling coils, calculating the load of air conditioning systems, and designing cooling towers. When air is cooled below its dew point, water condenses and releases latent heat; the enthalpy change tells you how much heat the cooling coil must remove. Similarly, in drying processes (grain, lumber, textiles), the enthalpy of the air determines how much moisture it can absorb and how much energy is needed to heat the air. Psychrometric charts plot enthalpy as diagonal lines, allowing quick graphical estimates.

How to Use the Calculator

  1. Enter the dry-bulb temperature in °C (range –40 to 60 °C).
  2. Enter the relative humidity in % (0 to 100).
  3. Enter the atmospheric pressure in kPa (typical sea level is 101.325 kPa; at altitude it is lower, e.g., 89.9 kPa at 1000 m).
  4. Read the humidity ratio (kg water/kg dry air) and the enthalpy (kJ/kg dry air) as outputs.

Note that the enthalpy is per kilogram of dry air, not per kilogram of moist air. This is the standard convention in psychrometrics because the amount of dry air remains constant during heating, cooling, humidification, or dehumidification processes, while the water vapor content changes.

Common Mistakes and Misconceptions

  • Using °C in the latent heat term incorrectly: The latent heat 2501 kJ/kg is at 0 °C; the term 1.86·T corrects it to the actual temperature. Some simplified formulas use 2501 only, which introduces errors at high temperatures.
  • Confusing humidity ratio with relative humidity: Relative humidity is a percentage of saturation; humidity ratio is an absolute mass ratio. You cannot substitute RH directly into the enthalpy formula.
  • Forgetting pressure: At higher altitudes, the same RH and temperature give a lower humidity ratio because total pressure is lower, reducing the partial pressure of water vapor. Always use the local barometric pressure.
  • Using kJ/kg of moist air: If you need the enthalpy per kg of moist air, you must divide by (1 + W). The calculator gives per kg dry air, which is the standard for process calculations.

Limits of the Formula

The formula assumes ideal gas behavior, which is excellent for air at atmospheric conditions. It also assumes constant specific heats; over the range –40 °C to 60 °C the error is less than 0.5%. At very high temperatures (above 100 °C) or very high pressures, the ideal gas assumption breaks down and more complex equations of state are needed. Also, the Antoine equation for saturation vapor pressure is only valid for liquid water; below 0 °C, the saturation pressure over ice is different (slightly lower), so the calculator may overestimate humidity ratio at sub-zero temperatures. For precise work below 0 °C, use the saturation pressure over ice (e.g., the Goff-Gratch equation).

Frequently Asked Questions

What is the difference between enthalpy and temperature?

Temperature measures the average kinetic energy of molecules, while enthalpy measures the total heat content, including both sensible heat (related to temperature) and latent heat (related to phase changes). Two air samples at the same temperature can have very different enthalpies if one is humid and the other is dry, because the humid air contains additional latent heat in the water vapor.

Why is the enthalpy per kg of dry air, not per kg of moist air?

Because in air conditioning processes, the amount of dry air remains constant while water vapor is added or removed. Using per kg of dry air makes energy balances simpler: you multiply the enthalpy difference by the mass flow rate of dry air, which you can measure directly. If you used per kg of moist air, the mass flow rate would change as moisture is added or removed.

How do I convert enthalpy from kJ/kg to Btu/lb?

Multiply by 0.4299 (since 1 kJ/kg = 0.4299 Btu/lb). For example, 50.32 kJ/kg × 0.4299 = 21.63 Btu/lb dry air. This conversion is useful when working with US customary units.

Does the formula work for humid air at high altitudes?

Yes, as long as you enter the correct atmospheric pressure. The humidity ratio formula includes pressure in the denominator, so at lower pressure (higher altitude), the humidity ratio decreases for the same temperature and relative humidity. The enthalpy formula itself does not explicitly include pressure, but it uses the humidity ratio, which already accounts for pressure.

What is the enthalpy of saturated air?

Saturated air has 100% relative humidity, so the humidity ratio is the maximum possible at that temperature. You can calculate it by setting RH = 100% in the calculator. For example, at 30 °C and 100% RH, the enthalpy is about 100 kJ/kg dry air, which is much higher than at 50% RH because of the extra latent heat.

Related

Formula used
in t | Dry-bulb temperature | °C | 25 | -40 | 60
in rh | Relative humidity | % | 50 | 0 | 100
in p | Atmospheric pressure | kPa | 101.325 | 50 | 110
out W | Humidity ratio | kg/kg | 0.622 * (rh/100 * psat(t)) / (p - rh/100 * psat(t)) | 4
out h | Enthalpy of moist air | kJ/kg dry air | 1.006 * t + W * (2501 + 1.86 * t) | 2

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.