Mixed air temperature is the temperature of the air after two or more airstreams combine, such as outdoor fresh air mixing with return air in an HVAC system. You calculate it using a weighted average based on the mass (or volume) flow rate of each stream: Tmixed = (T1×Q1 + T2×Q2) ÷ (Q1 + Q2), where T is dry-bulb temperature and Q is airflow. Enter the two temperatures and their flow rates below to get the resulting mixed temperature instantly.
Formula
The mixed air temperature is a flow-weighted arithmetic mean of the individual airstream dry-bulb temperatures. The general formula for any number of streams is:
Tmixed = (Σ Ti × Qi) ÷ (Σ Qi)
Where:
- Ti = dry-bulb temperature of stream i (°C or °F, but consistent)
- Qi = volumetric airflow of stream i (m³/h, L/s, or ft³/min, but consistent)
- Σ = sum over all airstreams
For two streams, this expands to Tmixed = (T1Q1 + T2Q2) / (Q1 + Q2). The result is always between the two input temperatures, closer to the temperature of the stream with the larger flow. The same formula works with mass flow (kg/s) instead of volumetric flow, and in HVAC practice the two are often treated interchangeably because air density differences are small at typical duct temperatures.
Worked Example
Using the calculator defaults: Airstream 1 is outdoor air at 35 °C with a flow of 1000 m³/h. Airstream 2 is return air at 22 °C with a flow of 2000 m³/h.
Step 1: Multiply each temperature by its flow.
Stream 1: 35 × 1000 = 35,000 °C·m³/h
Stream 2: 22 × 2000 = 44,000 °C·m³/h
Step 2: Add the products.
35,000 + 44,000 = 79,000 °C·m³/h
Step 3: Add the flows.
1000 + 2000 = 3000 m³/h
Step 4: Divide.
79,000 ÷ 3000 = 26.33 °C
The mixed air temperature is 26.33 °C (79.4 °F). The calculator rounds to two decimals, matching this result.
Assumptions
- Steady-state conditions: the temperatures and flows do not change during the measurement.
- Complete mixing: the streams are fully blended before the temperature is sensed.
- Constant air density: volumetric flow is used as a proxy for mass flow, which is accurate to within a few percent for typical HVAC temperature ranges (10–40 °C).
- No heat transfer to or from the duct walls, and no moisture condensation or evaporation affecting the dry-bulb temperature.
- Dry-bulb temperature is used; wet-bulb or enthalpy mixing requires a psychrometric chart.
Why Mixed Air Temperature Matters
HVAC designers and technicians use the mixed air temperature to size cooling and heating coils, set economizer damper positions, and predict coil performance. For example, an air handling unit that draws 20% outdoor air at 35 °C and 80% return air at 24 °C will see a mixed temperature of about 26.2 °C. The cooling coil must cool that mixture, not the outdoor air alone, so using the wrong value leads to oversized or undersized equipment.
Mixed air temperature also helps diagnose economizer problems. If the measured mixed temperature is much higher than the calculated value, the outdoor air damper may be stuck open, or the return air damper may be closed. If it is lower, the opposite is likely. A quick field check with a thermometer and the formula above tells you whether the dampers are doing their job.
Common Mistakes and Pitfalls
- Using temperatures in different units. Convert everything to °C or everything to °F before calculating. Mixing them produces nonsense.
- Using different flow units. Both flows must be in the same unit (m³/h, L/s, cfm). Convert first.
- Forgetting that flow weights the average. The result is not (T1 + T2)/2 unless the flows are equal.
- Measuring at the wrong location. The sensor must be downstream of the mixing point, far enough for turbulence to blend the air. Measuring too close to a damper gives a reading biased toward one stream.
- Ignoring humidity. Dry-bulb mixing is correct for temperature, but enthalpy (total heat) mixing is different. If you are calculating coil load, use wet-bulb or enthalpy values, not dry-bulb alone.
How to Choose the Right Flow Measurement
For the formula to be accurate, use the actual airflow at the mixing point, not the design airflow. Field measurements from a pitot tube traverse, a flow hood, or an anemometer are more reliable than nameplate ratings. In many systems, the outdoor airflow is not directly measured; it is calculated as the difference between supply and return flows. That difference is valid as long as the building is not heavily pressurized or depressurized.
When the system has more than two streams, sum all of them. For example, a unit with outdoor air, return air, and a small exhaust makeup stream uses the same formula with three terms in the numerator and three in the denominator. The calculator above handles two streams, which covers most applications; for more, extend the pattern.
Limits of the Simple Formula
The arithmetic average assumes constant specific heat and constant density across all streams. Over a typical HVAC range (0–50 °C), the error from density variation is under 3%. For extreme temperatures (e.g., mixing 300 °C exhaust with 20 °C air), density differences become significant and you must use mass flow rates in kg/s, obtained by multiplying volumetric flow by density at each stream’s temperature. Similarly, if the airstreams have very different humidities, the dry-bulb temperature mixing is still correct, but the wet-bulb temperature of the mixture cannot be found with this formula; you need a psychrometric chart or an enthalpy-weighted calculation.
Another limit: the formula gives the temperature after complete mixing. Real ducts have stratification, so a single sensor may read a value that differs from the theoretical average by several degrees. For control purposes, multiple sensors or an averaging sensor are recommended.
Frequently Asked Questions
Does mixed air temperature equal the average of the two temperatures? Only when the two flow rates are equal. If one stream has more airflow, the mixed temperature sits closer to that stream’s temperature. With 1000 m³/h at 35 °C and 2000 m³/h at 22 °C, the result is 26.3 °C, not 28.5 °C.
Can I use cfm and °F with this formula? Yes, as long as both flows are in cfm and both temperatures are in °F. The formula is unit-agnostic; just keep each variable consistent. The calculator above accepts °C and m³/h, but you can convert your inputs first.
Why does my measured mixed temperature differ from the calculated one? Usually because of incomplete mixing (sensor too close to the dampers), inaccurate flow measurements, or a leaking damper that lets outdoor air in when it should be closed. Check the sensor location first, then verify the flows with a direct measurement.
Should I use dry-bulb or wet-bulb temperature for mixing? For the physical air temperature, use dry-bulb. For coil load or enthalpy calculations, use wet-bulb or enthalpy. Mixing dry-bulb temperatures gives the correct final dry-bulb temperature, but it does not give the correct final wet-bulb temperature because latent heat is involved.
What if I have three or four airstreams? Extend the formula: multiply each temperature by its flow, add all the products, then divide by the sum of all flows. The calculator above handles two streams, but the math scales directly to any number.
Related
Formula used
in t1 | Temperature of airstream 1 | °C | 35 | -273.15 | 200 in q1 | Airflow of airstream 1 | m³/h | 1000 | 0 | 100000 in t2 | Temperature of airstream 2 | °C | 22 | -273.15 | 200 in q2 | Airflow of airstream 2 | m³/h | 2000 | 0 | 100000 out tm | Mixed air temperature | °C | (t1 * q1 + t2 * q2) / (q1 + q2) | 2 out tmF | Mixed air temperature | °F | (tm * 9/5) + 32 | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- How to Find the Continuous Decay Rate
- Total Constant of Decay: How to Calculate It0.000121 1/s
- How to Calculate Decay Constant0.000121 1/s
- Half Life GitHub: What It Is and How to Use It
- Decay Constant: How to Calculate It0.000121 1/s
- Half-Life Games in Order: Full Release Timeline