The mixed air temperature equation calculates the temperature of air after two or more airstreams combine, typically outdoor air and return air in an HVAC system. You enter the dry-bulb temperature and airflow (or mass flow) of each stream, and the calculator returns the resulting mixture temperature in °C or °F. The formula is a flow-weighted average: Tmixed = (T1·Q1 + T2·Q2) / (Q1 + Q2), where Q is the volumetric flow rate (e.g., L/s or cfm) or mass flow rate.
Formula
For two airstreams, the mixed air temperature is:
Tm = (T1·Q1 + T2·Q2) / (Q1 + Q2)
- Tm = mixed air temperature (°C or °F)
- T1, T2 = dry-bulb temperatures of the two streams (°C or °F)
- Q1, Q2 = volumetric airflow rates (L/s, m³/s, cfm) or mass flow rates (kg/s)
The equation works for any number of streams: sum of (temperature × flow) for each stream, divided by the total flow. It assumes the air streams are at the same pressure and that no heat is lost or gained during mixing—an adiabatic process. For HVAC design, the same formula applies to humidity ratio and enthalpy, not just temperature, when using a psychrometric chart.
Worked Example
Using the calculator defaults: return air at 22 °C with 500 L/s, outdoor air at 35 °C with 200 L/s.
- Multiply each temperature by its flow: 22 × 500 = 11,000 °C·L/s; 35 × 200 = 7,000 °C·L/s
- Sum the products: 11,000 + 7,000 = 18,000 °C·L/s
- Sum the flows: 500 + 200 = 700 L/s
- Divide: 18,000 / 700 = 25.714 °C
The mixed air temperature is 25.71 °C (rounded to two decimals). This matches the calculator output. Notice the result is closer to the return air temperature because the return air flow is larger—the mixture is weighted by flow, not simply averaged.
Assumptions
- Adiabatic mixing: no heat transfer to or from the surroundings.
- Constant pressure and no phase change (no condensation or evaporation).
- Air behaves as an ideal gas with constant specific heat—valid for typical HVAC temperature ranges.
- Volumetric flow rates are measured at the same conditions; if not, use mass flow rates instead.
How to Choose the Right Flow Rates
In practice, you rarely measure mixed air directly. Instead, you know the outdoor air intake flow (from damper position or a flow hood) and the return air flow (supply flow minus outdoor flow). The supply fan flow is usually the total. For example, if a supply fan moves 1,000 L/s and the outdoor air damper is set for 20% outdoor air, then Qoutdoor = 200 L/s and Qreturn = 800 L/s. Use those values in the equation.
When the two streams have different densities—e.g., very cold outdoor air vs. warm return air—mass flow is more accurate. Convert volumetric flow to mass flow by multiplying by density (ρ = P/(R·T), where P is absolute pressure, R is the specific gas constant for dry air ≈ 287 J/(kg·K), and T is absolute temperature in kelvin). For most building HVAC work, the error from using volumetric flow is under 1–2%, so it is commonly ignored.
Common Mistakes and Misconceptions
- Using a simple average: (T1+T2)/2 only works when both flows are equal. With unequal flows, the larger flow dominates.
- Mixing °C and °F: The equation is linear, so you can use either unit as long as you are consistent. But never mix units in the same calculation.
- Forgetting to convert L/s to m³/s: The ratio Q1/Q2 is what matters, so as long as both flows use the same unit, the result is correct. However, if you later use the mixed flow for other calculations (e.g., coil load), keep consistent units.
- Assuming the result is the wet-bulb temperature: The mixed air temperature is a dry-bulb temperature. The mixed wet-bulb or enthalpy requires a psychrometric calculation using humidity ratios, not just temperatures.
- Ignoring duct heat gain: The equation gives the theoretical mixing temperature; actual temperature at the mixing box may differ due to fan heat or duct losses.
