Mixed Air Formula: Calculate Supply Temp & Humidity

Calculator No. 01-6872 · Updated · Formula and assumptions shown below

Mixed air temperature 26.88 °C
Flow ratio of stream 1
0.375
Result, rounded to 3 decimal places
Temperature of airstream 1
35 °C
Set in the form below
Temperature of airstream 2
22 °C
Set in the form below
You enter
Temperature of airstream 1 (°C), Temperature of airstream 2 (°C), Flow rate of airstream 1 (m³/s), Flow rate of airstream 2 (m³/s)
You get
Mixed air temperature (°C), Flow ratio of stream 1
Rounding
2 dp · 3 dp

For study and lab planning. The result follows from the numbers you enter and the formula shown. Check it against your method before you weigh, mix or dilute anything, follow the safety data sheet and your supervisor, and do not use it for clinical, dosing or medication work.

The mixed air formula calculates the temperature and humidity of air after two or more airstreams combine, typically outdoor air mixed with return air in an HVAC system. You enter the dry-bulb temperature and humidity ratio (or enthalpy) of each airstream along with their respective volumetric flow rates, and the calculator returns the resulting mixed air temperature and humidity ratio. The calculation is a flow-weighted average of the individual airstream properties.

Formula

The mixed air temperature is the weighted arithmetic mean of the individual dry-bulb temperatures, weighted by the mass or volumetric flow rate of each airstream:

Tmixed = (T1 × Q1 + T2 × Q2) / (Q1 + Q2)

Where:

  • T1, T2 = dry-bulb temperatures of the two airstreams (°C or °F, must be consistent)
  • Q1, Q2 = volumetric flow rates of the two airstreams (m³/s, L/s, CFM, etc., must be consistent)

The same formula applies to humidity ratio (kg water per kg dry air) or enthalpy (kJ/kg). For more than two airstreams, extend the numerator and denominator with each additional stream.

Worked Example

Using the default values from the calculator:

  • Airstream 1: outdoor air at 35 °C, flow 1.5 m³/s
  • Airstream 2: return air at 22 °C, flow 2.5 m³/s

Step 1: Multiply each temperature by its flow:

35 × 1.5 = 52.5

22 × 2.5 = 55.0

Step 2: Sum the products: 52.5 + 55.0 = 107.5

Step 3: Sum the flows: 1.5 + 2.5 = 4.0 m³/s

Step 4: Divide: 107.5 / 4.0 = 26.875 °C

The calculator rounds to two decimals, giving 26.88 °C as the mixed air temperature. The flow ratio of stream 1 is 1.5 / 4.0 = 0.375 (37.5%).

Assumptions

  • The airstreams are at constant pressure and no heat is lost or gained from duct walls (adiabatic mixing).
  • Air behaves as an ideal gas, and the specific heat of dry air is constant over the temperature range.
  • Volumetric flow rates are measured at the same conditions (typically standard air density). If flows are given at different temperatures, convert to mass flow for accuracy.
  • For humidity ratio or enthalpy, the same flow-weighting applies, but you must use the same units for each stream.

When to Use the Mixed Air Formula

HVAC engineers and technicians use this calculation to predict the condition of air entering a cooling coil or heating coil after outdoor ventilation air mixes with return air from the building. This is essential for:

  • Sizing cooling and heating coils based on the actual entering air temperature.
  • Determining economizer performance when outdoor air can be used for free cooling.
  • Calculating the mixed air humidity ratio to avoid condensation or mold issues.
  • Balancing minimum outdoor air requirements with energy recovery decisions.

The same principle applies to mixing two process airstreams in industrial ventilation, laboratory exhaust systems, or greenhouse climate control.

How to Read the Result

The mixed air temperature always lies between the two entering temperatures. If the outdoor air is 35 °C and return air is 22 °C, the mixed temperature will be closer to the stream with the larger flow. In the example, the return air flow is larger (2.5 vs 1.5 m³/s), so the mixed temperature (26.88 °C) is closer to 22 °C than to 35 °C.