Why It Matters in HVAC Design
Mixed air temperature is a key input for sizing cooling and heating coils. For a cooling coil, the entering air temperature is often the mixed air temperature. A higher mixed temperature increases the coil load. For example, in a hospital or laboratory with high outdoor air requirements (say 100% outdoor air), the mixed temperature equals the outdoor temperature, so the coil must handle the full outdoor load. In a typical office with 20% outdoor air, the mixed temperature is moderated by the return air, reducing coil size and energy use.
Building energy codes often require economizers that increase outdoor air when it is cool—the mixed air equation helps predict the resulting supply temperature. It is also used to verify that the outdoor air fraction meets ventilation standards (e.g., ASHRAE 62.1). By measuring the mixed, return, and outdoor temperatures, you can back-calculate the actual outdoor air fraction: Qoa/Qtotal = (Tmixed − Treturn) / (Toutdoor − Treturn).
Limitations and When to Use Mass Flow
The simple volumetric equation breaks down when the temperature difference between streams is large (over ~30 °C) or when altitude causes significant density differences. For example, mixing 40 °C outdoor air with 10 °C return air at sea level gives a small error, but at 3,000 m elevation, the density difference is larger. In such cases, use mass flow rates:
Tm = (T1·ṁ1 + T2·ṁ2) / (ṁ1 + ṁ2)
where ṁ is mass flow in kg/s. To get mass flow, multiply volumetric flow by density at the stream’s temperature and pressure. For most building applications, the volumetric version is accurate enough, but for industrial processes or high-altitude locations, use mass flow.
Frequently Asked Questions
What is the difference between mixed air temperature and supply air temperature?
Mixed air temperature is the temperature after outdoor and return air combine, before any heating or cooling. Supply air temperature is the temperature after the coil (heating or cooling) and fan. The supply temperature is what enters the occupied space; the mixed temperature is what enters the coil.
Can I use the same equation for more than two airstreams?
Yes. Extend the formula: sum (Ti·Qi) for all streams, then divide by the sum of Qi. For example, three streams: (T1Q1 + T2Q2 + T3Q3) / (Q1+Q2+Q3).
Does the mixed air equation work for humidity or wet-bulb temperature?
Not directly. For humidity ratio (grams of water per kg of dry air), the same flow-weighted average works because it is a conserved quantity. For wet-bulb temperature or enthalpy, you must first calculate the mixed humidity ratio and mixed dry-bulb temperature, then find the wet-bulb from a psychrometric chart or formula—it is not a simple average.
Why does my measured mixed air temperature differ from the calculated value?
Common reasons: duct heat gain or loss, fan heat (especially if the mixed air sensor is downstream of the fan), stratification (poor mixing in the duct), and sensor error. The equation assumes perfect mixing and adiabatic conditions; real systems have inefficiencies. A difference of 1–2 °C is typical.
What if the two airflows have different pressures?
The equation assumes both streams are at the same static pressure. In practice, outdoor air and return air may have different pressures, but after mixing, the pressure equalizes. The energy balance still holds if you use mass flow rates and account for any pressure changes—but for HVAC design, the pressure difference is usually small enough to ignore.
Is the mixed air temperature the same as the average of the two temperatures?
Only if both airflows are equal. If Q1 = Q2, then Tm = (T1+T2)/2. With unequal flows, the larger flow has more influence—the result is a weighted average, not a simple one.
Related
Formula used
in t1 | Temperature of stream 1 | °C | 22 | -273.15 | 200 in q1 | Airflow of stream 1 | L/s | 500 | 0 | 10000 in t2 | Temperature of stream 2 | °C | 35 | -273.15 | 200 in q2 | Airflow of stream 2 | L/s | 200 | 0 | 10000 out tm | Mixed air temperature | °C | (t1 * q1 + t2 * q2) / (q1 + q2) | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation with the constants and conversion factors written on the page, rounded as each result states. See method and constants, the disclaimer or report an error.
More in this section
- How to Find the Continuous Decay Rate
- Total Constant of Decay: How to Calculate It0.000121 1/s
- How to Calculate Decay Constant0.000121 1/s
- Half Life GitHub: What It Is and How to Use It
- Decay Constant: How to Calculate It0.000121 1/s
- Half-Life Games in Order: Full Release Timeline