If you also know the humidity ratio of each stream, apply the same weighted average to get the mixed humidity ratio. Then use a psychrometric chart to find relative humidity or dew point. The mixed air enthalpy is similarly a flow-weighted average, which is useful for energy calculations.

Common Mistakes and Misconceptions

  • Using different units for flow: You must convert all flows to the same unit (e.g., L/s to m³/s) before averaging. The calculator does not do this for you.
  • Mixing temperatures with humidity: The formula for temperature is independent of humidity, but the humidity ratio must be averaged separately. Do not average relative humidity directly—it is not a conserved property.
  • Ignoring density differences: For precise work, especially when temperatures differ greatly, use mass flow (kg/s) instead of volumetric flow. The calculator assumes constant density; for most HVAC applications this is acceptable.
  • Rounding too early: Keep at least three significant figures in intermediate steps to avoid error in the final result.

Limits of the Formula

The formula is a simple mixing model. It does not account for:

  • Heat gain or loss from duct walls, fans, or solar radiation.
  • Moisture added or removed by humidifiers, dehumidifiers, or condensation on coils.
  • Pressure differences between airstreams, which can cause one stream to dominate.
  • Non-ideal behavior at extreme temperatures or very high humidity.

For accurate coil selection, use the mixed air conditions as an input to a manufacturer’s coil selection program, which accounts for coil geometry and refrigerant conditions.

Frequently Asked Questions

Q: Can I use the mixed air formula for more than two airstreams?
Yes. Extend the formula: Tmixed = (T1Q1 + T2Q2 + T3Q3) / (Q1+Q2+Q3). The same pattern works for any number of streams.

Q: What is the difference between mixed air temperature and supply air temperature?
Mixed air is the temperature after mixing but before any heating or cooling coil. Supply air is the temperature after the coil has heated or cooled the mixed air. The coil changes the temperature, so they are rarely the same.

Q: Should I use volumetric or mass flow in the formula?
For most HVAC work, volumetric flow is fine because air density is roughly constant. For high precision (e.g., lab exhaust with large temperature differences), convert to mass flow by multiplying volumetric flow by air density (kg/m³) at each stream’s condition.

Q: How do I find the mixed air humidity ratio?
Use the same weighted average with the humidity ratio (kg water/kg dry air) of each stream. You can get humidity ratio from a psychrometric chart or from a calculator using dry-bulb and wet-bulb temperatures.

Q: Why does the mixed air temperature not equal the average of the two temperatures?
Because the average is weighted by flow. If one airstream has a much higher flow rate, it pulls the mixed temperature closer to its own temperature. The simple arithmetic average would only be correct if both flows were equal.

Q: Does the formula work for mixing air with different pressures?
No. The formula assumes a single constant pressure. If pressures differ significantly, you must account for the energy change due to pressure difference, which is beyond simple mixing.

Practical Tips for HVAC Work

  • Always verify the flow units on the building management system or duct traversals—mixing up CFM and L/s will ruin the calculation.
  • When measuring outdoor air temperature, shield the sensor from direct sunlight and rain.
  • For economizer control, compare the outdoor air enthalpy to return air enthalpy, not just temperature, to decide when free cooling is beneficial.
  • Follow your lab method, the safety data sheet (SDS) and your supervisor when performing any physical measurements or duct work.

Related

Formula used
in t1 | Temperature of airstream 1 | °C | 35 | -273.15
in t2 | Temperature of airstream 2 | °C | 22 | -273.15
in f1 | Flow rate of airstream 1 | m³/s | 1.5 | 0
in f2 | Flow rate of airstream 2 | m³/s | 2.5 | 0
out tm | Mixed air temperature | °C | (t1 * f1 + t2 * f2) / (f1 + f2) | 2
out r | Flow ratio of stream 1 | - | f1 / (f1 + f2) | 3

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work